1. Introduction
The GEYA GRT6-A/B series are single-function electronic time relays designed for various automation control applications. The GRT6-A model provides a Delay ON function, while the GRT6-B model offers a Delay OFF function. These relays are suitable for applications requiring precise timing, such as pump decay time after switching heating off, or controlling fans.
Key features include a wide range voltage support, multiple time ranges, and clear LED indicators for relay status.
2. Product Overview
The GRT6 series time relays are compact, 1-module (18mm) devices designed for DIN rail mounting. They feature a potentiometer for time setting and LED indicators for power (green) and output status (red).


3. Setup and Installation
3.1 Dimensions
The GRT6 series relays are designed for compact installation. Refer to the diagram below for typical dimensions.

3.2 Mounting
The GRT6 series relays are designed for DIN rail mounting according to EN/IEC 60715 standards. Ensure the mounting location provides adequate ventilation and is within the specified operating temperature range.
3.3 Wiring
Proper wiring is crucial for safe and correct operation. Always ensure power is disconnected before performing any wiring. The relays support solid wire up to 1x2.5mm² or 2x1.5mm², and with sleeve up to 1x2.5mm² (AWG 12). The tightening torque for terminals is 0.4Nm.


4. Operating Instructions
4.1 Function Selection
- GRT6-A (Delay ON): The output relay activates after a preset delay time once the supply voltage is applied.
- GRT6-B (Delay OFF): The output relay deactivates after a preset delay time once the supply voltage is removed.
4.2 Time Setting
The delay time is set using two potentiometers (knobs) on the front panel:
- Knob 1 (Delay Gear Setting): Selects the time range (e.g., seconds 's', minutes 'm', hours 'h', days 'd'). It also includes 'ON' for relay action (15-18/25-28 closed) and 'OFF' for relay open (15-18/25-28 open) for continuous operation modes.
- Knob 2 (Fine Adjustment): Provides a fine adjustment of the delay time from 10% to 100% within the selected range.
Calculation: Delay time = Knob 1 setting × Knob 2 percentage.
Examples:
- To set a 5-second delay: Set Knob 1 to '10s', and Knob 2 to '50%'. Delay time = 10s × 50% = 5s.
- To set an 8-minute delay: Set Knob 1 to '10m', and Knob 2 to '80%'. Delay time = 10m × 80% = 8m.

4.3 Indicators
- Green LED (Un): Indicates the presence of supply voltage.
- Red LED (R): Indicates the status of the output relay.
5. Maintenance
The GEYA GRT6 series time relays are designed for reliable, long-term operation with minimal maintenance. To ensure optimal performance:
- Keep the device clean and free from dust and debris.
- Periodically check all electrical connections for tightness and ensure they are free from corrosion.
- Avoid exposing the device to extreme temperatures, humidity, or corrosive environments beyond its specified operating conditions.
- Do not attempt to open or repair the device yourself. Refer to qualified personnel for any servicing needs.
6. Troubleshooting
If the time relay is not functioning as expected, consider the following troubleshooting steps:
- No Power Indication (Green LED Off): Check the power supply connections (A1-A2) and ensure the correct voltage is applied.
- Relay Not Activating/Deactivating:
- Verify the wiring connections to the load (terminals 15, 16, 18 or 25, 26, 28).
- Ensure the time setting is correctly configured for the desired delay.
- Check the output relay status using the Red LED indicator.
- Incorrect Timing:
- Re-check the settings on both potentiometers (Knob 1 for range, Knob 2 for fine adjustment).
- Ensure the ambient temperature is within the specified operating range, as extreme temperatures can affect timing accuracy.
- Device Overheating: Ensure adequate ventilation around the device and that it is not overloaded beyond its rated current.
If problems persist after performing these checks, contact GEYA customer support.
7. Specifications
Below are the technical parameters for the GRT6-A/B series time relays:

| Parameter | GRT6-A/B1 (1SPDT) | GRT6-A/B2 (2SPDT) |
|---|---|---|
| Function | A: delay ON; B: delay OFF | |
| Supply terminals | A1-A2 | |
| Voltage range | AC/DC 24-240V or AC 230V (50-60Hz) | |
| Burden | AC 0.09-3VA / DC 0.05-1.7W | |
| Voltage tolerance | AC max. 6VA/1.3W, -15% +10% | |
| Supply indication | green LED | |
| Time ranges | 0.1s-10days, ON, OFF (in 10 alternate) | |
| Time setting | potentiometer | |
| Time deviation | 10% - mechanical setting | |
| Repeat accuracy | 0.2% - set value stability | |
| Temperature coefficient | 0.05%/°C, at -20°C (0.05%/°F, at 68°F) | |
| Output | 1x SPDT | 2x SPDT |
| Current rating | 10A/AC1 | |
| Switching voltage | 250VAC/24VDC | |
| Min. breaking capacity DC | 500mW | |
| Output indication | red LED | |
| Mechanical life | 1x107 | |
| Electrical life (AC1) | 1x105 | |
| Reset time | Max. 200ms | |
| Operating temperature | -20°C to +55°C (-4°F to 131°F) | |
| Storage temperature | -35°C to +75°C (-22°F to 158°F) | |
| Mounting/DIN rail | DIN rail EN/IEC 60715 | |
| Protection degree | IP40 for front panel / IP20 terminals | |
| Operating position | any | |
| Overvoltage category | III. | |
| Pollution degree | 2 | |
| Max. cable size (mm²) | solid wire max. 1x2.5 or 2x1.5 / with sleeve max. 1x2.5 (AWG 12) | |
| Tightening torque | 0.4Nm | |
| Dimensions | 90x18x64mm | |
| Weight | S240-61g, A230-61g | |
| Standards | EN 61812-1, IEC60947-5-1 | |
| Certification | CE, RoHS, WEEE | |
8. User Tips
- Understanding Delay Functions: The GRT6-A is a 'delay on connection' type relay, meaning the output activates after a set time once power is applied. The GRT6-B is a 'delay off' type, where the output deactivates after a set time once power is removed. Ensure you select the correct model for your application.
- Voltage Compatibility: Always confirm the voltage of your power supply matches the relay's specified voltage (AC230V or AC/DC24-240V) to prevent damage.
- Application Versatility: These relays are widely applicable in industrial automation, power systems, household appliances, and automotive electronics. Consider their use for controlling motors, lighting, or other timed processes.

9. Warranty and Support
GEYA products are manufactured to high-quality standards and come with standard manufacturer warranties. For specific warranty details, please refer to your purchase documentation or contact GEYA directly.
Contact Information:
GEYA Official StoreWebsite: www.geya.net
Email: cassie@cngeya.com
Phone: +86 13968799499
Address: Wenzhou Bridge Industrial Zone, Beibaixiang Town, Wenzhou City, Zhejiang Province, China