Growatt SPE 12000 ES

Contents

Growatt 12000W Hybrid Solar Inverter SPE 12000 ES User Manual

Model: SPE 12000 ES | Brand: Growatt

1. Introduction

The Growatt SPE 12000 ES is a multifunctional PV Hybrid inverter, integrating an MPPT solar charge controller, a high-frequency pure sine wave inverter, and a UPS function module. It is designed for both off-grid backup power and self-consumption applications, capable of operating with or without batteries.

For a complete system, additional devices such as PV modules, a generator, or a utility grid are required. The inverter supports a plug-and-play monitoring device (WIFI / 4G module) for remote monitoring via mobile phone or website.Product Features

  • Rated power: 8KW to 12KW, with a power factor of 1.
  • Dual MPPT trackers, supporting a maximum PV array power of 10000W to 15000W.
  • MPPT Voltage range: 60Vdc-480Vdc, 550Voc.
  • Integrated pure sine wave inverter and MPPT solar charge controller.
  • Built-in ATS for automatic grid and generator switching.
  • Operates with or without batteries.
  • CAN/RS485 for BMS communication.
  • Optional WIFI/4G wireless monitoring.
  • Parallel operation for up to 9 units (with battery connected).
  • Grid-tied function.
  • Dual outputs.
  • Grid peak shaving.
  • External CT for zero exporting into grid.

2. Safety Information

WARNING!

  • All installation and wiring must be performed by qualified personnel.
  • Risk of electric shock: Exercise extreme caution due to high battery voltages. Always disconnect all circuit breakers before making any connections to the battery power cable, AC power source, or PV input.
  • Ensure correct polarity for all connections (battery, AC, PV). Incorrect polarity can cause short circuits, overheating, fire, or damage to the inverter and connected appliances.
  • Do not install the inverter in areas with salt damage, as corrosion may occur and lead to fire. Salt-damaged areas are defined as those within 500m of the shore or affected by sea breezes.
  • Do not place anything between the flat part of the inverter terminal and the ring terminal to prevent short circuits.
  • Do not apply anti-oxidant substances on terminals before tightening connections.
  • Appliances like air conditioners require a time-delay function to prevent damage from short power interruptions. Consult the appliance manufacturer before connecting to avoid issues.

3. Package Contents

Upon receiving your inverter, please inspect the package for any damage. Ensure all items listed below are included:

ItemDescriptionQuantity
AThe unit (Inverter)1
BCommunication cable1
CParallel communication cable1
DR-type terminal1
EO-type terminal4
FUser manual1

4. Installation Instructions

4.1 General Points for Attention

  • Install the inverter at eye level for easy reading of the LCD display.
  • Ensure the ambient temperature is between -10°C and 50°C for optimal operation.
  • Mount the inverter vertically on a wall.
  • Avoid installing in confined spaces and ensure adequate ventilation. Maintain sufficient clearance around the unit for heat dissipation and access for wiring.
  • Mount only on concrete or other non-combustible surfaces.
  • Secure the unit with three M4 or M5 screws.

4.2 Panel and Port Definitions

The inverter features a clear display panel and various connection ports. Refer to the diagram below for an overview of the panel and port definitions.

Diagram of Growatt SPE 12000 ES Inverter Panel and Port Definitions
Figure 1: Inverter Panel and Port Definitions
No.DescriptionNo.Description
1LCD display2Status indicator
3Charging indicator4Fault indicator
5Function buttons6USB communication port
8BMS communication port (CAN/RS485)9RS485 communication port (expansion)
10Parallel communication ports11DIP switches
14Generator input15Grid input
16PE (Protective Earth)17AC output (main)
18AC output (smart load)19WiFi / 4G communication port
20Battery input21Power on/off switch
22PV1 input23PV2 input
12EXT CT13Dry contact

4.3 Battery Connection

Before connecting batteries, ensure all circuit breakers are disconnected. Use appropriate cable sizes and terminals as specified below. Always connect positive to positive and negative to negative.

4.3.1 Wiring Preparation

  • Install a separate DC breaker (over-current protector) between the battery and the inverter. Recommended breaker size for SPE 12000 ES is 400A / 60VDC.
  • Use recommended cable sizes: 2 * 2 AWG (2*33.62mm²) for SPE 12000 ES.
  • Ensure bolts are tightened to 2-3 Nm.
  • For battery module selection, choose appropriate batteries based on your system needs. For SPE 12000 ES, 400Ah capacity batteries (Lithium or Lead-acid) are recommended.

4.3.2 Battery Power Cable Connection

  1. Assemble battery ring terminals with recommended cable and terminal sizes.
  2. Connect all battery packs as required.
  3. Insert the ring terminal of the battery cable into the inverter's battery connector. Ensure bolts are tightened to 2Nm.
  4. Verify correct polarity at both the battery and inverter.

