1. About This Manual
1.1 Purpose
This manual describes the assembly, installation, operation, and troubleshooting of this unit. Please read this manual carefully before installations and operations. Keep this manual for future reference.
1.2 Scope
This manual provides safety and installation guidelines as well as information on tools and wiring.
2. Safety Instructions
WARNING: This chapter contains important safety and operating instructions. Read and keep this manual for future reference.
- Before using the unit, read all instructions and cautionary markings on the unit, the batteries, and all appropriate sections of this manual.
- CAUTION – To reduce risk of injury, charge only deep-cycle lead acid type rechargeable batteries. Other types of batteries may burst, causing personal injury and damage.
- Do not disassemble the unit. Take it to a qualified service center when service or repair is required. Incorrect re-assembly may result in a risk of electric shock or fire.
- To reduce risk of electric shock, disconnect all wirings before attempting any maintenance or cleaning. Turning off the unit will not reduce this risk.
- CAUTION – Only qualified personnel can install this device with battery.
- NEVER charge a frozen battery.
- For optimum operation of this inverter/charger, please follow required spec to select appropriate cable size. It's very important to correctly operate this inverter/charger.
- Be very cautious when working with metal tools on or around batteries. A potential risk exists to drop a tool to spark or short circuit batteries or other electrical parts and could cause an explosion.
- Please strictly follow installation procedure when you want to disconnect AC or DC terminals. Please refer to INSTALLATION section of this manual for the details.
- Fuses (6 pieces of 40A, 32VDC for 2.4KW) are provided as over-current protection for the battery supply.
- GROUNDING INSTRUCTIONS -This inverter/charger should be connected to a permanent grounded wiring system. Be sure to comply with local requirements and regulation to install this inverter.
- NEVER cause AC output and DC input short circuited. Do NOT connect to the mains when DC input short circuits.
- Warning!! Only qualified service persons are able to service this device. If errors still persist after following troubleshooting table, please send this inverter/charger back to local dealer or service center for maintenance.
3. Introduction
This is a multi-function inverter/charger, combining functions of inverter, solar charger, and battery charger to offer uninterruptible power support with portable size. Its comprehensive LCD display offers user-configurable and easy-accessible button operation such as battery charging current, AC/solar charger priority, and acceptable input voltage based on different applications.
3.1 Features
- Pure sine wave inverter
- Configurable input voltage range for home appliances and personal computers via LCD setting
- Configurable battery charging current based on applications via LCD setting
- Configurable AC/Solar Charger priority via LCD setting
- Compatible to mains voltage or generator power
- Auto restart while AC is recovering
- Overload/Over temperature/short circuit protection
- Smart battery charger design for optimized battery performance
- Cold start function
3.2 Basic System Architecture
The following illustration shows a basic application for this inverter/charger. It also includes the following devices to have a complete running system: Generator or Utility, and PV modules (option). Consult with your system integrator for other possible system architectures depending on your requirements. This inverter can power all kinds of appliances in home or office environments, including motor-type appliances such as tube lights, fans, refrigerators, and air conditioners.

4. Product Overview
The PowMr 2.4KW PWM Hybrid Solar Inverter is a compact and efficient unit designed for small home power systems. It features a clear LCD display and intuitive function buttons for easy operation.

Component Identification:
- LCD display
- Status indicator
- Charging indicator
- Fault indicator
- Function buttons (ESC, UP, DOWN, ENTER)
- Power on/off switch
- AC input
- AC output
- PV input
- Battery input
- Circuit breaker
- RS232 communication port
- Dry contact

Key Specifications from Image:
- Weight: 6.9KG
- Rated Output Power: 2400W
- Max Solar Charge Current: 50A
- Charging Current PWM: 50AMP 24VDC
- Max. PV Array Open Circuit Voltage: 80VDC
- Dimensions: 10.7in (W) x 13.97in (H) x 3.9in (D)
5. Setup and Installation
5.1 Unpacking and Inspection
Before installation, carefully inspect the unit. Ensure no damage occurred during transit. The package should contain:
- The inverter unit x 1
- User manual x 1
- Communication cable x 1
- Software CD x 1
5.2 Preparation
Before connecting any wiring, remove the bottom cover of the inverter by unscrewing the two retaining screws.
