1. Safety Rules and Precautions
Thank you for purchasing our transformer turns ratio tester. Before you use the instrument for the first time, in order to avoid possible electric shock or personal injury, please be sure to read in detail and strictly observe the safety rules and precautions listed in this manual.
In any case, special attention should be paid to safety when using this instrument.
- The instrument is designed, manufactured and tested in accordance with IEC61010 safety specifications.
- Notice the labeled text and symbols on the body of this instrument.
- Before use, it should be confirmed that the instrument and accessories are intact, and the insulation of the instrument and test line is not broken exposed, No broken wires to use.
- During measurement, it is strictly prohibited to touch the exposed conductors and the circuit being measured.
- Verify that the wire connection plugs are tightly inserted into the instrument connector.
- Do not measure in flammable locations, sparks may cause an explosion.
- Discontinue use of the instrument if metal is exposed due to breakage of the housing or test cable during use.
- Do not place and store the instrument for a long time in a hot and humid place or under direct sunlight.
- Pay attention to the measurement range specified for this instrument and the environment in which it is used.
- The use, disassembly, calibration, and maintenance of this instrument must be carried out by authorized and qualified personnel.
- If continued use poses a danger due to this instrument, stop using it and seal it immediately deposit, to be handled by an authorized and qualified body.
- The "!" safety warning symbols in the instrument and in the manual must be strictly followed by the user in this manual. Allow for safe operation.
2. Introduction
The ES6030 transformer turns ratio tester adopts microprocessor technology for measurement calculation and automatic control, which can quickly and easily measure the actual transformer ratio and group. It is mainly used in the power industry to measure the transformer ratio and group, and at the same time, it is used by transformer manufacturers and distributors to measure the transformer parameters.
The ES6030 transformer ratio tester consists of the host, monitoring software, test line, communication line, and so on. The host has a charging function without the need to find power on site, a full-color large-screen LCD display, and the language can be chosen between Chinese or English. It features convenient touch-screen operation, port anti-overload function, and large-capacity storage of 500 groups of data. Upper computer software provides historical data reading, access, save, and other functions.
Please note: Since 2026, the ES6030 color has changed to green, but the specifications and functions remain unchanged.

Image: The ES6030 Transformer Turns Ratio Tester in its updated green color.
3. Specifications
3.1. General Specifications
| Feature | Description |
|---|---|
| Function | Mainly used for ratio and group testing of three-phase transformers, single-phase transformers, PT and CT. Supports blind testing of three-phase transformers and Z-type transformers. |
| Type of test product | Single-phase transformer, three-phase transformers, Z-type transformers, PT, CT |
| Variable ratio range | 0.9~10000 |
| Overload protection | Yes |
| Power source | DC9.6V 3800mAh high capacity lithium battery |
| Charging function | Yes |
| Display mode | 5-inch touchscreen (854dots × 480dots) full-color LCD display |
| Interactive mode | Touch screen & button |
| LCD size | Length × width: 108 mm × 65mm |
| Instrument size | Length × width × height: 229mm × 166mm × 74mm |
| Mobile APP | Yes, Bluetooth connection |
| Computer connect | Yes, the USB cable connection |
| Data storage | 500 groups |
| Data access | Data access function |
| Battery voltage | Real-time display of battery power indicates that the battery should be charged in time when the voltage is low |
| Auto shut off | Automatic shutdown can be set for 1 to 30 minutes |
| Power dissipation (Standby) | Approx. 2W (100% brightness) |
| Power dissipation (Measured) | 12W Max |
| Instrument Weight | 1.5kg (including battery) |
| Test cables Weight | 1.7kg |
| Working temperature and humidity | -10℃~40℃; below 70%rh |
| Store temperature and humidity | -20℃~60℃; below 70%rh |
| Insulation resistance | Above 10 MΩ (500V between circuit and housing) |
| Withstand voltage | AC 3700V/rms (between circuit and enclosure) |
| Electromagnetic property | IEC61010-4-3, radio frequency≤1V/m |
| Suitable for safety Regulations | IEC61010-1, CAT III 600V, pollution class2 |
3.2. Measurement Range and Accuracy
| Measure the radio range | Resolution radio | Accuracy |
|---|---|---|
| 0.9 ≤ TTR < 10 | 0.0001 | ±0.2% ± 2dgt |
| 10 ≤ TTR < 100 | 0.001 | ±0.2% ± 2dgt |
| 100 ≤ TTR < 1000 | 0.01 | ±0.2% ± 2dgt |
| 1000 ≤ TTR < 2000 | 0.1 | ±0.2% ± 2dgt |
| 2000 ≤ TTR < 10000 | 0.1 | ±0.5% ± 2dgt |
| 10000 ≥ TTR | 1 | -- |
4. Instrument Structure
The ES6030 features a user-friendly interface with clearly labeled ports and buttons.

Image: Front view of the ES6030 tester, showing the display and control buttons.