4.4 Lithium Battery Communication Cable Connection

If using lithium batteries, connect the BMS communication cable between the battery and the inverter. It is recommended to use lithium batteries tested with Growatt configurations.

  1. Connect one end of the battery's communication cable to the inverter's BMS communication port (supports RS485 or CAN protocols).
  2. Plug the other end of the communication cable into the battery's communication port (RS485 or CAN).

The inverter BMS port pin assignment is as follows:

Pin numberBMS portRS485 port (for expansion)
1RS485B
2RS485ARS485B
3RS485A
4CANH
5CANL
6----
7----
8----

Note: For normal communication with lithium battery BMS, set the battery type to "Li" in program 5. The LCD will then automatically switch to program 36 to select the communication protocol. Consult your dealer or manufacturer for specific protocol addresses.

4.5 AC Connection

Before connecting to the AC input power source, install a separate AC breaker between the inverter and the grid. This ensures safe disconnection during maintenance and protection from overcurrent.

4.5.1 Wiring Preparation

  • Recommended AC breaker size for SPE 12000 ES is 70A / 230VAC.
  • Use recommended cable sizes: 1 * 6 AWG (13.3mm²) for SPE 12000 ES.
  • Ensure bolts are tightened to 1.2-1.6 Nm.

4.5.2 Grid/GEN/Load/Smart Load Wires Connection

Follow these steps for Load/Smart Load/Grid/GEN connections:

  1. Remove the insulation covers of the seven wires.
  2. Connect the PE (Protective Earth) line first.
  3. Connect the Load, Smart Load, Grid, and GEN lines according to polarity.
  4. Polarity: Ground (yellow-green), L (brown or black), N (blue).
  5. Insert wires into the terminal block, ensuring the buckle presses the wire tightly.
System Wiring Diagram for Growatt Hybrid Inverter
Figure 2: System Wiring Diagram

4.6 PV Connection

Before connecting PV modules, install a separate DC circuit breaker between the inverter and PV modules.

4.6.1 Wiring Preparation

  • Recommended DC breaker size for SPE 12000 ES is 27A / 550Vdc.
  • Use recommended cable sizes: 1 * 9 AWG (8.4mm²) for SPE 12000 ES.
  • Ensure bolts are tightened to 1.2-1.6 Nm.

4.6.2 PV Module Selection

  • The open circuit voltage (Voc) of PV modules must not exceed the inverter's maximum PV array open circuit voltage (550Vdc).
  • The Voc of PV modules should be higher than the inverter's start-up voltage (120Vdc).
  • The PV array MPPT voltage range is 60Vdc-480Vdc.
  • It is recommended to use 2-11 photovoltaic panels.

4.6.3 PV Cable Connection

  1. Remove 10mm of insulation from positive and negative conductors.
  2. Connect the positive pole (+) of the connection cable to the positive pole (+) of the PV input connector.
  3. Connect the negative pole (-) of the connection cable to the negative pole (-) of the PV input connector.

5. Operation

5.1 Power ON/OFF

After completing all connections and ensuring they are correct:

  1. Switch on the battery switch.
  2. Switch on the inverter switch.
  3. Wait approximately 40 seconds for the inverter to output power.

5.2 Display Panel Introduction

The inverter's front panel features an LCD display, three indicators, and four function keys to show operating status and input/output power information.

Growatt Inverter Display Panel with Icons and Descriptions
Figure 3: Inverter Display Panel Overview

5.2.1 LED Indicators

IndicatorStatusMessages
AC/INV (Green)Solid OnOutput is powered by utility in Line mode.
FlashingOutput is powered by battery or PV in battery mode.
CHG (Green)Solid OnBattery is fully charged.
FlashingBattery is charging.
FAULT (Red)Solid OnFault occurs in the inverter.
FlashingWarning condition occurs in the inverter.

5.2.2 Function Buttons

ButtonDescription
ESCTo exit setting mode
UPTo go to previous selection
DOWNTo go to next selection
ENTERTo confirm the selection in setting mode or enter setting mode

5.2.3 LCD Display Icons

The LCD displays various icons representing system status and information. Refer to the manual for a complete list of icons and their meanings.

5.2.4 Display Information

The LCD display information can be cycled through by pressing the "UP" or "DOWN" keys. This includes voltage, frequency, current, power, temperature, energy, and firmware version. Battery charge and discharge status are also displayed.

6. Parallel Installation Guide

This inverter supports parallel operation in two modes:

  • Single-phase parallel operation with up to 9 units.
  • Maximum 9 units working together to support 3-phase equipment (7 units maximum for one phase).

