1. Product Overview
The GEYA GRT6-M Multifunction Time Relay is a versatile device designed for precise time control in various applications, including electrical appliances, lighting, heating, motors, pumps, and fans. It offers 10 distinct time functions and 10 time ranges, operating across multiple voltage inputs. Its compact 1-MODULE (18mm) design allows for convenient DIN rail mounting.
Key features include:
- 10 Function Modes: 5 time functions controlled by supply voltage (A, B, C, D, J), 4 time functions controlled by control input (E, F, G, H), and 1 function of latching relay (I).
- Wide Voltage Range: Available in AC230V or AC/DC24~240V.
- Output: 10A with either 1SPDT (GRT6-M1) or 2SPDT (GRT6-M2) contacts.
- Adjustable Time Scale: 0.1 seconds to 10 days, divided into 10 ranges.
- Compact Design: 1-MODULE (18mm) width for DIN rail mounting.
2. Setup and Installation
2.1 Dimensions
The GRT6-M series relays feature a compact design suitable for DIN rail mounting.

2.2 Mounting
The device is designed for DIN rail mounting, ensuring easy integration into electrical panels.
2.3 Wiring Diagram
Proper wiring is crucial for safe and correct operation. Refer to the diagram below for typical wiring connections. Ensure all connections are secure and comply with local electrical codes.

Terminal connections:
- A1(+), A2(-): Supply terminals for power input.
- S: Control input terminal for specific functions.
- 15, 16, 18: Output contact terminals (15 is common, 16 is normally closed, 18 is normally open).
3. Operating Instructions
3.1 Function Modes
The GRT6-M offers 10 selectable function modes, categorized by how they are triggered and their timing behavior. Use the function selector knob to choose the desired mode.

- A: On Delay (Power On) - Upon input voltage (Un), timing delay begins. Relay contacts R change state after time delay is complete. Contacts R return to their shelf state when input voltage Un is removed. Trigger switch S is not used in this function.
- B: Interval (Power On) - Upon input voltage (Un), relay contacts R change state immediately and timing delay begins. When time delay is complete, contacts return to shelf state. When input voltage Un is removed, contacts will also return to their shelf state. Trigger switch S is not used in this function.
- C: Repeat Cycle (Starting Off) - When input voltage (Un) is applied, time delay begins. When time delay is complete, relay contacts R change state for time delay. This cycle will repeat until input voltage Un is removed. Trigger switch S is not used in this function.
- D: Repeat Cycle (Starting On) - When input voltage (Un) is applied, relay contacts R change state immediately and time delay begins. When time delay is complete, contacts return to shelf state for time delay. This cycle will repeat until input voltage Un is removed. Trigger switch S is not used in this function.
- E: Off Delay (S Break) - Input voltage Un must be applied continuously. When trigger switch S is closed, relay contacts R change state. When trigger switch S is opened, delay t begins. When delay is complete, contacts R return to their shelf state. If trigger switch S is closed before time delay is complete, then time is reset. When trigger switch S is opened, the delay begins again, and relay contacts R remain in their energized state. If input voltage Un is removed, relay contacts R return to their shelf state.
- F: Single Shot - Upon application of input voltage Un, the relay is ready to accept trigger signal S. Upon application of the trigger signal S, the relay contacts R transfer and the preset time t begins. During time-out, the trigger signal S is ignored. The relay resets by applying the trigger switch S when the relay is not energized.
- G: Single Shot Trailing Edge (Non-Retriggerable) - Upon application of input voltage Un, the relay is ready to accept trigger signal S. Upon application of the trigger signal S, the relay contacts R transfer and the preset time t begins. At the end of the preset time, the relay contacts R return to their normal condition unless the trigger switch S is opened and closed prior to time out t (before preset time elapses). Continuous cycling of the trigger switch S at a rate faster than the preset time will cause the relay contacts R to remain closed. If input voltage Un is removed, relay contacts R return to their shelf state.
- H: On/Off Delay - Input voltage Un must be applied continuously. When trigger switch S is closed, time delay begins. When time delay is complete, relay contacts R change state and remain transferred until trigger switch S is opened. If input voltage Un is removed, relay contacts R return to their shelf state.
- I: Latching Relay - Input voltage Un must be applied continuously. Output changes state with every trigger switch S closure. If input voltage Un is removed, relay contacts R return to their shelf state.
- J: Pulse Generator - Upon application of input voltage Un, a single output pulse of 0.5 seconds is delivered to relay after time delay t. Power must be removed and re-applied to repeat pulse. Trigger switch S is not used in this function.
3.2 Time Setting
The time delay is set using two rotary knobs on the front panel:

