1. Introduction
This manual describes the assembly, installation, operation, and troubleshooting of the PowMr POW-HVM13.2M Hybrid Solar Inverter Charger. This multi-function inverter/charger combines the functions of an inverter, solar charger, and battery charger to provide uninterruptible power support. Its comprehensive LCD display offers user-configurable and easy-accessible button operation for settings such as battery charging current, AC/solar charger priority, and acceptable input voltage based on different applications.
The POW-HVM13.2M is a 13.2kW 48V off-grid hybrid photovoltaic inverter and controller, integrating a pure sine wave inverter, dual-channel MPPT solar charger, AC/generator charger, and battery energy storage management system into a single multi-functional energy storage power supply. It can simultaneously connect to solar photovoltaic panels, household AC/diesel generators, and 48V batteries, automatically and intelligently allocating power sources to achieve uninterrupted household power supply. It is compatible with lead-acid batteries and lithium batteries with BMS communication, supports dual-load branch output, mobile WiFi remote monitoring, and battery equalization maintenance.
1.1 Key Features
- Pure sine wave output for sensitive electronics.
- Configurable input voltage range for home appliances and personal computers via LCD setting.
- Configurable battery charging current based on applications via LCD setting.
- Configurable AC/Solar Charger priority via LCD setting.
- Compatible with mains voltage or generator power.
- Auto restart while AC is recovering.
- Overload, over temperature, and short circuit protection.
- Smart battery charger design for optimized battery performance.
- Cold start function.
- Dual high-power MPPT for up to 16KW photovoltaic input.
- Deep lithium battery compatibility with BMS communication.
- Dual load intelligent hierarchical output.
- Wide operating temperature range (-10℃ to 50℃) with removable dust filter.
- Up to 94% inverter peak efficiency, low no-load power consumption (<80W), and energy-saving mode standby power (<15W).
1.2 Basic System Architecture
The following diagram illustrates the basic application of this inverter/charger, showing how it integrates with a generator or utility, PV modules, and external battery packs to power home appliances.
Consult with your system integrator for other possible system architectures depending on your requirements. This inverter can power all kinds of appliances in home or office environments, including motor-type appliances such as tube lights, fans, refrigerators, and air conditioners.
2. Safety Instructions
WARNING: This chapter contains important safety and operating instructions. Read and keep this manual for future reference.
- Before using the unit, read all instructions and cautionary markings on the unit, the batteries, and all appropriate sections of this manual.
- CAUTION --To reduce the risk of injury, charge only deep-cycle lead-acid type rechargeable batteries. Other types of batteries may burst, causing personal injury and damage.
- Do not disassemble the unit. Take it to a qualified service center when service or repair is required. Incorrect re-assembly may result in a risk of electric shock or fire.
- To reduce the risk of electric shock, disconnect all wirings before attempting any maintenance or cleaning. Turning off the unit will not reduce this risk.
- CAUTION - Only qualified personnel can install this device with a battery.
- NEVER charge a frozen battery.
- For optimum operation of this inverter/charger, please follow the required specifications to select the appropriate cable size. It's very important to correctly operate this inverter/charger.
- Be very cautious when working with metal tools on or around batteries. A potential risk exists to drop a tool to spark or short circuit batteries or other electrical parts and could cause an explosion.
- Please strictly follow the installation procedure when you want to disconnect AC or DC terminals. Please refer to the INSTALLATION section of this manual for details.
- One piece of 150A fuse is provided as over-current protection for the battery supply.
- GROUNDING INSTRUCTIONS - This inverter/charger should be connected to a permanent grounded wiring system. Be sure to comply with local requirements and regulations to install this inverter.
- NEVER cause AC output and DC input short-circuited. Do NOT connect to the mains when DC input short circuits.
- Warning!! Only qualified service persons are able to service this device. If errors still persist after following the troubleshooting table, please send this inverter/charger back to a local dealer or service center for maintenance.