5.3 Mounting the Unit
Consider the following points when selecting an installation location:
- Do not mount the inverter on flammable construction materials.
- Mount on a solid surface.
- Install this inverter at eye level for easy readability of the LCD display.
- For proper air circulation and heat dissipation, allow a clearance of approximately 20 cm to the sides and 50 cm above and below the unit.
- The ambient temperature should be between 0°C and 55°C for optimal operation.
- The recommended installation position is vertically on the wall.
- Ensure sufficient space for heat dissipation and wire removal as shown in the diagram.
SUITABLE FOR MOUNTING ON CONCRETE OR OTHER NON-COMBUSTIBLE SURFACE ONLY.

Install the unit by screwing three screws. It's recommended to use M4 or M5 screws.
5.4 Battery Connection
CAUTION:
- For safety and regulation compliance, install a separate DC over-current protector or disconnect device between the battery and inverter.
- Refer to the typical amperage in the table below for required fuse or breaker size.
WARNING:
- All wiring must be performed by qualified personnel.
- Use appropriate cable for battery connection to ensure system safety and efficient operation.
| Model | Typical Amperage | Battery Capacity | Wire Size | Cable (mm²) | Terminal D(mm) | Terminal L(mm) | Torque Value |
|---|---|---|---|---|---|---|---|
| 2.4KW | 100A | 100Ah | 1*4 AWG | 22 | 6.4 | 33.2 | 2~3Nm |
| 200Ah | 2*8 AWG | 14 | 6.4 | 29.2 |
Battery Connection Steps:
- Assemble battery ring terminals based on recommended cable and terminal size.
- The 2.4KW model supports a 24VDC system. Connect all battery packs as shown in the diagram. It is suggested to connect at least a 100Ah capacity battery for the 2.4KW model.
- Insert the ring terminal of the battery cable flatly into the battery connector of the inverter and ensure the bolts are tightened with a torque of 2-3 Nm. Verify polarity at both the battery and the inverter/charger is correctly connected, and ring terminals are tightly screwed to the battery terminals.

NOTE: Please only use sealed lead acid battery or sealed GEL/AGM lead-acid battery.
WARNING: Shock Hazard
- Installation must be performed with care due to high battery voltage in series.
CAUTION:
- Do not place anything between the flat part of the inverter terminal and the ring terminal. Otherwise, overheating may occur.
- Do not apply anti-oxidant substance on the terminals before terminals are connected tightly.
- Before making the final DC connection or closing the DC breaker/disconnector, ensure positive (+) is connected to positive (+) and negative (-) to negative (-).
5.5 AC Input/Output Connection
| Model | Gauge | Torque Value |
|---|---|---|
| 2.4KW | 10 AWG | 1.2~1.6 Nm |
WARNING:
- All wiring must be performed by qualified personnel.
- Use appropriate cable for AC input connection to ensure system safety and efficient operation.
CAUTION:
- Before connecting to AC input power source, install a separate AC breaker (recommended 45A for 2.4KW) between the inverter and the AC input source.
- Do NOT mis-connect input and output connectors.
AC Input/Output Connection Steps:
- Before making AC input/output connections, ensure the DC protector or disconnector is open.
- Remove 10mm of insulation from six conductors. Shorten phase L and neutral conductor N by 3mm.
- Insert AC input wires according to polarities indicated on the terminal block and tighten the terminal screws. Connect PE protective conductor (yellow-green) first, then L (brown or black), and N (blue).
- Insert AC output wires according to polarities indicated on the terminal block and tighten the terminal screws. Connect PE protective conductor (yellow-green) first, then L (brown or black), and N (blue).
- Ensure all wires are securely connected.
WARNING: Be sure that AC power source is disconnected before attempting to hardwire it to the unit.
CAUTION:
- Connect AC wires with correct polarity. Reversed L and N wires can cause utility short-circuiting in parallel operation.
- Appliances like air conditioners require 2-3 minutes to restart. Ensure they have a time-delay function to prevent damage from short power outages.