- Knob 1 (Gear Setting): Selects the time range (e.g., 's' for seconds, 'm' for minutes, 'h' for hours, 'd' for days). It also includes 'ON' for relay action (15-18/25-28 closed) and 'OFF' for relay open (15-18/25-28 open).
- Knob 2 (Fine Adjustment): Adjusts the delay time from 10% to 100% within the selected gear.
Formula: Delay time = Knob 1 setting × Knob 2 percentage.
Example 1: To set for 5 seconds, set Knob 1 to '10s' and Knob 2 to '50%'. Delay time = 10s × 50% = 5s.
Example 2: To set for 8 minutes, set Knob 1 to '10m' and Knob 2 to '80%'. Delay time = 10m × 80% = 8m.
3.3 Video Demonstration of Function Modes
Watch the official demonstration video to see the various function modes in action. This video illustrates the behavior of the relay for each of the 10 selectable functions (A-J).
4. Specifications
Detailed technical parameters for the GRT6-M1 and GRT6-M2 models:

| Parameter | GRT6-M1 | GRT6-M2 |
|---|---|---|
| Function | A, B, C, D, E, F, G, H, I, J | |
| Supply terminals | A1-A2 | |
| Voltage range | AC/DC 24-240V (50-60Hz) | |
| Burden | AC 0.09-3VA/DC 0.05-1.7W | |
| Voltage range (A230) | AC 230V/50-60Hz | |
| Power input | AC max.6VA/1.3W, AC max.6VA/1.9W | |
| Supply voltage tolerance | -15%; +10% | |
| Supply indication | green LED | |
| Time ranges | 0.1s-10days, ON, OFF | |
| Time setting | potentiometer | |
| Time deviation | 10%-mechanical setting | |
| Repeat accuracy | 0.2%-set value stability | |
| Temperature coefficient | 0.05%/°C (at=20°C (0.05% /°F, at=68°F)) | |
| Output | 1 × SPDT | 2 × SPDT |
| Current rating | 10A / AC1 | |
| Switching voltage | 250VAC/240VDC | |
| Min.breaking capacity DC | 500mW | |
| Output indication | red LED | |
| Mechanical life | 1 × 107 | |
| Electrical life (AC1) | 1 × 105 | |
| Reset time | max. 200ms | |
| Operating temperature | -20°C to +55°C (-4°F to 131°F) | |
| Storage temperature | -35°C to +75°C (-22°F to 158°F) | |
| Mounting/DIN rail | Din rail EN/IEC 60715 | |
| Protection degree | IP40 for front panel/IP20 terminals | |
| Operating position | any | |
| Overvoltage category | III. | |
| Pollution degree | 2 | |
| Max. cable size (mm2) | solid wire max. 1x2, 5or2x1.5/with sleeve max.1x2, 5(AWG 12) | |
| Tightening torque | 0.4Nm | |
| Dimensions | 90 × 18 × 64mm | |
| Weight | 1 × SPDT: 63g | 2 × SPDT: 82g |
| Standards | EN 61812-1, IEC60947-5-1 | |
Certifications: CE, RoHS, CB.
5. Maintenance
The GEYA GRT6-M Time Relay is designed for long-term, reliable operation with minimal maintenance. Keep the device clean and free from dust and moisture. Periodically check terminal connections for tightness to ensure optimal performance and safety. Do not attempt to open or repair the device yourself; refer to qualified personnel for servicing.
6. Troubleshooting
If the device is not functioning as expected, perform the following basic checks:
- No Power Indication: Verify the power supply voltage matches the device's rating and that connections to terminals A1 and A2 are secure.
- Incorrect Timing: Double-check the settings on both time adjustment knobs (Knob 1 for range, Knob 2 for percentage). Ensure the selected function mode is correct for your application.
- Output Not Switching: Confirm that the load is correctly wired to the output terminals (15, 16, 18) and that the load's power requirements do not exceed the relay's current rating (10A). Check if the control input 'S' is being applied correctly for functions that require it.
- Intermittent Operation: Inspect all wiring for loose connections or damaged insulation. Ensure the operating environment is within the specified temperature range.
If issues persist after these checks, contact GEYA customer support or a qualified electrician.
7. User Tips
Based on common user experiences and questions:
- For precise timing, ensure the environment is stable and free from excessive vibrations or temperature fluctuations.
- When changing function modes or time ranges, it's recommended to cycle the power to the relay to ensure the new settings are properly applied.
- Always use appropriate wire gauges for your connections to prevent overheating and ensure reliable current flow.
- Consider using a protective enclosure if installing in harsh industrial environments to maintain the IP40 protection rating.
8. Warranty and Support
GEYA products are manufactured to high standards and come with a standard warranty. For specific warranty details, technical support, or service inquiries, please refer to the official GEYA website or contact GEYA customer service directly. Contact information can typically be found on the product packaging or the manufacturer's official website.

GEYA Official Store: https://www.aliexpress.com/store/1101291693