1. Introduction
The LEFOO LF12 is a robust three-phase air pressure switch designed for precise pressure regulation in air compressors and water pumps. It features an integrated unloader valve to prevent motor overload during startup and an On-Off knob for manual control. This manual provides essential information for the safe installation, operation, and maintenance of your LF12 pressure switch.

Figure 1: LEFOO LF12 Air Pressure Switch
2. Safety Information
- Always disconnect power before installing, servicing, or performing any maintenance on the pressure switch or connected equipment.
- Installation and wiring should only be performed by qualified personnel in accordance with local electrical codes and regulations.
- Ensure the pressure switch's electrical rating matches the power supply and motor requirements.
- Do not exceed the maximum pressure rating of the device.
- Protect the switch from moisture, dust, and extreme temperatures unless specifically rated for such environments.
3. Product Overview and Components
The LF12 pressure switch is designed for durability and ease of use. Key features include:
- Pressure Regulation: Automatically controls the operating pressure of compressors and pumps.
- Unloader Valve: Prevents the compressor from starting under load, reducing strain on the motor.
- On-Off Knob: Provides manual control to cut off the compressor or pump.
- Thermal Relay: Offers overload protection, preventing motor burnout.
- Connection Options: Available in single or four-port manifold styles for versatile installation.

Figure 2: Top view showing the On-Off/AUTO knob

Figure 3: Internal components of the LF12 pressure switch
4. Specifications
The LF12 series offers various configurations. Refer to the table below for general specifications and the ordering reference for specific model details.

Figure 4: Dimensional Drawing (Dimensions in mm)
4.1 General Specifications
| Model | Operating Pressure Range | Differential | Factory Setting | Electrical Rating | Contact Arrangement | Connection |
|---|---|---|---|---|---|---|
| LF12 | 1-6bar | 0.7-2bar | 2-3bar | Single phase 120VAC/10A; 230VAC/10A; Three phase 120VAC/10A; 230VAC/10A; 400VAC/7.5A; 400VAC/11A; 500VAC/6A; 500VAC/9A; 690VAC/4.5A; 690VAC/6.5A | NC | G1/2 or NPT1/2 or R1/2 Female |
| 3-11bar | 1.5-3.5bar | 6-8bar | ||||
| 6-16bar | 2-7bar | 9-12bar | ||||
| 5-25bar | 3-8bar | 16-20bar | ||||
| 12-35bar | 3-8bar | 25-30bar |
4.2 LF12 Order Reference Number Breakdown
The LF12 model number can be broken down into several components, each indicating a specific feature:

Figure 5: LF12 Order Reference Number Breakdown
- A: Connection Type
- 1: Single port
- 2: Four port
- B: Female Connection Size
- 1: G1/2+3*G1/4
- 2: G3/8+3*G1/4
- 3: NPT1/2+3*NPT1/4
- 4: R1/2+3*R1/4
- C: Unloader Valve Type
- 1: Without
- 2: Vertical (Brass)
- 3: Horizontal (zinc alloy)
- 4: Vertical (zinc alloy)
- D: Unloader Valve Connection
- 1: Without
- 2: Φ6.0
- 3: Φ6.4
- 4: Φ6.5
- E: Handle Type
- 1: Without
- 2: Rotary Knob
- F: Thermal Relay
- 1: Without
- 2: With
5. Setup and Installation
Before beginning installation, ensure all safety precautions are followed.
5.1 Mechanical Installation
- Mount the LF12 pressure switch securely to a stable surface or directly onto the compressor/pump system using appropriate fittings. Refer to the dimensional drawing (Figure 4) for mounting hole locations and connection sizes.
- Connect the pressure inlet of the switch to the pressure line of the compressor or pump. Ensure all connections are tight and leak-free.
- If your model includes an unloader valve, connect it according to the system requirements.
5.2 Electrical Wiring
- Disconnect all power sources to the compressor/pump and the pressure switch before wiring.
- Open the electrical cover of the LF12 switch.
- Connect the power supply wires and motor wires to the appropriate terminals inside the switch. Ensure correct phase connections for three-phase systems.
- If your model includes a thermal relay, ensure it is correctly integrated into the motor circuit for overload protection.
- Close the electrical cover securely to protect against environmental factors.
6. Operating Instructions
6.1 Initial Power-Up
- After installation, ensure the On-Off knob is in the 'OFF' position.
- Restore power to the system.
- Slowly turn the On-Off knob to the 'AUTO' position. The compressor/pump should start if the pressure is below the cut-in setting.
6.2 Pressure Adjustment
The LF12 allows for adjustment of the cut-in and cut-out pressure settings. This typically involves adjusting internal screws or mechanisms. Consult the specific instructions provided with your LF12 variant for detailed adjustment procedures. Always make small adjustments and test the system's response.
6.3 Manual Operation
The On-Off knob can be used to manually stop the compressor or pump. Turn the knob to 'OFF' to immediately cease operation. Return it to 'AUTO' for automatic pressure regulation.
7. Maintenance
- Regular Inspection: Periodically check the pressure switch for any signs of physical damage, corrosion, or loose connections.
- Cleanliness: Keep the switch free from excessive dust, dirt, and debris. Use a dry cloth for cleaning.
- Pressure Line Check: Ensure the pressure lines connected to the switch are clear and free from blockages.
- Thermal Relay Test (if applicable): If your model has a thermal relay, periodically test its functionality according to manufacturer guidelines to ensure proper overload protection.
8. Troubleshooting
- Compressor/Pump Not Starting:
- Check if the power supply is connected and active.
- Ensure the On-Off knob is in the 'AUTO' position.
- Verify that the system pressure is below the set cut-in pressure.
- Inspect wiring for loose connections or damage.
- Compressor/Pump Not Stopping:
- Check for leaks in the air or water system that prevent pressure from reaching the cut-out setting.
- Verify that the system pressure is reaching the set cut-out pressure.
- Inspect the pressure switch for internal damage or blockages.
- Motor Overheating/Tripping:
- If equipped with a thermal relay, it may be tripping due to motor overload. Check the motor for excessive load, proper ventilation, or mechanical issues.
- Ensure the thermal relay settings are appropriate for the motor's current draw.
9. User Tips
- For optimal performance and longevity, ensure the pressure switch is installed in a location protected from direct impact and excessive vibration.
- When adjusting pressure settings, make small incremental changes and observe the system's behavior to avoid over-adjustment.
- Consider installing a pressure gauge near the switch to easily monitor system pressure and verify switch operation.
10. Warranty and Support
LEFOO products are manufactured by Zhejiang Lefoo Controls Co., Ltd., a company committed to developing reliable, high-quality control devices. For warranty information, technical support, or specific product inquiries, please contact your seller or the manufacturer directly. LEFOO offers OEM and ODM support for customized requirements.