5.6 PV Connection (for models with solar charger)
| Model | Typical Amperage | Gauge | Torque Value |
|---|---|---|---|
| 2.4KW | 50A | 8 AWG | 1.4~1.6 Nm |
WARNING:
- All wiring must be performed by qualified personnel.
- Use appropriate cable for PV module connection to ensure system safety and efficient operation.
CAUTION: Before connecting to PV modules, install a separate DC circuit breaker between the inverter and PV modules.
PV Module Selection:
When selecting proper PV modules, consider these requirements:
- The Open Circuit Voltage (Voc) of PV modules must not exceed the max PV array open circuit voltage of the inverter (80Vdc).
- The Max. Power Voltage (Vmpp) of PV modules should be close to the inverter's best Vmp (30Vdc) or within the Vmp range (30V~32V) for optimal performance. If a single PV module cannot meet this, use several PV modules in series.
| INVERTER MODEL | POW-LVM2.4K-24V |
|---|---|
| Solar Charger Charging Current | 50Amp |
| System DC Voltage | 24Vdc |
| Operating Voltage Range | 30~32Vdc |
| Max. PV Array Open Circuit Voltage | 80Vdc |
PV Connection Steps:
- Remove 10mm of insulation from positive and negative conductors.
- Check correct polarity of connection cable from PV modules and PV input connectors. Connect positive pole (+) of connection cable to positive pole (+) of PV input connector. Connect negative pole (-) of connection cable to negative pole (-) of PV input connector.
- Ensure the wires are securely connected.
5.7 Final Assembly
After connecting all wirings, replace the bottom cover by screwing the two screws back into place.
6. Operating Instructions
6.1 Power ON/OFF
Once the unit is properly installed and batteries are connected, simply press the On/Off switch (located on the bottom of the case) to turn on the unit.
6.2 Operation and Display Panel
The operation and display panel is on the front of the inverter. It includes three indicators, four function keys, and an LCD display, showing operating status and input/output power information.
| Function Key | Description |
|---|---|
| ESC | To exit setting mode |
| UP | To go to previous selection |
| DOWN | To go to next selection |
| ENTER | To confirm the selection in setting mode or enter setting mode |
6.3 LCD Display Icons and LED Indicators
| LED Indicator | Color | Status | Message |
|---|---|---|---|
| AC / INV | Green | Solid On | Output is powered by utility in Line mode. |
| Flashing | Output is powered by battery or PV in battery mode. | ||
| CHG | Green | Solid On | Battery is fully charged. |
| Flashing | Battery is charging. | ||
| FAULT | Red | Solid On | Fault occurs in the inverter. |
| Flashing | Warning condition occurs in the inverter. |
| Icon | Function Description |
|---|---|
| AC | Indicates the AC input. |
| PV | Indicates the PV input. |
| INPUTBATT (with values) | Indicates input voltage, input frequency, PV voltage, battery voltage, and charger current. |
| 88 (with values) | Indicates the setting programs. |
| 8.8 (with ERROR) | Indicates warning and fault codes. Flashing indicates warning, solid indicates fault. |
| Battery Level Indicator | Indicates battery level (0-24%, 25-49%, 50-74%, 75-100%) in battery mode and charging status in line mode. |
| OVER LOAD | Indicates overload. |
| Load Level Indicator | Indicates the load level by 0-24%, 25-50%, 50-74%, and 75-100%. |
| Utility Connection Icon | Indicates unit connects to the mains. |
| PV Panel Icon | Indicates unit connects to the PV panel. |
| BYPASS | Indicates load is supplied by utility power. |
| Utility Charger Icon | Indicates the utility charger circuit is working. |
| DC/AC Inverter Icon | Indicates the DC/AC inverter circuit is working. |
| Mute Icon | Indicates unit alarm is disabled. |
6.4 LCD Setting
After pressing and holding the ENTER button for 3 seconds, the unit will enter setting mode. Use the "UP" or "DOWN" buttons to select setting programs, then press "ENTER" to confirm or "ESC" to exit.