3. Unpacking and Inspection
Before installation, please inspect the unit. Be sure that nothing inside the package is damaged. You should have received the following items inside the package:
- The unit x 1
- User manual x 1
- Ring terminal x 1
- MC4 terminal head x 2
Watch the unboxing video for a visual guide to the package contents:
4. Installation
4.1 Preparation
Before connecting all lines, remove the screws under the machine and remove the bottom cover plate.
4.2 Mounting the Unit
Consider the following points before selecting where to install:
- Do not mount the inverter on flammable construction materials.
- Mount on a solid surface.
- Install this inverter at eye level to allow the LCD display to be read at all times.
- For proper air circulation to dissipate heat, allow a clearance of approx. 20 cm to the side and approx. 50 cm above and below the unit.
- The ambient temperature should be between 0°C and 55°C to ensure optimal operation.
- The recommended installation position is to be adhered to the wall vertically.
- Make sure that other objects and surfaces are left with enough space from the machine to ensure adequate heat dissipation and that there is enough room to remove the wires.
SUITABLE FOR MOUNTING ON CONCRETE OR OTHER NON-COMBUSTIBLE SURFACE ONLY.
Install the unit by screwing two M4 or M5 screws.
4.3 Battery Connection
CAUTION: For safety operation and regulation compliance, it's requested to install a separate DC over-current protector or disconnect device between the battery and inverter. It may not be requested to have a disconnect device in some applications; however, it's still requested to have over-current protection installed. Please refer to the typical amperage in the table below for the required fuse or breaker size.
WARNING! All wiring must be performed by qualified personnel.
WARNING! It's very important for system safety and efficient operation to use appropriate cable for battery connection. To reduce the risk of injury, please use the proper recommended cable as below.
| Model | Wire Size | Cable (mm²) | Torque value (max) |
|---|---|---|---|
| 8.2KW/10.2KW (Referenced for 13.2kW) | 1 x 2AWG | 25 | 2 Nm |
Please follow the steps below to implement battery connection:
- Remove insulation sleeve 18 mm for positive and negative conductors.
- Suggest putting bootlace ferrules on the end of positive and negative wires with a proper crimping tool.
- Connect all battery packs as shown in the diagram below.
- Insert the battery wires flatly into the battery connectors of the inverter and make sure the bolts are tightened with a torque of 2 Nm in a clockwise direction. Make sure the polarity at both the battery and the inverter/charger is correctly connected and conductors are tightly screwed into the battery terminals. Recommended tool: #2 Pozi Screwdriver.
WARNING: Shock Hazard! Installation must be performed with care due to high battery voltage in series.
CAUTION!! Before making the final DC connection or closing the DC breaker/disconnector, be sure positive (+) must be connected to positive (+) and negative (-) must be connected to negative (-).
4.4 AC Input/Output Connection
CAUTION!! Before connecting to the AC input power source, please install a separate AC breaker between the inverter and the AC input power source. This will ensure the inverter can be securely disconnected during maintenance and fully protected from overcurrent of the AC input. The recommended specification of the AC breaker is 63A for 8.2KW/10.2KW models.
CAUTION!! There are two terminal blocks with "IN" and "OUT" markings. Please do NOT mis-connect input and output connectors.
WARNING! All wiring must be performed by qualified personnel.
WARNING! It's very important for system safety and efficient operation to use appropriate cable for AC input connection. To reduce the risk of injury, please use the proper recommended cable size as below.
| Model | Gauge | Cable (mm²) | Torque Value |
|---|---|---|---|
| 8.2KW/10.2KW (Referenced for 13.2kW) | 10 AWG | 6 | 1.2 Nm |
Please follow the steps below to implement AC input/output connection:
- Before making AC input/output connection, be sure to open the DC protector or disconnector first.
- Remove insulation sleeve 10mm for six conductors. Shorten phase L and neutral conductor N by 3 mm.
- Insert AC input wires according to the polarities indicated on the terminal block and tighten the terminal screws. Be sure to connect the PE protective conductor (yellow-green) first.
