GEYA GYL9 RCCB Recloser

Contents

GEYA GRD9L-R Type A RCD Auto Recloser Differential Circuit Breaker User Manual

Model: GYL9 RCCB Recloser

1. Introduction

The GEYA GRD9L-R Auto Recloser is a Type A Residual Current Device (RCD) designed to automatically reclose after an electrical fault, such as an earth leakage current. This device eliminates the need for manual resetting, reducing maintenance costs and improving efficiency in power grid terminal lines. It is suitable for various applications including meter boxes, new energy circuit management, PV solar control boxes, smart electricity systems, smart homes, and new energy vehicle charging piles.

This manual provides essential information for the safe and effective installation, operation, and maintenance of your GEYA GRD9L-R Auto Recloser.

GEYA GRD9L-R Type A RCD Auto Recloser

Figure 1: GEYA GRD9L-R Type A RCD Auto Recloser

2. Safety Warnings

  • Do not disassemble or modify the unit without authorization. Unauthorized modifications can lead to malfunction, electric shock, or fire.
  • Avoid use in high-temperature or humid environments. Such conditions can degrade performance and safety.
  • Inspect the device for integrity before use. Ensure there are no visible damages or loose connections.
  • This accessory must not be used for non-security inspection purposes.
  • Avoid strong vibrations or impacts during installation and operation.

3. Product Features

  • Can be matched with RCCB (Residual Current Circuit Breaker) for remote switching and splitting.
  • Features a manual/automatic selector switch for flexible operation.
  • Equipped with mechanical and electronic double locking functions for enhanced safety.
  • Work status is clearly indicated by an LED.
  • Automatically switches on the distribution board when an electrical trip occurs.
  • Adjustable auto reclosing interval times: 10 seconds, 60 seconds, 300 seconds.
  • Built-in 3 reclosing attempts; continuous closing failure within 15 minutes triggers an alarm via auxiliary contact.
  • Manual Close Reclosing Time: AUTO → MANU → AUTO.

4. Specifications

ParameterValue
Control ModeAuto Reclosing
Supply TerminalsDC12V, DC24-48V
Voltage RangeAC 220V
Power InputDC max. 1W (standby), max. 20W (action)
Power Voltage RangeAC 220V +/- 10% (50/60Hz)
Supply Voltage Tolerance-10% to +10%
Supply IndicationRed LED
Action Time<1s
Auto Reclosing Times3
Auto Reclosing Interval Time10s, 60s, 300s
Reset Closing TimesNo trip or manual reset within 15 minutes after successful closing
Mechanical Life10000
Electrical Life (AC1)6000
Operating Temperature-35°C to +75°C (-22°F to 158°F)
Storage Temperature-35°C to +75°C (-22°F to 158°F)
Mounting/DIN RailDin rail EN/IEC 60715
Protection DegreeIP20
Operating PositionAny
Overvoltage CategoryIII
Pollution Degree2
Max. Cable Size (mm²)Solid wire max. 1x2.5 or 2x1.5; with sleeve wire max. 1x2.5 (AWG 12)
Rated Voltage220V
EU LVD VoltageLow voltage: Below 50Vac or 75Vdc
CertificationCE
Is Smart DeviceNo
Wireless FunctionalityNo
Battery IncludedNo
High-concerned chemicalNone
Technical parameters table and panel diagram

Figure 2: Technical Parameters and Panel Diagram

5. Installation and Use

5.1 Installation Steps

  1. Install the accessory at the designated location, typically on a DIN rail (EN/IEC 60715).
  2. Ensure secure electrical connections before powering on the device. Refer to the wiring diagram for correct connections.
  3. Perform commissioning according to the operation manual.

5.2 Wiring Diagram

Wiring Diagram for GRD9L-R

Figure 3: Wiring Diagram for GRD9L-R

5.3 Operating Modes

  • AUTO Mode: The auto reclosing function is enabled. The device will automatically attempt to reclose after a trip.
  • MANU Mode: The auto reclosing function is disabled. The MCB/RCCB can only be opened and closed manually.

5.4 Status Indicators

  • When powered on, the green indicator light will flash for 2 seconds to stabilize.
  • If the MCB/RCCB is ON, the green indicator light will stay on.
  • If the MCB/RCCB fails to trip, the red indicator light will flash.
  • After the delay, it will switch on automatically and the green light will be on.
Functions diagram and application examples

Figure 4: Functions Diagram and Application Examples

5.5 Accessories Installation

Accessories installation diagram

Figure 5: Accessories Installation

6. Maintenance

  • Keep the accessory clean and dry to ensure optimal performance and longevity.
  • Regularly inspect the device for any signs of wear, damage, or loose connections.
  • Avoid exposing the device to strong vibrations or impacts, which could compromise its internal components.

7. Troubleshooting (Common Faults)

Fault DescriptionResolution
Unable to close or open
  1. Confirm whether the power supply voltage is normal.
  2. Confirm whether the working mode is set to AUTO mode.
  3. Please confirm the buckle of the electric operation mechanism and MCB/RCCB.
Trip immediately after closing
  1. Check the circuit to confirm whether there is overload / short circuit / leakage fault at the lower end of MCB / RCCB.
  2. Whether the circuit breaker is damaged or not, and whether it is slipped.
Accessory fails to connectCheck whether the interface is loose.
Abnormal functionalityRestart the device or contact after-sales service.
Alarm triggers during useImmediately cease operation and inspect the device.
Common faults and dimensions diagram

Figure 6: Common Faults and Dimensions

8. Dimensions (mm)

Dimensions of GRD9L-R

Figure 7: Product Dimensions

9. User Tips

  • The device is noted for being sturdy and well-built, with a noticeable weight indicating quality construction.
  • Users have reported that the device works effectively without power interruptions.
  • The design allows for easy connection to a DIN rail, simplifying installation.
  • Consider the 6000A cut-off and C curve characteristics for your specific electrical system requirements.

10. Video Overview

Video 1: GEYA Company Introduction and Product Overview

11. Warranty and Support

GEYA products are certified to required industry standards, including CE, CB, SAA, SEMKO, TUV, and Rosh. For detailed warranty information, technical support, or service inquiries, please refer to the official user manual PDF available for download or contact GEYA customer service.

A user manual in PDF format is available for more detailed guides and documents. You can typically find this on the product's official support page or by contacting the seller directly.

© 2024 GEYA. All rights reserved.

Ask a question about this manual

Ask about setup, troubleshooting, compatibility, parts, safety, or missing instructions. Manuals+ will review the question and use this page’s manual context to help answer it.

After a successful submission, we securely hash the supplied account or form email before sending it to Microsoft Advertising for conversion attribution. Privacy details.