Smartgen MGC100

Smartgen MGC100 Genset Controller User Manual

Model: MGC100 | Brand: Smartgen

1. Introduction

The Smartgen MGC100 is a compact and reliable genset controller designed for small power gasoline generators. It provides automatic start/stop control, comprehensive protection functions, and a clear LED display for monitoring essential generator parameters. This manual provides detailed instructions for the installation, operation, and maintenance of the MGC100 controller.

2. Product Overview

2.1 Features

  • Automatic start/stop control for gasoline generators.
  • Integrated protection functions including low oil pressure, high temperature, over speed, over/under voltage, emergency stop, and fail to start.
  • LED display for real-time monitoring of generator parameters such as running time, battery voltage, AC voltage, and frequency.
  • Intuitive pushbutton interface for easy operation and parameter setting.
  • Compact panel built-in design for easy installation.

2.2 Controller Components

The MGC100 controller features a front panel with indicators and control buttons, and a rear panel with terminal connections.

Smartgen MGC100 Front Panel with Labeled Indicators
Figure 1: MGC100 Controller Front Panel with Indicators

Front Panel Indicators:

  • Running Time Indicator: Displays total operating hours.
  • Battery Volt. Indicator: Shows the battery voltage.
  • Alarm Indicator: Illuminates to indicate an active alarm condition.
  • Stop Indicator: Indicates the generator is stopped.
  • Gen Volt. Indicator: Displays the generator's AC voltage.
  • Gen Freq. Indicator: Shows the generator's frequency (Hz).
  • Running Indicator: Indicates the generator is currently running.
Smartgen MGC100 Rear Panel with Terminal Connections
Figure 2: MGC100 Controller Rear Panel

The rear panel provides access to the terminal block for all necessary electrical connections.

3. Specifications

3.1 Dimensions

MGC100 Case Dimensions Diagram
Figure 3: MGC100 Case Dimensions and Notes (Refer to image for detailed measurements)

The controller is designed for panel built-in installation and is fixed by clips. The approximate dimensions are 106mm (width) x 91mm (height) x 57mm (depth).

3.2 Electrical Parameters

  • Battery Voltage Input: DC9-18V. The negative terminal of the battery must be soundly connected to the engine shell. The wire diameter from the power supply to the battery must be over 1.0mm². If a floating charge is configured, first connect the charger's output wires directly to the battery's positive and negative terminals, then connect the battery's B+ (DC9-18V) positive and negative to the controller's corresponding input ports to prevent charging from disturbing the controller's normal operation.

3.3 Terminal Connection Description

MGC100 Rear Panel Connection Description Table
Figure 4: Rear Panel Connection Description (Refer to image for full table)
No.FunctionCable SizeNote
1B-1.0mm²Connected with negative of starter battery.
2B+1.0mm²Connected with positive of starter battery. If wire length is over 30m, better to double wires in parallel. Max. 10A fuse is recommended.
3Start Relay Output1.0mm²B+ power is supplied by terminal 2, rated 7A. Connected with start coil of starter.
4Fuel Relay Output1.0mm²B+ power is supplied by terminal 2, rated 7A.
5Controller Types1.0mm²When this terminal short circuit with (B-), it is used as a diesel genset controller. When this terminal is connected with nothing, it is used as a petrol genset controller.
6High Temperature1.0mm²Ground connected is active (B-).
7Low Oil Pressure1.0mm²Ground connected is active (B-).
8Emergency Stop1.0mm²Ground connected is active (B-).
9Remote Start1.0mm²Ground connected is active (B-).
10Aux. Transistor1.0mm²B-power is supplied by terminal 1, rated 1A.
11Magnetic Pickup 2 (B+)0.5mm²Connected with Rotate Speed Sensor, shielding line is recommended.
12Magnetic Pickup 10.5mm²Connected with N wire.
13N1.0mm²Connected with W phase (2A fuse is recommended).
14W phase voltage monitor1.0mm²Connected with W phase (2A fuse is recommended).
15V phase voltage monitor1.0mm²Connected with V phase (2A fuse is recommended).
16U phase voltage monitor1.0mm²Connected with U phase (2A fuse is recommended).