- Then, insert AC output wires according to the polarities indicated on the terminal block and tighten the terminal screws.
- Make sure the wires are securely connected.
WARNING: Be sure that the AC power source is disconnected before attempting to hardwire it to the unit.
4.5 PV Connection
CAUTION: Before connecting to PV modules, please install separately a DC circuit breaker between the inverter and PV modules.
WARNING! It's very important for system safety and efficient operation to use appropriate cable for PV module connection. To reduce the risk of injury, please use the proper recommended cable size as below.
| Model | Wire Size | Cable (mm²) | Torque value (max) |
|---|---|---|---|
| 8.2KW/10.2KW (Referenced for 13.2kW) | 1 x 10AWG | 6 | 1.2 Nm |
PV Module Selection: When selecting proper PV modules, please be sure to consider the parameters:
- Open circuit Voltage (Voc) of PV modules does not exceed the max. PV array open circuit voltage of the inverter.
- Open circuit Voltage (Voc) of PV modules should be higher than the min. battery voltage.
| INVERTER MODEL | 8.2KW/10.2KW (Referenced for 13.2kW) |
|---|---|
| Max. PV Array Open Circuit Voltage | 500Vdc |
| PV Array MPPT Voltage Range | 90Vdc~450Vdc |
Take a 250Wp PV module as an example. After considering the above two parameters, the recommended module configurations are listed below:
| Solar Panel Spec. (reference) | SOLAR INPUT (Min in serial: 6 pcs, max. in serial: 13 pcs) | Q'ty of panels | Total input power |
|---|---|---|---|
| 250Wp, Vmp: 30.1Vdc, Imp: 8.3A, Voc: 37.7Vdc, Isc: 8.4A, Cells: 60 | 6 pcs in serial | 6 pcs | 1500W |
| 8 pcs in serial | 8 pcs | 2000W | |
| 12 pcs in serial | 12 pcs | 3000W | |
| 13 pcs in serial | 13 pcs | 3250W | |
| 12 pieces in serial and 3 sets in parallel | 36 pcs | 8200W | |
| 10 pieces in serial and 4 sets in parallel | 40 pcs | 10200W |
PV Module Wire Connection:
Step 1: Check the input voltage of PV array modules. The acceptable input voltage of the inverter is 120VDC - 500VDC. Please make sure that the maximum current load of each PV input connector is 10A.
CAUTION: Exceeding the maximum input voltage can destroy the unit!! Check the system before wire connection.
Step 2: Disconnect the DC circuit breaker.
Step 3: Assemble provided PV connectors with PV modules by following the steps below. Components for PV connectors and Tools:
| Component | Image |
|---|---|
| Female connector housing | ![]() |
| Female terminal | ![]() |
| Male connector housing | ![]() |
| Male terminal | ![]() |
| Crimping tool and spanner | ![]() |
Cable preparation and connector assembly process: Strip one cable 8 mm on both end sides and be careful NOT to nick conductors.
Step 4: Check the correct polarity of the connection cable from PV modules and PV input connectors. Then, connect the positive pole (+) of the connection cable to the positive pole (+) of the PV input connector. Connect the negative pole (-) of the connection cable to the negative pole (-) of the PV input connector.
4.6 Communication Connection
1. Wi-Fi cloud communication (option): Use the supplied communication cable to connect to the inverter and Wi-Fi module. Download the APP from the APP store and refer to the "Wi-Fi Plug Quick Installation Guideline" to set up the network and register. The inverter status will be shown by the mobile phone APP or computer webpage.
2. GPRS cloud communication (option): Use the supplied communication cable to connect to the inverter and GPRS module, and then apply external power to the GPRS module. Download the APP from the APP store and refer to the "GPRS RTU Quick Installation Guideline" to set up the network and register. The inverter status will be shown by the mobile phone APP or computer webpage.
3. Battery communication: The communication between the battery and the inverter can be realized through the battery communication interface, allowing the inverter and the lithium battery to exchange information (Baud rate: 9600).