Image: ES6030 tester with dimensions indicated (229mm x 166mm x 74mm).
4.1. Component Identification
| No. | Component |
|---|---|
| 1 | HV side A phase terminal |
| 2 | HV side B phase terminal |
| 3 | HV side C phase terminal |
| 4 | LV side A phase terminal |
| 5 | LV side B phase terminal |
| 6 | LV side C phase terminal |
| 7 | USB PORT |
| 8 | Power button |
| 9 | Confirmation key |
| 10 | Return key |
| 11 | Test key |
| 12 | Color screen |
| 13 | Multi-function key |
| 14 | Right button |
| 15 | Left button |
| 16 | Down button |
| 17 | Upper button |
| 18 | Charging port |
4.2. Iconography
The device uses both silicone keypad buttons and touch screen buttons. Here's a guide to their functions:
4.2.1. Silicone Keypad
| Icon | Name | Note |
|---|---|---|
| Upper key | Select upwards | |
| Down key | Select downwards | |
| Left key | Select to the left | |
| Right key | Select to the right | |
| Multiplex key | Equivalent to touching the bottom left button of the screen, including deleting, saving, sound, etc. | |
| Power button | Switching power supply | |
| Confirm key | Conform or checked. | |
| Return key | Return to the previous screen | |
| Test key | Start testing |
4.2.2. Touch Screen Buttons
| Icon | Name | Note |
|---|---|---|
| OK | Confirm key | Conform or checked. |
| Return key | Return to the previous screen | |
| Upper key | Select upwards | |
| Down key | Select downwards | |
| Left key | Select to the left | |
| Right key | Select to the right | |
| Delete key | Delete all test records. | |
| Time | Time key | Enter the set time interface |
| Sound key | Set the buzzer switch. | |
| Save | Save key | Save the test record |
| BLE | Bluetooth key | Set up Bluetooth on or off. |
| EN/CN | Language switching | Switch between Chinese and English |
| TEST | Test key | Start testing |
4.2.3. Other Icons
| Icon | Note |
|---|---|
| Used for adjusting the brightness of the backlight. | |
| Battery level display | |
| Charging status display | |
| Bluetooth is displayed in the upper right corner of the large screen when it is switched on. | |
| View test record |
5. Setup
5.1. Switching On and Off
Pressing the red "power button" in the off state will turn the power on. Pressing the red "power button" again in the on state will turn the power off.
5.2. Interface Introduction
The main interface provides access to different test modes and settings.

Image: Main interface of the ES6030, showing options for Three phase, Single phase, Z-type, Set, View, and OPI.
5.3. Time Setting
To set the time, navigate to the time setting screen. You can adjust the year, month, day, hour, and second by sliding the values up and down. Confirm with the OK button to update the system time.

Image: Time setting screen, allowing adjustment of date and time.
5.4. General Settings
From the main interface, click the "Set" icon to enter the system settings interface.

Image: Settings interface, showing options for Backlight, Shutdown, Time, EN/CN, and BLE.
- Backlight Setting: Drag the icon to the left or right to adjust the brightness.
- Shutdown Time Setting: Press the left and right keys to select 1~30 minutes auto shutdown. If there is no operation, the tester will turn off automatically after this time.
- Sound Settings: Click the sound icon to switch the sound on and off.
- Language Switching: Click "EN/CN" to switch between Simplified Chinese and English.
- Bluetooth Setting: Click "BLE" to switch Bluetooth on/off. When Bluetooth is on, the Bluetooth icon is displayed in the upper right corner of the screen.
5.5. Wiring Methods
5.5.1. Single-Phase Transformer Wiring

Image: Diagram showing how to connect the ES6030 to a single-phase transformer.
Connect the two ports on the high-voltage side of the transformer to the tester's UA and UB terminals, and the two ports on the low-voltage side of the transformer to the tester's Ua and Ub terminals.
5.5.2. Three-Phase Transformer Wiring

Image: Diagram showing how to connect the ES6030 to a three-phase transformer.
Connect the three ports (A, B, C) on the high-voltage side of the transformer and the three terminals (UA, UB, UC) of the tester according to the same name. Similarly, connect the three ports (a, b, c) on the low-voltage side of the transformer and the three terminals (Ua, Ub, Uc) of the tester according to the same name.
6. Operating Instructions
6.1. Single-Phase Transformer Test Operation
In the main interface, click on the "Single phase test" icon to enter the test setup interface.

Image: Single-phase test setup screen, showing Sample, High, Low, TS, and RT parameters.
- Specimen No.: Adjust the value to distinguish the tested transformer. This parameter does not affect the test results.
- Rated HV: The rated voltage of the high voltage side, used to calculate the ratio error and deduce the tap position.
- Rated Low Voltage: The rated voltage of the low voltage side, used to calculate the ratio error and deduce the tap position.
- Tap Spacing: If there is no tap, any value can be set for this position.
- Rated Tap: If there is no tap, please set 0 or 1.
After setting the parameters, click "TEST" or press the silicone button "TEST" to initiate the test. The test result will be displayed on the screen.

