1. Introduction
This Sumry Hybrid Solar Inverter is a multi-function inverter/charger designed to provide uninterruptible power support. It combines the functions of an inverter, solar charger, and battery charger. The unit features a comprehensive LCD display that allows users to configure various settings, including battery charging current, AC/solar charger priority, and acceptable input voltage ranges, to suit different applications.
1.1 Key Features
- Pure sine wave output for clean and stable power.
- Configurable input voltage range for home appliances and personal computers via LCD settings.
- Configurable battery charging current based on application needs.
- Configurable AC/Solar Charger priority.
- Compatible with both mains voltage and generator power.
- Automatic restart upon AC recovery.
- Protection against overload, over-temperature, and short circuits.
- Smart battery charger design for optimized battery performance.
- Cold start function.
- Built-in 120A MPPT solar charge controller.
- High PV input voltage range (60-500VDC).
- Built-in anti-dust kit for harsh environments.
- Dual output capability.
- Dual communication ports for Battery (RS485) and Wi-Fi (RS232) communication.
- Automatic activation for Lithium batteries.
1.2 Basic System Architecture
The inverter/charger can be integrated into various system architectures. A typical setup includes solar panels, a generator or utility grid, external battery packs, and home appliances. The inverter manages power flow between these components to provide continuous power.

Diagram illustrating the basic system architecture of the hybrid solar inverter, showing connections between solar panels, utility/generator, battery, inverter, and home appliances.
1.3 Product Overview
The inverter features an LCD display and function buttons on the front panel for operation and monitoring. The rear panel provides various connection terminals for AC input, main output, second output, battery input, PV input, and communication ports.

Image showing the rear panel of the inverter with labeled ports for AC input, main output, second output, battery, communication, and PV input.
2. Safety Instructions
WARNING: This chapter contains important safety and operating instructions. Read and keep this manual for future reference.
- Before using the unit, read all instructions and cautionary markings on the unit, the batteries, and all appropriate sections of this manual.
- CAUTION: To reduce risk of injury, charge only deep-cycle lead acid type rechargeable batteries. Other types of batteries may burst, causing personal injury and damage.
- Do not disassemble the unit. Take it to a qualified service center when service or repair is required. Incorrect re-assembly may result in a risk of electric shock or fire.
- To reduce risk of electric shock, disconnect all wirings before attempting any maintenance or cleaning. Turning off the unit will not reduce this risk.
- CAUTION: Only qualified personnel can install this device with battery.
- NEVER charge a frozen battery.
- For optimum operation, follow required specifications for cable sizing.
- Be very cautious when working with metal tools on or around batteries to avoid short circuits or explosions.
- Strictly follow installation procedures when disconnecting AC or DC terminals.
- A 150A fuse is provided for battery over-current protection.
- GROUNDING INSTRUCTIONS: This inverter/charger must be connected to a permanent grounded wiring system. Comply with local requirements.
- NEVER cause AC output and DC input short circuits. Do NOT connect to the mains when DC input short circuits.
- Warning! Only qualified service persons are able to service this device. If errors persist after troubleshooting, return to local dealer or service center.
3. Installation
3.1 Unpacking and Inspection
Before installation, inspect the unit for any damage. The package should contain the inverter unit and a user manual.
3.2 Preparation
Before connecting any wiring, remove the bottom cover by unscrewing two screws.
3.3 Mounting the Unit
Consider the following for mounting:
- Do not mount on flammable construction materials.
- Mount on a solid surface.
- Install at eye level for easy LCD display reading.
- Allow approximately 20 cm clearance to the sides and 50 cm above and below for proper air circulation and heat dissipation.
- Ambient temperature should be between 0°C and 55°C.
- The recommended installation position is vertically on a wall.
SUITABLE FOR MOUNTING ON CONCRETE OR OTHER NON-COMBUSTIBLE SURFACE ONLY.
Install the unit by screwing two M6 screws. Dimensions are approximately 420mm (W) x 310mm (D) x 110mm (H).

Diagram showing the dimensions of the inverter (420mm W x 310mm D x 110mm H) and recommended mounting clearances.
3.4 Battery Connection
CAUTION: For safety, install a separate DC over-current protector or disconnect device between the battery and inverter.
WARNING! All wiring must be performed by qualified personnel. Use appropriate cable for battery connection to reduce risk of injury.
Recommended Battery Cable Size:
| Model | Wire Size | Cable (mm²) | Torque Value (max) |
|---|---|---|---|
| 3.6KW/4.2KW/6.2KW | 1 x 2AWG | 25 | 2 Nm |
Connection Steps:
- Remove 18 mm of insulation from positive and negative conductors.
- Suggest using bootlace ferrules on the wire ends with a proper crimping tool.
- Connect all battery packs as shown in the diagram. For 3.6KW/4.2KW models, use 24V batteries. For 6.2KW models, use 48V batteries.
- Insert battery wires flatly into inverter battery connectors and tighten bolts to 2 Nm in clockwise direction. Ensure correct polarity.