4. Lithium battery and inverter connection: Use power cables and communication cables for lithium batteries and inverters to connect. Note: For lithium battery and inverter positive and negative positions, check the correct installation. The RJ45 connector of the communication cable connects to the BMS port of the inverter, and the other RJ45 connector connects to the RS485 port of the lithium battery. Before connecting, make sure that the lithium battery and inverter are turned off. (It is recommended to install a circuit breaker for the power cables of the lithium battery and the inverter battery interface. Otherwise, a spark may occur.)
The lithium battery communication cable interface is shown in the figure:
In order to communicate with the lithium battery BMS, you should press the "ENTER" button for a long time, and set the battery type as "LIB-485" in program 05. Then select the matching battery protocol in Program 43.
4.7 Final Assembly
After connecting all wirings, please put the bottom cover back by screwing two screws.
5. Operation
5.1 Power ON/OFF
Once the unit has been properly installed and the batteries are connected well, simply press the On/Off switch (located on the button of the case) to turn on the unit.
5.2 Operation and Display Panel
The operation and display panel, shown below, is on the front panel of the inverter. It includes three indicators, four function keys, and an LCD display, indicating the operating status and input/output power information.
| LED Indicator | Color | Status | Messages |
|---|---|---|---|
| INV/AC | Green | Solid On | Output is powered by utility in Line mode. |
| Flashing | Output is powered by battery or PV in battery mode. | ||
| CHG | Green | Solid On | Battery is fully charged. |
| Flashing | Battery is charging. | ||
| FAULT | Red | Solid On | Fault occurs in the inverter. |
| Flashing | Warning condition occurs in the inverter. |
| Function Key | Description |
|---|---|
| ESC | To exit setting mode |
| UP | To go to previous selection |
| DOWN | To go to next selection |
| ENTER | To confirm the selection in setting mode or enter setting mode |
5.3 LCD Display Icons
The LCD display provides various icons to indicate the inverter's status and operational information.
| Icon | Function description |
|---|---|
| GRID icon | Indicates the AC input. |
| SOLAR icon | Indicates the PV input. |
| Numeric/Unit displays | Indicate input voltage, input frequency, PV voltage, charger current (if PV in charging for 10.2KW models), charger power, battery voltage. |
| 8.8.8 (Program) | Indicates the setting programs. |
| Warning/Fault icon | Indicates the warning and fault codes. |
| LOAD icon | Indicates overload. |
| Mains connection icon | Indicates unit connects to the mains. |
| PV panel connection icon | Indicates unit connects to the PV panel. |
| AC BYPASS icon | Indicates load is supplied by utility power. |
| Utility charger circuit icon | Indicates the utility charger circuit is working. |
| DC/AC inverter circuit icon | Indicates the DC/AC inverter circuit is working. |
| Mute icon | Indicates unit alarm is disabled. |
5.4 LCD Setting
After pressing and holding the ENTER button for 3 seconds, the unit will enter setting mode. Press "UP" or "DOWN" button to select setting programs. Then, press "ENTER" button to confirm the selection or ESC button to exit.
CAUTION: When the battery type is set to "LIB-485", the setting items 12, 13, and 29 are displayed in percentage. When communication fails, the inverter will cut off the output.
CAUTION: When the battery type is set to "LIB-485", the user cannot modify the maximum charging current.
Refer to the manual's detailed tables (pages 20-28) for specific LCD setting programs and their selectable options, including output source priority, maximum charging current, AC input voltage range, battery type, auto restart settings, output frequency, output voltage, voltage points for SBU priority, floating charging voltage, low DC cut-off voltage, battery equalization settings, dual output voltage, and maximum second load.
5.5 Operating Mode Description
The inverter supports various operating modes, each with specific power flow and display indications. These modes include Line Mode, Standby Mode, and Grid-Tie Operation. Detailed LCD display examples for each mode and different power states (charged, discharged, power less than 1kW, power greater than 1kW) are provided in the manual (pages 29-33).