3.4 Auxiliary Output Ports

MGC100 Auxiliary Output Ports Table
Figure 5: Defined Contents of Auxiliary Output Ports (Refer to image for full table)
No.ContentDescription
0Not UsedWhen this is chosen, output port will not output.
1Preheat OutputCloses before start, opens before energize.
2Common AlarmWhen stop alarm is initiated, this alarm will self-lock until the alarm is reset.
3Idle OutputUsed for engines with idle function. Closes before starting and opens during warming up delay; closes during stopping idle process and opens when stop is completed.
4ETS OutputUsed for some gensets with stop electromagnet. Closes before stopping idle ends. Opens when "ETS Delay" ends.
5Air Flap ChokeUsed for gensets with choke valve electromagnet. Closes when genset starts and opens when safety running delay is over.
6Reserved
7Reserved
8Reserved
9Reserved

3.5 Crank Disconnect Conditions

MGC100 Crank Disconnect Conditions Table
Figure 6: Crank Disconnect Conditions Selection (Refer to image for full table)
No.Content
1Magnetic Sensor
2Generator
3Magnetic Sensor + Generator

4. Installation and Setup

4.1 Mounting

The MGC100 controller is designed for panel built-in installation. It is secured using clips after being inserted into the panel cutout.

4.2 Wiring Diagram

Refer to the following diagram for typical application wiring. Ensure all connections are secure and follow local electrical codes.

MGC100 Typical Application Wiring Diagram
Figure 7: Typical Application Wiring Diagram

Wiring Notes:

  • When controlling a petrol genset, terminal 4 connects with ignition control; when controlling a diesel genset, terminal 5 needs to short circuit with B-, and terminal 4 needs to connect with fuel output.
  • Speed Sensor Input: A magnetic speed sensor is typically installed on the engine body for testing flywheel teeth number. Two core shielding wire is used for the connection of the sensor and controller. The wire is supposed to be connected to terminal 11 of the controller with one end and the other end hanging in the air. The other two wires connect separately to terminal 12. The speed sensor is passive, and its maximum input voltage is AC12V (when in rated rotate speed). When installing the speed sensor, screw it to contact the flywheel first, average it with 1/3 circle, and then tighten the nut.
  • Withstand Voltage Test: If a high voltage test is required after the controller has been installed in the control panel, please disconnect all terminals of the controller to prevent high voltage from damaging it.

5. Operation

5.1 Pushbuttons

MGC100 Pushbuttons and Alarm Icons
Figure 8: Pushbuttons and Alarm Icon Indication (Refer to image for full tables)
IconDefinitionExplanation
Stop/-Stops the running genset. In stop status, press to stop generator immediately or to reset any shutdown alarm. Press for more than 2s to test the nixie tube and panel indicator. In setting menu, decreases parameter value (double-clickable). Press for more than 3s to exit the menu.
Page/ConfirmSwitches display contents of the nixie tube in normal status. Pressing for more than 3 seconds enters the parameter configuration menu. In setting menu, presses this button to modify and save the value.
Run/+Manual start in stop status. In setting menu, increases parameter value (double-clickable).

5.2 Alarm Icon Indication

IconDescriptionIconDescription
Emergency Stop AlarmOver Speed Alarm
High Temp AlarmLow Oil Pressure Alarm
Fail To Start AlarmOver/Under Volt Alarm

5.3 Manual Start/Stop

MGC100 Manual Start/Stop and Protection Functions
Figure 9: Manual Start/Stop and Protection Functions (Refer to image for full details)
  • To start genset: Press the Run/+ button. The controller will accelerate to high-speed running automatically. With high temperature, low oil pressure, over speed, and abnormal voltage during genset running, the controller will protect it by stopping quickly.
  • To stop genset: Press the Stop/- button.

Note:

  • The genset can be stopped manually in remote start status; at this time, remote input is inhibited and will become active when remote input is closed again.
  • After start conditions are satisfied, the accumulative running timer will be initiated; at the same time, the last blinking/decimal of the nixie tube indicates that the genset is working normally.

5.4 Protection Functions

  1. Low Oil Pressure: Detected after Safety On. An alarm stop occurs when the Low Oil Pressure input is active and lasts for 2 seconds.
  2. High Temperature: Detected when starting. An alarm stop occurs when High Temperature is active and lasts for 2 seconds.
  3. Over Speed: Detected when starting. An alarm stop occurs after the duration exceeds the Over Speed Stop Delay.
  4. Gen Over Volt: An alarm stop occurs when the controller detects genset voltage exceeding the overvoltage value and the delay exceeds the abnormal delay.
  5. Gen Under Volt: An alarm stop occurs when the controller detects genset voltage less than the undervoltage value and the delay is less than the abnormal delay.
  6. Emergency Stop: The ETS output activates immediately when Emergency Stop is active. Simultaneously, fuel, preheat, and start signals are cut off, and an Emergency Shutdown Alarm Signal is sent.
  7. Fail To Start: An alarm stop occurs when starting fails within the preset start times.
  8. Gen Under Frequency: When the genset is running normally, the controller detects if the generator frequency falls below the under-frequency value and the "under frequency" delay has expired. An under-frequency shutdown alarm will be sent.
  9. Gen Over Frequency: Detected when starting the genset. If the generator frequency exceeds the over-frequency value and the "over frequency" delay has expired, an over-frequency shutdown alarm will be sent.