6.1 Points of Attention for Parallel Operation

  • Ensure all breakers on the load side are disconnected.
  • All battery cables must be of the same length to avoid voltage differences.
  • All inverters must share the same battery bank to prevent fault mode.
  • Each inverter in the parallel system must be connected to a separate PV string. Do not share PV ports.
  • Recommended battery capacity for SPE 12000 ES parallel systems: 800AH for 2 units, up to 3600AH for 9 units.

6.2 Wire Connections for Parallel Systems

When inverters are connected in parallel, ensure N wires are connected together, and L wires are connected together at the Grid, Generator, and AC Output.

Parallel Connection Wiring Diagram for Multiple Inverters
Figure 4: Parallel Connection Wiring Diagram
  • For DC input, positive (+) wires are connected together, and negative (-) wires are connected together.
  • Each inverter battery must be connected to a DC circuit breaker (recommended 400A). For a system with multiple inverters, the total circuit breaker should be 400A multiplied by the number of parallel inverters.
  • Set the CAN communication DIP switches to 'ON' for the first and last inverters in the parallel chain.
  • Connect the BMS communication cable between the battery and one inverter (preferably the master inverter) in the parallel system.

7. Maintenance

To ensure optimal performance and longevity of your Growatt inverter, regular maintenance is recommended:

  • Regular Cleaning: Keep the inverter's exterior clean and free from dust and debris. Ensure ventilation openings are not blocked.
  • Connection Checks: Periodically inspect all wiring connections (battery, AC, PV) to ensure they are secure and free from corrosion. Tighten any loose connections.
  • Environmental Inspection: Ensure the installation environment remains within specified temperature and humidity ranges. Check for any signs of moisture ingress or pest activity.
  • Firmware Updates: Check the Growatt website or contact support for available firmware updates to ensure your inverter has the latest features and bug fixes.
  • Professional Inspection: It is recommended to have a qualified technician perform a comprehensive inspection and service at least once a year.

8. Troubleshooting

This section provides general guidance for common issues. For detailed troubleshooting, refer to the comprehensive user manual PDF or contact technical support.

  • No Power Output: Check all circuit breakers (DC, AC) to ensure they are in the ON position. Verify battery and PV connections. Check the LCD display for any fault indicators.
  • Fault Indicator On: Note the specific fault code displayed on the LCD. Refer to the manual's fault code section for explanations and solutions.
  • Low Efficiency: Ensure PV panels are clean and not shaded. Check PV array voltage and current against specifications. Verify battery health and charge status.
  • Communication Issues: Check WiFi/4G module connection. Ensure network connectivity. Verify communication settings in the inverter.

If you encounter persistent issues or complex problems, do not attempt repairs yourself. Contact qualified service personnel.

9. Specifications

Below are the key technical specifications for the Growatt SPE 12000 ES Hybrid Solar Inverter:

CategoryParameterValue
Input Data (DC)Max. recommended PV power (for module STC)15000W
Max. DC voltage550V
MPP voltage range60V-480V
No. of MPP trackers2
No. of PV strings per MPP tracker1
Max. input current per MPP tracker27A
Output Data (AC)AC nominal power12000W
Max. AC apparent power12000VA
Nominal AC voltage230V
AC grid frequency50/60Hz
Output current52.2A
THDi< 5%
Battery Data (DC)Nominal DC voltage48V
Max charging and discharging current250A/280A
Type of batteryLithium/Lead-acid
Backup Power (AC)AC nominal output power12000W
Nominal AC output voltage230V
Nominal AC output frequency50/60Hz
Switch time<20ms@Single, <30ms@Parallel
EfficiencyMax. conversion efficiency (PV/AC)96.5%
European efficiency @ vnominal (PV/AC)95.50%
General DataDimensions (W / H / D)550 / 465 / 150mm
Weight21.5kg
Operating temperature range-10℃ ~ +50℃
Noise emission (typical)< 75dB
Self-consumption< 75W
CoolingDC fan
Protection degreeIP20
CommunicationWiFi/4G

10. User Tips

  • Voltage Compatibility: The nominal AC output voltage for this inverter is 230V. If your local grid or appliances require 120V or 240V, ensure you have appropriate transformers or a compatible model.
  • Monitoring: Utilize the optional WiFi/4G communication module and the Shinephone APP to monitor your system's performance remotely. This can help in early detection of issues and optimization.

11. Warranty and Support

For detailed warranty information, technical support, and service inquiries, please refer to the official Growatt documentation or contact your authorized dealer.

A comprehensive user manual in PDF format is available for download: Growatt SPE 12000 ES User Manual (PDF).


Documents and downloads

Ask a question about this manual

Ask about setup, troubleshooting, compatibility, parts, safety, or missing instructions. Manuals+ will review the question and use this page’s manual context to help answer it.

After a successful submission, we securely hash the supplied account or form email before sending it to Microsoft Advertising for conversion attribution. Privacy details.