5.6 Battery Equalization Description
Equalization function is added into the charge controller. It reverses the buildup of negative chemical effects like stratification, a condition where acid concentration is greater at the bottom of the battery than at the top. Equalization also helps to remove sulfate crystals that might have built up on the plates. If left unchecked, this condition, called sulfation, will reduce the overall capacity of the battery. Therefore, it's recommended to equalize the battery periodically.
How to Apply Equalization Function: You must enable the battery equalization function in monitoring LCD setting program 30 first. Then, you may apply this function in the device by either one of the following methods:
- Setting equalization interval in program 35.
- Active equalization immediately in program 36.
When to Equalize: In the float stage, when the setting equalization interval (battery equalization cycle) is arrived, or equalization is active immediately, the controller will start to enter the Equalize stage.
Equalize charging time and timeout: In the Equalize stage, the controller will supply power to charge the battery as much as possible until the battery voltage raises to the battery equalization voltage. Then, constant-voltage regulation is applied to maintain the battery voltage at the battery equalization voltage. The battery will remain in the Equalize stage until the setting battery equalized time is arrived.
However, in the Equalize stage, when the battery equalized time is expired and the battery voltage doesn't rise to the battery equalization voltage point, the charge controller will extend the battery equalized time until the battery voltage achieves the battery equalization voltage. If the battery voltage is still lower than the battery equalization voltage when the battery equalized timeout setting is over, the charge controller will stop equalization and return to the float stage.
5.7 Mains and Lithium Battery Activation Function
- After 90s of mains power connection to the inverter, the machine is connected to the mains and starts to work.
- The inverter is in lithium battery mode (item 05 is LIP or LIL). After the mains is connected, the battery is not connected, and the mains activation function is automatically enabled.
6. Clearance and Maintenance for Anti-Dust Kit
6.1 Overview
Every inverter is already installed with an anti-dust kit from the factory. The inverter will automatically detect this kit and activate an internal thermal sensor to adjust the internal temperature. This kit also keeps dust from your inverter and increases product reliability in harsh environments.
6.2 Clearance and Maintenance
Step 1: Please loosen the screw in a counterclockwise direction on the top of the inverter.
Step 2: Then, the dustproof case can be removed, and the air filter foam taken out as shown in the diagram below.
Step 3: Clean the air filter foam and dustproof case. After clearance, re-assemble the dust-kit back to the inverter.
NOTICE: The anti-dust kit should be cleaned from dust every one month.
7. Troubleshooting
This section provides guidance on common problems, their possible causes, and recommended solutions.
7.1 Fault Reference Code
| Fault Code | Fault Event | Icon on |
|---|---|---|
| 01 | Fan is locked when inverter is off. | 01 ERROR |
| 02 | Over temperature | 02 ERROR |
| 03 | Battery voltage is too high | 03 ERROR |
| 04 | Battery voltage is too low | 04 ERROR |
| 05 | Output short circuited or over temperature is detected by internal converter components. | 05 ERROR |
| 06 | Output voltage is too high. | 06 ERROR |
| 07 | Overload time out | 07 ERROR |
| 08 | Bus voltage is too high | 08 ERROR |
| 09 | Bus soft start failed | 09 ERROR |
| 51 | Over current or surge | 51 ERROR |
| 52 | Bus voltage is too low | 52 ERROR |
| 53 | Inverter soft start failed | 53 ERROR |
| 55 | Over DC voltage in AC output | 55 ERROR |
| 57 | Current sensor failed | 57 ERROR |
| 58 | Output voltage is too low | 58 ERROR |
| 59 | PV voltage is over limitation | 59 ERROR |
7.2 Battery Fault Code (Lithium Battery Mode)
| Fault Code | Fault Event | Fault Condition |
|---|---|---|
| 02 | The battery temperature is too high Procedure | Lithium battery charging battery temperature ≥65°C; The discharge temperature of the lithium battery is higher than 70°C. |