Image: Single-phase test result screen, showing Ratio, Angle, Error, and Tap.
6.2. Three-Phase Transformer Test Operation
For conventional three-phase transformers with a recognizable nameplate, click the "Three phase test" icon and then "Normal test" to enter the setup interface. If the nameplate is not recognizable, click "Three-phase test" and then "Three phase blind test" to enter the setup interface.
For Z-Type Transformers, if the nameplate is recognizable, click the "Z-Type Test" icon to enter the test setup interface.

Image: Three-phase test setup screen, showing Sample, High, Low, Tap, and Group parameters.
- Specimen No.: As with single-phase tests, this helps distinguish transformers and does not affect results.
- Rated HV/Low Voltage: Used for ratio error calculation and tap position deduction.
- Tap: The parameter on the left is tap spacing; the parameter on the right is the rated tap. Set to 0 or 1 if no tap.
- LINK GROUP: Contains three parameters for high-voltage side coupling methods, including D, Y, YN, ZN. Unknown can be selected during three-phase blind testing.
- Low-voltage side linkage: Includes d, y, yn, and optionally unknown for three-phase blind measurements.
- Group: Transformer group, including 0, 11, and "Auto". Only "Auto" is available in three-phase blind test.
After setting parameters, click "TEST" or press the silicone button "TEST". The test result will be displayed.

Image: Three-phase test result screen, showing Ratio and Error for AB/ab, BC/bc, CA/ca, Group, and Tap.
6.3. Data Management
6.3.1. Data Storage
In the test result interface, click "Save" to save the test results. The tester can save 500 sets of test results. If storage is full, clear old records from the access screen before saving new data.
6.3.2. Data Access/Deletion
In the main interface, click the "View" icon to enter the access interface for data access and deletion. If no data is saved, the interface will prompt "No saved data!".
Press the left and right buttons to turn pages, and the up and down buttons to select the record you need to view. You can also directly click on a record on the large screen to view it.

Image: Data access screen, showing a list of saved test records with options to view or delete.
6.4. APP and PC Upper Computer Operation
This instrument supports connecting to Android APP and PC upper computer.
6.4.1. PC Upper Connection Instructions:
- Install the USB driver and host computer software from the provided CD ROM.
- After the instrument is switched on, use the instrument accessory USB cable. Connect one end to the USB port of the instrument and the other end to the USB port of the computer.
- Run the software on the computer. It will automatically search for the port and connect.
- After successful connection, you can check historical data, generate Excel reports, and perform other operations through the software.
6.4.2. Android APP Connection Instructions:
- Before using, ensure your mobile phone or tablet system version is Android 5.0 or above.
- Ensure the TTR Tester APP is installed on your intelligent device.
- In the "Settings" page, click the Bluetooth icon to turn on Bluetooth.
- Turn on the APP, search for the Bluetooth device with the name "TTR Tester", and connect to it.
- After successful connection, you can realize wireless control measurement and data browsing.
6.5. Product Demonstration Video
Video: A demonstration of the ES6030 Transformer Turns Ratio Tester's interface and basic operation, including setting parameters, running a test, saving data, and navigating settings.
7. Maintenance
7.1. Battery Level Check
After power on, if the upper right corner of the screen shows a low battery voltage symbol, it means the battery power is insufficient. Please charge it in time to ensure measurement accuracy.
The power consumption during the test is higher than standby. If the low battery voltage symbol appears during a test, the battery power is about to be insufficient. Please charge it promptly to ensure accuracy.
If the battery power is not enough to support the test, the device will automatically shut down. Please charge and then re-test.
7.2. Overload Protection
Every time before switching on and testing the resistance, the instrument will perform an overload check. If an overload is detected, it will carry out overload protection and prompt a warning. In such a case, please switch off the device and ensure that the test body is not charged before switching on and testing again.
After overload protection, disconnect the cable and restart the instrument to turn on normally.
8. Troubleshooting
If you encounter any issues not covered in this manual, please refer to the official user manual PDF or contact customer support.
User Manual (PDF) Reference: A detailed user manual in PDF format is available for further reference. You can access it at: ES6030 User Manual (PDF)
9. User Tips
- When performing three-phase transformer tests, the ES6030 supports various connection types including star (Y) and delta (D) configurations, as well as YN and ZN. Ensure you select the correct group setting for accurate measurements.
- For blind tests where the transformer nameplate is unknown, utilize the "Three phase blind test" option to determine the ratio and group.
- Regularly check the battery level, especially before critical measurements, to avoid unexpected shutdowns and ensure consistent performance.
10. Packing List
The following items are included with your ES6030 Transformer Turns Ratio Tester:

Image: Contents of the ES6030 packing list, including the tester, cables, manual, CD, charger, and carrying bag.
| Item | Quantity | Details |
|---|---|---|
| Instrument | 1 pcs | ES6030 Transformer Turns Ratio Tester |
| Test line | 2 groups | Red and black, each 10 meters/group |
| CD | 1 pcs | Contains USB driver and host computer software |
| Data cable | 1 pcs | Type-C, 1 meter |
| Charger | 1 pcs | 14.8V/1.5A |
| Introduction manual, warranty, certification | 1 set | |
| Parcel | 1 pcs | Carrying bag |