| NO. | Description | Selectable Option | Explanation |
|---|---|---|---|
| 00 | Exit setting mode | 00 ESC | Exits the setting menu. |
| 01 | Output source priority: To configure load power source priority | 01 SOL (Solar first) | Solar energy provides power first. If insufficient, battery energy supplies power. |
| 01 UTI (Utility first) | Utility provides power first. Solar and battery energy provide power only when utility is unavailable. | ||
| 01 SBU (SBU priority) | Solar energy provides power first. If insufficient, battery energy supplies power. Utility provides power only when battery voltage drops to low-level warning or setting point in program 12. | ||
| 02 | Maximum charging current | 20-80A (50A default) | Sets the total charging current for solar and utility chargers. Increment of 10A per click. |
| 03 | AC input voltage range | 03 APL (Appliances) | Acceptable AC input voltage range: 65-140VAC. |
| 03 UPS (UPS) | Acceptable AC input voltage range: 95-140VAC. | ||
| 04 | Power saving mode enable/disable | 04 SdS (Saving mode disable) | Output of inverter is not affected by load level. |
| 04 SEn (Saving mode enable) | Output of inverter turns off when connected load is very low or not detected. | ||
| 05 | Battery type | 05 AGn (AGM) | Sets battery type to AGM. |
| 05 FLd (Flooded) | Sets battery type to Flooded. | ||
| 05 USE (User-Defined) | Allows user to define battery parameters. | ||
| 06 | Auto restart when overload occurs | 06 LFD (Restart disable) | Inverter does not auto-restart after overload. |
| 06 LtE (Restart enable) | Inverter auto-restarts after overload. | ||
| 07 | Auto restart when over temperature occurs | 07 LFD (Restart disable) | Inverter does not auto-restart after over temperature. |
| 07 LtE (Restart enable) | Inverter auto-restarts after over temperature. | ||
| 09 | Output frequency | 09 50Hz | Sets output frequency to 50Hz. |
| 09 60Hz | Sets output frequency to 60Hz. | ||
| 11 | Maximum utility charging current | 20A / 30A | Sets the maximum charging current from utility. |
| 12 | Setting voltage point back to utility source | 22.0-25.5V (23.0V default) | Voltage at which system switches to utility when SBU or Solar first priority is selected. Increment of 0.5V. |
| 13 | Setting voltage point back to battery mode | 24-29V (27V default) | Voltage at which system switches back to battery when SBU or Solar first priority is selected. Increment of 0.5V. |
| 16 | Charger source priority | 16 CSD (Solar first) | Solar energy charges battery first. Utility charges only if solar is unavailable. |
| 16 CUt (Utility first) | Utility charges battery first. Solar charges only if utility is unavailable. | ||
| 16 SNU (Solar and Utility) | Solar and utility charge battery simultaneously. | ||
| 16 OSO (Only Solar) | Only solar energy charges battery, regardless of utility availability. | ||
| 18 | Alarm control | 18 bOn (Alarm on) | Enables audible alarms. |
| 18 bOF (Alarm off) | Disables audible alarms. | ||
| 19 | Auto return to default display screen | 19 ESP (Return to default) | Automatically returns to default display (Input/Output voltage) after 1 minute of inactivity. |
| 19 HEP (Stay at latest) | Display screen stays on the last selected view. | ||
| 20 | Backlight control | 20 LOn (Backlight on) | Keeps LCD backlight on. |
| 20 LOF (Backlight off) | Turns LCD backlight off after a period of inactivity. | ||
| 22 | Beeps while primary source is interrupted | 22 bOn (Alarm on) | Enables beeping when primary source is interrupted. |
| 22 bOF (Alarm off) | Disables beeping when primary source is interrupted. | ||
| 23 | Overload bypass | 23 bYd (Bypass disable) | Unit does not transfer to line mode on overload in battery mode. |
| 23 bYE (Bypass enable) | Unit transfers to line mode on overload in battery mode. | ||
| 25 | Record Fault code | 25 FEn (Record enable) | Enables recording of fault codes. |
| 25 FdS (Record disable) | Disables recording of fault codes. | ||
| 26 | Bulk charging voltage (C.V voltage) | 24.0V to 29.2V (28.2V default) | Sets the constant voltage charging level. Increment of 0.1V. |
| 27 | Floating charging voltage | 24.0V to 29.2V (27.0V default) | Sets the floating charge voltage level. Increment of 0.1V. |
| 29 | Low DC cut-off voltage | 20.0V to 24.0V (21.0V default) | Sets the low DC voltage threshold for inverter shutdown. Increment of 0.1V. |
| 30 | Battery equalization | 30 EEn (Enable) | Enables battery equalization function. |
| 30 EdS (Disable) | Disables battery equalization function. | ||
| 31 | Battery equalization voltage | 25.0V to 30V (29.2V default) | Sets the voltage level for battery equalization. Increment of 0.1V. |
| 33 | Battery equalized time | 5min to 900min (60min default) | Sets the duration for battery equalization. Increment of 5min. |
| 34 | Battery equalized timeout | 5min to 900min (120min default) | Sets the maximum time for equalization before stopping if voltage is not reached. Increment of 5min. |
| 35 | Equalization interval | 0 to 90 days (30 days default) | Sets the frequency of automatic battery equalization. Increment of 1 day. |
| 36 | Equalization activated immediately | 36 AEn (Enable) | Activates battery equalization immediately. |
| 36 AdS (Disable) | Cancels immediate equalization. |
6.5 Operating Mode Description
The inverter operates in various modes depending on power availability and settings. The LCD display provides visual cues for each mode.