| 03 | The battery voltage is too high Procedure | Lithium battery maximum single cell voltage >3.65V; Total voltage of lithium battery >54.6V (48V lithium battery). |
| 04 | The battery voltage is too low Procedure | Minimum voltage of a lithium battery cell <2.71V; Lithium battery total voltage <40.4V (48V lithium battery). |
7.3 Warning Indicator
| Warning Code | Warning Event | Audible Alarm | Icon flashing |
|---|---|---|---|
| 01 | Fan is locked when inverter is on. | Beep three times every second | 01 (flashing) |
| 03 | Battery is over-charged | Beep once every second | 03 (flashing) |
| 04 | Low battery | Beep once every second | 04 (flashing) |
| 07 | Overload | Beep once every 0.5 second | 07 (flashing) |
| 10 | Output power derating | Beep twice every 3 seconds | 10 (flashing) |
| 15 | PV energy is low. | Beep twice every 3 seconds | 15 (flashing) |
| E9 | Battery equalization | None | E9 (flashing) |
| bP | Battery is not connected | None | bP (flashing) |
7.4 Added Battery Warning Code in Lithium Battery Mode
| Warning Code | Warning Event | Warning Condition |
|---|---|---|
| 04 | The battery voltage is too low | Minimum voltage of a lithium battery cell <2.85V; Lithium battery total voltage <42V (48V lithium battery). |
| 05 | The battery voltage is too high | Lithium battery maximum single cell voltage >3.55V; Total voltage of lithium battery >54V (48V lithium battery). |
| 06 | The battery is low warning | Remaining battery capacity ≤10%. |
7.5 General Troubleshooting Table
| Problem | LCD/LED/Buzzer | Explanation / Possible cause | What to do |
|---|---|---|---|
| Unit shuts down automatically during startup process. | LCD/LEDs and buzzer will be active for 3 seconds and then complete off. | The battery voltage is too low (<1.91V/Cell) | 1. Re-charge battery. 2. Replace battery. |
| No response after power on. | No indication. | 1. The battery voltage is far too low. (<1.4V/Cell) 2. Internal fuse tripped. |
1. Contact repair center for replacing the fuse. 2. Re-charge battery. 3. Replace battery. |
| Input voltage is displayed as 0 on the LCD and green LED is flashing. | Input protector is tripped | Check if AC breaker is tripped and AC wiring is connected well. | |
| Mains exist but the unit works in battery mode. | Green LED is flashing. | Insufficient quality of AC power. (Shore or Generator) | 1. Check if AC wires are too thin and/or too long. 2. Check if generator (if applied) is working well or if input voltage range setting is correct. (UPS/Appliance) |
| Green LED is flashing. | Set "Solar First" as the priority of output source. | Change output source priority to Utility first. | |
| When the unit is turned on, internal relay is switched on and off repeatedly. | LCD display and LEDs are flashing | Battery is disconnected. | Check if battery wires are connected well. |
| Buzzer beeps continuously and red LED is on. | Fault code 07 | Overload error. The inverter is overload 110% and time is up. | Reduce the connected load by switching off some equipment. |
| Fault code 05 | Output short circuited. | Check if wiring is connected well and remove abnormal load. | |
| Fault code 02 | Temperature of internal converter component is over 120°C. Internal temperature of inverter component is over 100°C. | Check whether the air flow of the unit is blocked or whether the ambient temperature is too high. | |
| Fault code 03 | Battery is over-charged. | Return to repair center. | |
| The battery voltage is too high. | Check if spec and quantity of batteries are meet requirements. | ||
| Fault code 01 | Fan fault | Replace the fan. | |
| Fault code 06/58 | Output abnormal (Inverter voltage below than 190Vac or is higher than 260Vac) | 1. Reduce the connected load. 2. Return to repair center |
|
| Fault code 08/09/53/57 | Internal components failed. | Return to repair center. | |
| Fault code 51 | Over current or surge. | Restart the unit, if the error happens again, please return to repair center. | |
| Fault code 52 | Bus voltage is too low. | ||
| Fault code 55 | Output voltage is unbalanced. |
8. Specifications
Note: The following specifications are primarily for the 8.2KW/10.2KW models. The POW-HVM13.2M model will have similar characteristics, with a rated output power of 13.2kW and potentially higher ratings in some areas.