5.5 Parameter Setting

MGC100 Parameter Setting and Reset Functions
Figure 10: Parameter Setting, Restore Factory Settings, and Eliminate Accumulated Time (Refer to image for full details)

To enter the parameter configuration menu, press the Page/Confirm button for more than 3 seconds. The LED will display "P00".

  1. Press Stop/- and Run/+ to decrease/increase the parameter number.
  2. After selecting the parameter number, press Page/Confirm to enter the parameter setting menu. Use Stop/- and Run/+ to increase/decrease the parameter value (double-clickable).
  3. Press Page/Confirm to modify and save the value.
  4. For multiple parameters, repeat steps 1-3.
  5. After parameter setting, press Stop/- for 3s to exit the parameter setting status.

5.6 Restore Factory Settings

In emergency stop input status, press Page/Confirm and Stop/- for 5 seconds simultaneously. The unit will restore to default settings, and "reset" will be displayed on the LED.

5.7 Eliminate Accumulated Time

Press Page/Confirm and Run/+ for 5 seconds simultaneously. The accumulated running time will be reset, and "hour" will be displayed on the LED.

Note for Parameter Setting:

  • The overvoltage threshold must be greater than the undervoltage threshold.
  • When starting successfully, the generator frequency needs to be set lower as soon as possible to ensure the starter separates sooner.
  • The number of setting contents refers to "Parameter Content and Range (Table 7)" (not provided in source).
  • Exiting the parameter setting status is only possible from the parameter number menu. If no button is pressed in the parameter number menu, it will exit automatically in 30 seconds.

6. Maintenance

To ensure the longevity and reliable operation of your Smartgen MGC100 controller, perform regular checks:

  • Keep the controller clean and free from dust and moisture.
  • Periodically inspect all wiring connections for tightness and corrosion.
  • Ensure the generator's battery is in good condition and properly charged.
  • Verify that all sensors (oil pressure, temperature, speed) are functioning correctly.

For any complex issues or repairs, it is recommended to consult with a qualified technician.

7. Troubleshooting

This section provides solutions to common issues you might encounter with the MGC100 controller.

MGC100 Fault Finding Table
Figure 11: Fault Finding Table (Refer to image for full table)
SymptomsPossible Solutions
Controller no response with powerCheck starting batteries; Check controller connection wirings; Check DC fuse.
Crank not disconnectCheck fuel oil circuit and its connections; Check starting batteries; Check speed sensor and its connections; Refer to engine manual.
Shutdown alarm in runningCheck related switch and its connections according to the information on LED.
Starter no responseCheck starter connections; Check starting batteries.

8. User Tips

  • Always ensure proper grounding for all components to prevent electrical interference and ensure safety.
  • When performing any wiring, double-check all connections against the provided diagram to avoid damage to the controller or generator.
  • For optimal performance, keep the controller's display and buttons clean and free from debris.
  • Familiarize yourself with the alarm icons and their meanings to quickly diagnose issues.

9. Warranty and Support

For any technical assistance, warranty claims, or further inquiries, please contact the seller or manufacturer's support channels. Keep your purchase records handy for faster service.

Related Documents - MGC100

Preview SmartGen MGC100 Genset Controller User Manual
User manual for the SmartGen MGC100 Genset Controller, detailing its features, specifications, operation, connections, parameters, and troubleshooting for genset management.
Preview SmartGen MGC100 Genset Controller User Manual
Comprehensive user manual for the SmartGen MGC100 Genset Controller, detailing its features, specifications, operation, connections, parameters, and troubleshooting for diesel and petrol generators.
Preview SmartGen HGM501 Genset Controller User Manual
This user manual provides detailed information on the SmartGen HGM501 Genset Controller, covering its overview, performance, technical data, operation, auto-protection features, terminal connections, configurable parameters, commissioning, typical wiring diagram, installation, and troubleshooting.
Preview SmartGen HGM93XXMPU(CAN) Series Genset Controller User Manual
User manual for SmartGen HGM93XXMPU(CAN) series genset controllers (HGM9310MPU, HGM9320MPU, HGM9310CAN, HGM9320CAN). Covers automation, monitoring, protection, specifications, and operation for generator control systems.
Preview SmartGen HGM9510N/HGM9530N Paralleled Genset Controller User Manual
Comprehensive user manual for SmartGen HGM9510N and HGM9530N paralleled genset controllers. Learn about features, operation, specifications, wiring, protection, and commissioning for efficient generator synchronization and control.
Preview Smartgen HGM7211/HGM7221 Genset Controller User Manual
This user manual provides comprehensive details on the Smartgen HGM7211 and HGM7221 series genset controllers. These advanced units are designed for automated operation and monitoring of single-unit gensets, enabling automatic start/stop, data measurement, alarm protection, and remote communication.