| Operation Mode | Description | LCD Display (Example Icons) |
|---|---|---|
| Standby / Power Saving Mode | No output is supplied, but batteries can still be charged. In power saving mode, output turns off if load is very low. | Charging by utility and PV energy, Charging by utility, Charging by PV energy, No charging. |
| Line Mode | Unit provides output power from the mains and charges the battery. | Charging by utility and PV energy, Charging by utility. |
| Battery Mode | Unit provides output power from battery and PV power. | Power from battery and PV energy, Power from battery only. |
| Fault Mode | Errors due to internal circuit, over temperature, short circuit, etc. PV energy and utility can still charge batteries. | Charging by utility and PV energy, Charging by utility, Charging by PV energy. |
6.6 Battery Equalization Description
The equalization function in the charge controller reverses the buildup of negative chemical effects like stratification and removes sulfate crystals from battery plates, which can reduce battery capacity. Periodic equalization is recommended.
How to Apply Equalization Function:
First, enable the battery equalization function in LCD setting program 30. Then, you can apply this function by:
- Setting the equalization interval in program 35.
- Activating equalization immediately in program 36.
When to Equalize:
In the float stage, when the set equalization interval is reached, or if equalization is activated immediately, the controller will enter the Equalize stage.

Equalize Charging Time and Timeout:
During the Equalize stage, the controller charges the battery until it reaches the battery equalization voltage. It then maintains this voltage. The battery remains in this stage until the set equalized time expires. If the battery voltage doesn't reach the equalization voltage within the set time, the controller may extend the time. If the voltage is still not reached by the equalization timeout, the equalization stops, and the system returns to the float stage.
7. Maintenance
Regular maintenance ensures the longevity and optimal performance of your PowMr Hybrid Solar Inverter.
- General Cleaning: Periodically clean the exterior of the inverter to prevent dust buildup, especially around ventilation openings. Ensure proper air circulation for heat dissipation.
- Ventilation: Regularly check that the inverter's ventilation openings are not blocked. Blocked vents can lead to overheating and reduced performance.
- Wiring Inspection: Periodically inspect all wiring connections (battery, AC input/output, PV input) for tightness and signs of corrosion or damage. Loose connections can cause overheating or system malfunction.
- Battery Health: Monitor battery performance and ensure they are within their recommended operating parameters. Perform battery equalization as described in the operating instructions to maintain battery health.
- Safety First: Always disconnect all power sources (AC, DC, PV) before performing any maintenance or cleaning to avoid electric shock.
8. Troubleshooting
This section provides guidance on common issues and their solutions. For persistent errors, contact a qualified service center.