8.1 Line Mode Specifications
| INVERTER MODEL | 8.2KW | 10.2KW |
|---|---|---|
| Input Voltage Waveform | Sinusoidal (utility or generator) | |
| Nominal Input Voltage | 230Vac | |
| Low Loss Voltage | 170Vac±7V (UPS); 90Vac±7V (Appliances) | |
| Low Loss Return Voltage | 180Vac±7V (UPS); 100Vac±7V (Appliances) | |
| High Loss Voltage | 280Vac±7V | |
| High Loss Return Voltage | 270Vac±7V | |
| Max AC Input Voltage | 300Vac | |
| Nominal Input Frequency | 50Hz / 60Hz (Auto detection) | |
| Low Loss Frequency | 40±1Hz | |
| Low Loss Return Frequency | 42±1Hz | |
| High Loss Frequency | 65±1Hz | |
| High Loss Return Frequency | 63±1Hz | |
| Output Short Circuit Protection | Circuit Breaker | |
| Efficiency (Line Mode) | >95% (Rated R load, battery full charged) | |
| Transfer Time | 10ms typical (UPS); 20ms typical (Appliances) | |
8.2 Inverter Mode Specifications
| INVERTER MODEL | 8.2KW | 10.2KW |
|---|---|---|
| Rated Output Power | 8.2KW | 10.2KW |
| Output Voltage Waveform | Pure Sine Wave | |
| Output Voltage Regulation | 230Vac±5% | |
| Output Frequency | 50Hz | |
| Peak Efficiency | 93% | |
| Overload Protection | 3s@≥150% load; 5s@101%~150% load | |
| Surge Capacity | 2* rated power for 5 seconds | |
| Nominal DC Input Voltage | 48Vdc | |
| Cold Start Voltage | 46.0Vdc | |
| Low DC Warning Voltage @ load < 50% | 44.0Vdc | |
| Low DC Warning Voltage @ load ≥ 50% | 42.0Vdc | |
| Low DC Warning Return Voltage @ load < 50% | 45.0Vdc | |
| Low DC Warning Return Voltage @ load ≥ 50% | 44.0Vdc | |
| Low DC Cut-off Voltage @ load < 50% | 41.0Vdc | |
| Low DC Cut-off Voltage @ load ≥ 50% | 40.0Vdc | |
| High DC Recovery Voltage | 62Vdc | |
| High DC Cut-off Voltage | 63Vdc | |
| No Load Power Consumption | 70W | 75W |
8.3 Two Load Output Power
| INVERTER MODEL | 8.2KW | 10.2KW |
|---|---|---|
| Full Load | 8200W | 10200W |
| Maximum Main Load | 8200W | 10200W |
| Second Load Range | 1640W~5740W | 2040W~7140W |
| Main Load Cut Off Voltage | 52VDC | |
| Main Load Return Voltage | 54VDC | |
8.4 Charge Mode Specifications
| INVERTER MODEL | 8.2KW | 10.2KW |
|---|---|---|
| Utility Charging Mode | ||
| Charging Algorithm | 3-Step | |
| AC Charging Current (Max) | 140Amp | 140Amp |
| Bulk Charging Flooded Battery Voltage | 58.4Vdc | |
| Bulk Charging AGM / Gel Battery Voltage | 56.4Vdc | |
| Floating Charging Voltage | 54Vdc | |
| MPPT Solar Charging Mode | ||
| Max. PV Array Power | PV1 Channel:5400W, PV2 Channel:5400W | PV1 Channel:5400W, PV2 Channel:5400W |
| IMax.PV | PV1 Channel:18A, PV2 Channel:18A | PV1 Channel:18A, PV2 Channel:18A |
| Nominal PV Voltage | 360Vdc | |
| PV Array MPPT Voltage Range | 90Vdc~450Vdc | |
| Max. PV Array Open Circuit Voltage | 500Vdc | |
| Max Charging Current (AC charger plus solar charger) | 160Amp | |
8.5 Grid-Tie Operation Specifications
| INVERTER MODEL | 8.2KW | 10.2KW |
|---|---|---|
| Nominal Output Voltage | 220/230/240 VAC | |
| Feed-in Grid Voltage Range | 195~253VAC | |
