1. Introduction
The GEYA W2R series Mini ATS Dual Power Automatic Transfer Switch is a PC Level, newly developed micro household power transfer switch designed to ensure continuous, reliable, and safe power supply. It automatically switches to a backup power source when the normal city power supply becomes abnormal, providing an uninterrupted power transition.
Key features include millisecond switching, quick transfer, PC level performance, and a wide range of applications for household distribution boxes.
2. Important Safety Warnings
- Read this manual carefully before installing or operating the product. Contact the manufacturer for any questions.
- Unauthorized disassembly of the product is strictly prohibited to prevent instrument failure or malfunctions.
- Installation and wiring must be performed by qualified personnel familiar with this manual and local electrical codes.
- Before installation, inspect the ATS for any damage or missing parts.
- Ensure the text on the ATS panel is visible from the front. If the correct mounting orientation cannot be achieved due to wiring or space constraints, contact the manufacturer.
- Install suitable circuit breakers in accordance with IEC 60947-6-1 and the distribution system design to ensure personnel and equipment safety.
- Do not operate the device at control voltages below 190 V (for 220 V models) or 95 V (for 110 V models). Operation below these limits may cause overheating and permanent damage.
- The rated voltage of the common and backup power supply must be within the range of 85%-110% of the rated voltage. The current cannot be less than 5A; otherwise, the coil may overheat or spontaneously burn. If your city voltage is unstable, consider adding voltage protectors to your system.
- The Control Circuit TSE (Transfer Switching Equipment) is instantly energized during transfer. If internal switches malfunction after transfer, the control coil may be damaged. Ensure a stable power supply to avoid coil damage.
- This product has undergone insulation testing before leaving the factory. Incorrect dielectric testing will damage the control system, and it is strictly prohibited to conduct dielectric testing with the ATS.
3. Specifications
| Parameter | Value |
|---|---|
| Model Number | W2R-100 |
| Rated Current | 63A / 100A |
| Poles | 2P, 3P, 4P |
| Coil Voltage | 110V or 220V AC |
| Rated Frequency | 50/60Hz |
| Rated Working Voltage Us | AC220V, 50HZ |
| Rated Impulse Withstand Voltage | 8KV |
| Working Condition | 85% Us ~ 110% Us |
| Switching Time | <50ms |
| Action Time | <50ms |
| Electrical Life | 2000 times |
| Mechanical Life | 5000 times |
| Material | Plastic |
| Mounting | Din Rail Type |
| Certification | CCC, CE |
| Is Smart Device | No |
Product Dimensions (Approximate)
- 2P Model: 107.5mm (Width) x 103mm (Height) x 78.5mm (Depth)
- 3P Model: 125.5mm (Width) x 103mm (Height) x 78.5mm (Depth)
- 4P Model: 142.5mm (Width) x 103mm (Height) x 78.5mm (Depth)
4. Installation
Ensure all safety warnings are read and understood before proceeding with installation. Installation should only be performed by qualified personnel.
4.1. Working Conditions
- Ambient Temperature Range: -5°C to +40°C (24-hour average must not exceed +35°C)
- Altitude: Should not exceed 2000 meters.
- Operating Humidity: Up to 50% at +40°C; up to 90% at +25°C (condensation prevention required).
- Contamination Level: Level 3.
- Mounting Orientation: The ATS can be installed vertically in cabinets.
4.2. DIN Rail Installation
- Insert the upper end of the ATS base into the DIN rail.
- Push the lower end of the ATS base into the DIN rail until the snap fastener locks securely.
4.3. DIN Rail Disassembly
- Insert a screwdriver into the round hole of the DIN rail snap fastener at the bottom of the ATS.
- Use a screwdriver to pry the DIN rail snap fastener downward.
- Tilt the ATS upwards and remove it from the DIN rail.
4.4. Screw Mounting
- Pull out the upper and lower snap fasteners located at the bottom of the ATS.
- Secure the ATS to the panel with screws.
5. Wiring Instructions
All wiring must be performed by qualified personnel with power disconnected.
- Connect the phase (AR) and neutral (AN) to the main power input terminals (Source A). This connection is mandatory.
- Connect the phase (BR) and neutral (BN) to the backup power input terminals (Source B). This connection is mandatory.
- The power indication signal uses a dry contact output. The generator signal is taken from the common (C) and normally closed (NC) terminals.
- Use copper wires with a cross-sectional area of at least 2.0 mm², and keep control circuit wiring as short as possible.
- Connect the load to the lower terminals on the backup power side using stepped wiring.
- Remove the isolation board before wiring the load, then reinstall the board, ensuring proper alignment. It is recommended to connect the load before wiring the backup power.
6. Operating Modes
The GEYA W2R ATS offers both Manual and Automatic operating modes.
- Automatic Mode: Electric (automatic) operation ensures reliable switching between power sources. This is the recommended mode for normal operation.
- Manual Mode: Manual operation allows for direct control using the manual handle.
Important Tip: Always set the switch to "Manual" mode before turning the knob for manual operation. Switch to manual mode only after power is disconnected and maintenance is completed. Return to automatic mode promptly after any manual operation.
7. Maintenance, Inspection, and Storage
Regular maintenance ensures the longevity and reliable operation of your ATS. All maintenance and inspection must be performed by qualified personnel after disconnecting all power supplies.
- Inspection Frequency: The first inspection should be completed within 6 months of commissioning, and at least once per year thereafter. In harsh environments, increase inspection frequency as needed.
- Key Tasks:
- Remove dust and debris from the unit.
- Check contact parts for damage, discoloration, or burn marks.
- Measure contact resistance if necessary.
- Damp Conditions: If the ATS is damp or idle for an extended period, dry it thoroughly and measure insulation resistance with a 500V megohmmeter (minimum 10 MΩ).
- Storage: Store the ATS in a clean, dry environment, protected from mechanical impact.
8. Troubleshooting
This section addresses common issues you might encounter with your GEYA W2R ATS.
8.1. Automatic Transfer Failure
Symptom: In automatic mode, the switch triggers (a noise is heard) but the switch lever remains in place and does not transfer to the backup power source.
Possible Causes & Solutions:
- Unstable Control Voltage: Ensure the control voltage is stable and within the specified range of 85%-110% of the rated voltage. Unstable voltage can prevent proper coil operation.
- Insufficient Current: Verify that the current is not less than 5A. A low current can cause the coil to overheat or fail to engage the transfer mechanism.
- Incorrect Wiring: Double-check all wiring connections according to the wiring diagrams in Section 5. Ensure all terminals are securely fastened.
- Internal Malfunction: If the above steps do not resolve the issue, there might be an internal malfunction. Contact customer support for further assistance.
9. User Tips
- For areas with unstable city voltage, it is highly recommended to install voltage protectors in your electrical system to safeguard the ATS and connected appliances.
- Be aware that some models of the W2R ATS are also suitable for solar panel applications. These versions might have a slightly longer switching delay, which could potentially cause sensitive electronics like computers to shut down during a transfer. Plan accordingly for such devices.
- Always ensure the switch is in "Manual" mode before attempting to turn the manual knob to prevent damage to the internal mechanism.
10. Warranty and Support
The GEYA W2R Dual Power Automatic Transfer Switch comes with a 2-year warranty from the date of purchase.
For technical support, warranty claims, or any questions regarding the product, please contact GEYA customer service or your authorized dealer. Refer to the official GEYA website for contact information.
A detailed user manual in PDF format is available for download. You can access it via the official product page or by contacting customer support. The PDF manual can be found at: GEYA W2R User Manual (PDF)