8.1 Fault Reference Codes
| Fault Code | Fault Event | Icon on | What to do |
|---|---|---|---|
| 01 | Fan is locked when inverter is off. | 01 ERROR | Replace the fan. |
| 02 | Over temperature (internal component > 100°C) | 02 ERROR | Check air flow, ensure vents are not blocked, and ambient temperature is not too high. |
| 03 | Battery voltage is too high. | 03 ERROR | Return to repair center. |
| 04 | Battery voltage is too low. | 04 ERROR | Check battery specifications and quantity. |
| 05 | Output short circuited or over temperature (internal converter components > 120°C) | 05 ERROR | Check if wiring is connected well and remove abnormal load. |
| 06 | Output voltage is abnormal. | 06 ERROR | Return to repair center. |
| 07 | Overload time out. | 07 ERROR | Reduce the connected load by switching off some equipment. |
| 08 | Bus voltage is too high. | 08 ERROR | Return to repair center. |
| 09 | Bus soft start failed. | 09 ERROR | Return to repair center. |
| 11 | Main relay failed. | 11 ERROR | Return to repair center. |
8.2 Warning Indicators
| Warning Code | Warning Event | Audible Alarm | Icon Flashing |
|---|---|---|---|
| 01 | Fan is locked when inverter is on. | Beep three times every second. | 01 (fan icon) |
| 03 | Battery is over-charged. | Beep once every second. | 03 (battery icon) |
| 04 | Low battery. | Beep once every second. | 04 (battery icon) |
| 07 | Overload. | Beep once every 0.5 second. | 07 (overload icon) |
| 10 | Output power derating. | Beep twice every 3 seconds. | 10 (power icon) |
8.3 General Troubleshooting
| Problem | LCD/LED/Buzzer | Explanation / Possible Cause | What to do |
|---|---|---|---|
| Unit shuts down automatically during startup process. | LCD/LEDs and buzzer active for 3 seconds then off. | Battery voltage is too low (<1.91V/Cell). | 1. Re-charge battery. 2. Replace battery. |
| No response after power on. | No indication. | 1. Battery voltage is far too low (<1.4V/Cell). 2. Battery polarity is connected reversed. | 1. Check if batteries and wiring are connected well. 2. Re-charge battery. 3. Replace battery. |
| Input voltage displayed as 0 on LCD, green LED flashing. | Input protector is tripped. | Check if AC breaker is tripped and AC wiring is connected well. | |
| Mains exist but unit works in battery mode. | Green LED is flashing. | Insufficient quality of AC power (Shore or Generator). | 1. Check if AC wires are too thin and/or too long. 2. Check if generator (if applied) is working well or if input voltage range setting is correct (UPS→Appliance). |
| Green LED is flashing. | Set "Solar First" as the priority of output source. | Change output source priority to Utility first. | |
| When unit is turned on, internal relay switches on and off repeatedly. | LCD display and LEDs are flashing. | Battery is disconnected. | Check if battery wires are connected well. |
9. Specifications
9.1 Table 1 Line Mode Specifications
| INVERTER MODEL | POW-LVM2.4K-24V |
|---|---|
| Input Voltage Waveform | Pure Sine Wave (utility or generator) |
| Nominal Input Voltage | 120Vac |
| Low Loss Voltage | 95Vac±7V (UPS); 65Vac±7V (Appliances) |
| Low Loss Return Voltage | 100Vac±7V (UPS); 70Vac±7V (Appliances) |
| High Loss Voltage | 140Vac±7V |
| High Loss Return Voltage | 135Vac±7V |
| Max AC Input Voltage | 150Vac |
| Nominal Input Frequency | 50Hz/60Hz (Auto detection) |
| Low Loss Frequency | 40±1Hz |
| Low Loss Return Frequency | 42±1Hz |
| High Loss Frequency | 65±1Hz |
| High Loss Return Frequency | 63±1Hz |
| Output Short Circuit Protection | Circuit Breaker |
| Efficiency (Line Mode) | >95% (Rated R load, battery full charged) |
| Transfer Time | 10ms typical (UPS); 20ms typical (Appliances) |
9.2 Table 2 Inverter Mode Specifications
| INVERTER MODEL | POW-LVM2.4K-24V |
|---|---|
| Rated Output Power | 3KVA/2.4KW |
| Output Voltage Waveform | Pure Sine Wave |