| Feed-in Grid Frequency Range | 50±1Hz/60±1Hz | |
| Nominal Output Current | 35.6A | 44.3A |
| Power Factor Range | >0.99 | |
| Maximum Conversion Efficiency (DC/AC) | 98% | |
8.6 General Specifications
| INVERTER MODEL | 8.2KW | 10.2KW |
|---|---|---|
| Safety Certification | CE | |
| Operating Temperature Range | -10°C to 50°C | |
| Storage temperature | -15°C~60°C | |
| Humidity | 5% to 95% Relative Humidity (Non-condensing) | |
| Dimension (D*W*H), mm | 500*390*136mm | |
| Net Weight, kg | 14.5 | 14.7 |
8.7 Approximate Back-up Time Table
| Model | Load (W) | Backup Time @ 48Vdc 100Ah (min) | Backup Time @ 48Vdc 200Ah (min) |
|---|---|---|---|
| 8.2KW/10.2KW (Referenced for 13.2kW) | 500 | 613 | 1288 |
| 1000 | 268 | 613 | |
| 1500 | 158 | 402 | |
| 2000 | 111 | 271 | |
| 2500 | 90 | 215 | |
| 3200 | 76 | 182 | |
| 3500 | 65 | 141 | |
| 4000 | 50 | 112 | |
| 4500 | 44 | 100 | |
| 5000 | 40 | 90 | |
| 6200 | 36 | 80 | |
| 7200 | 32 | 70 | |
| 8200 | 28 | 60 | |
| 9200 | 24 | 50 | |
| 10200 | 20 | 40 |
Note:
- Backup time depends on the quality of the battery, age of battery, and type of battery. Specifications of batteries may vary depending on different manufacturers.
- The final interpretation right of this product belongs to the company.
9. User Tips
- Solar Panel Sizing: When selecting solar panels, ensure their total open circuit voltage (Voc) does not exceed the inverter's maximum PV array open circuit voltage (500Vdc) and is higher than the minimum battery voltage. Pay close attention to the PV array MPPT voltage range (90Vdc-450Vdc) for optimal performance.
- Battery Compatibility: This inverter is designed for 48V battery systems and is compatible with LiFePO4, Lead-Acid (Flooded, AGM, Gel) batteries. For LiFePO4 batteries, ensure proper BMS communication setup (Program 05 and 43) for real-time monitoring and protection.
- Load Management: Utilize the dual-load output feature to prioritize essential appliances. In situations where battery power is low, the inverter can automatically cut off high-power main loads while maintaining power for basic lighting and smaller loads, significantly extending backup time.
- Regular Maintenance: Clean the anti-dust kit monthly to ensure proper air circulation and prevent overheating, which contributes to the inverter's long-term reliability.
- Wiring Safety: Always ensure all wiring, especially for battery and AC connections, is performed by qualified personnel using appropriate cable sizes and correct polarity to prevent electric shock, fire, or damage to the unit.
10. Warranty & Support
PowMr offers a 2-year warranty for this product, ensuring peace of mind. For technical support, troubleshooting assistance, or warranty claims, please contact PowMr directly using the information below.
SHENZHEN HEHEJIN INDUSTRIAL CO.,LTD
- Tel/Fax: +86755-28219903
- Email: support@powmr.com
- Web: www.powmr.com
- Address: Henggang Street, Longgang District, Shenzhen, Guangdong, China