| Output Voltage Regulation | 120Vac±5% |
| Output Frequency | 60Hz |
| Peak Efficiency | 94% |
| Overload Protection | 5s@≥150% load; 10s@110%~150% load |
| Surge Capacity | 2 * rated power for 5 seconds |
| Nominal DC Input Voltage | 24Vdc |
| Cold Start Voltage | 23.0Vdc |
| Low DC Warning Voltage | 22.0 Vdc |
| Low DC Warning Return Voltage | 23.0 Vdc |
| Low DC Cut-off Voltage | 21.0 Vdc |
| High DC Recovery Voltage | 29 Vdc |
| High DC Cut-off Voltage | 31 Vdc |
| No Load Power Consumption | <20W |
| Saving Mode Power Consumption | <10W |
9.3 Table 3 Charge Mode Specifications
| INVERTER MODEL | POW-LVM2.4K-24V |
|---|---|
| Utility Charging Mode | |
| Charging Algorithm | 3-Step |
| AC Charging Current | 20/30Amp (@VI/p=120Vac) |
| Bulk Charging Voltage (Flooded Battery) | 29.2 |
| Bulk Charging Voltage (AGM / Gel Battery) | 28.2 |
| Floating Charging Voltage | 27Vdc |
| Solar Charging Mode | |
| Max. PV Array Power | 1200W |
| Charging Current (PWM) | 50Amp |
| System DC Voltage | 24Vdc |
| Operating Voltage Range | 30~32Vdc |
| Max. PV Array Open Circuit Voltage | 80Vdc |
| Standby Power Consumption | 2W |
| DC Voltage Accuracy | +/-0.3% |
| Joint Utility and Solar Charging | |
| Max Charging Current | 80Amp |
| Default Charging Current | 50Amp |
9.4 Table 4 General Specifications
| INVERTER MODEL | POW-LVM2.4K-24V |
|---|---|
| Safety Certification | CE |
| Operating Temperature Range | 0°C to 55°C |
| Storage temperature | -15°C~60°C |
| Dimension (D* W* H) | 100x272x355 mm |
| Net Weight | 6.9 kg |
9.5 Appendix: Approximate Back-up Time Table
| Model | Load (VA) | Backup Time @24Vdc 100Ah (min) | Backup Time @24Vdc 200Ah (min) |
|---|---|---|---|
| 2.4KW | 300 | 449 | 1100 |
| 600 | 222 | 525 | |
| 900 | 124 | 303 | |
| 1200 | 95 | 227 | |
| 1500 | 68 | 164 | |
| 1800 | 56 | 126 | |
| 2100 | 48 | 108 | |
| 2400 | 35 | 94 | |
| 2700 | 31 | 74 | |
| 3000 | 28 | 67 |
Note: Backup time depends on the quality of the battery, age of battery, and type of battery. Specification of batteries may vary depending on different manufacturers.
10. Warranty and Support
The PowMr 2.4KW PWM Hybrid Solar Inverter comes with a 12-month warranty. For technical support, service, or warranty claims, please contact your local dealer or the PowMr customer service. Refer to the official website or contact customer service for the latest user manual and support information.
User Manual PDF: For a detailed user manual in PDF format, please refer to the official document: PowMr Inverter User Manual (PDF).
11. User Tips
- Handling Weight: The inverter weighs approximately 6.9 kg. Ensure you have adequate support or assistance when lifting and mounting the unit to prevent injury.
- Battery Compatibility: This inverter is compatible with various 24V system batteries, including lithium and lead-acid types (Flooded, AGM, Gel, Sealed Lead Acid). Always select the correct battery type in the LCD settings (Program 05) for optimal charging and performance.
- PV Input Voltage: Pay close attention to the PV input voltage range (30-80VDC) and ensure your solar panels are configured to operate within this range to avoid damage and ensure efficient charging.
12. Frequently Asked Questions (FAQ)
- Q: What is the weight of the PowMr 2.4KW Hybrid Solar Inverter?
- A: The inverter weighs 6.9 kg (approximately 15.2 lbs).
- Q: What types of batteries are compatible with this inverter?
- A: The inverter is compatible with various 24V system batteries, including lithium and lead-acid batteries (Flooded, AGM, Gel, Sealed Lead Acid). Ensure you select the correct battery type in the LCD settings.
- Q: What are the available charging modes?
- A: The inverter supports four charging modes: Solar First, Utility First, Solar and Utility, and Only Solar. These can be configured via the LCD settings (Program 16).