Diagram illustrating the series connection of 12V batteries to form 24V or 48V battery banks for the inverter.
WARNING: Shock Hazard. Installation must be performed with care due to high battery voltage in series.
CAUTION!! Before making the final DC connection or closing DC breaker/disconnector, ensure positive (+) is connected to positive (+) and negative (-) to negative (-).
3.5 AC Input/Output Connection
CAUTION!! Install a separate AC breaker between the inverter and AC input power source. This protects the inverter and allows for safe disconnection during maintenance.
Recommended AC breaker sizes: 32A for 3.6KW/4.2KW models, and 50A for 6.2KW models.
CAUTION!! Do NOT mis-connect input and output connectors. There are two terminal blocks marked “IN” and “OUT”.
WARNING! All wiring must be performed by qualified personnel. Use appropriate cable for AC input connection.
Suggested Cable Requirement for AC Wires:
| Model | Gauge | Cable (mm²) | Torque Value |
|---|---|---|---|
| 3.6KW/4.2KW | 12 AWG | 4 | 1.2 Nm |
| 6.2KW | 10 AWG | 6 | 1.2 Nm |
Connection Steps:
- Before making AC input/output connections, open the DC protector or disconnector.
- Remove 10mm of insulation from six conductors. Shorten phase L and neutral conductor N by 3mm.
- Insert AC input wires according to polarities (L=LINE, N=Neutral) and tighten terminal screws.
WARNING: Ensure AC power source is disconnected before attempting to hardwire it to the unit.
- Insert AC output wires according to polarities (L=LINE, N=Neutral) and tighten terminal screws.
- Ensure all wires are securely connected.

Image detailing the AC input, main output, second output, battery, and PV input terminals on the inverter's rear panel.
CAUTION: Appliances like air conditioners require 2-3 minutes to restart. If power fluctuates rapidly, it can damage connected appliances. Check if your air conditioner has a time-delay function.
3.6 PV Connection
CAUTION: Install a DC circuit breaker between the inverter and PV modules.
WARNING! Use appropriate cable for PV module connection.
PV Module Selection:
When selecting PV modules, consider:
- Open circuit Voltage (Voc) of PV modules must not exceed the max. PV array open circuit voltage of the inverter.
- Open circuit Voltage (Voc) of PV modules should be higher than the min. battery voltage.
| INVERTER MODEL | 3.6KW/4.2KW | 6.2KW |
|---|---|---|
| Max. PV Array Open Circuit Voltage | 500Vdc | |
| PV Array MPPT Voltage Range | 60Vdc~450Vdc | |
Recommended PV Module Configurations (Example: 250Wp PV module):
| Solar Panel Spec. (reference) | SOLAR INPUT (Min in serial: 6 pcs, max. in serial: 13 pcs) | Q'ty of panels | Total input power |
|---|---|---|---|
| 250Wp (Vmp: 30.1Vdc, Imp: 8.3A, Voc: 37.7Vdc, Isc: 8.4A, Cells: 60) | 6 pcs in serial | 6 pcs | 1500W |
| 8 pcs in serial | 8 pcs | 2000W | |
| 12 pcs in serial | 12 pcs | 3000W | |
| 13 pcs in serial | 13 pcs | 3250W | |
| 8 pieces in serial and 2 sets in parallel | 16 pcs | 4000W | |
| 10 pieces in serial and 2 sets in parallel | 20 pcs | 5000W | |
| 10 pieces in serial and 2 sets in parallel | 20 pcs | 6200W | |
| 12 pieces in serial and 2 sets in parallel | 24 pcs | 6500W | |
| 10 pieces in serial and 3 sets in parallel | 30 pcs | 7500W |
PV Module Wire Connection Steps:
- Remove 10 mm of insulation from positive and negative conductors.
- Suggest using bootlace ferrules on the wire ends.
- Check correct polarity of wire connection from PV modules and PV input connectors. Connect positive pole (+) to positive pole (+) and negative pole (-) to negative pole (-). Recommended tool: 4mm blade screwdriver.

Diagram illustrating the connection of solar panels to the inverter, including the use of a circuit protector.
3.7 Final Assembly
After connecting all wirings, replace the bottom cover by screwing the two screws back in.
3.8 Communication Connection
The inverter has two communication ports: RS232 for Wi-Fi module communication and RS485 for lithium battery BMS communication.

Diagram showing the inverter's communication ports (COMM, RS485, CAN, RS232) and how an RS485 communication cable connects to a battery.
- Wi-Fi Cloud Communication (Optional): Use the supplied communication cable to connect to the inverter and a Wi-Fi module. Download the app from the APP store and follow the “Wi-Fi Plug Quick Installation Guideline” to set up the network and register. The inverter status can then be monitored via mobile app or web page.
- GPRS Cloud Communication (Optional): Use the supplied communication cable to connect to the inverter and a GPRS module. Apply external power to the GPRS module. Download the app and follow the “GPRS RTU Quick Installation Guideline” to set up the network and register. The inverter status can then be monitored via mobile app or web page.
- Battery Communication: Communication between the battery and the inverter is realized through the battery communication interface, allowing the inverter and lithium battery to exchange information. If using lithium battery BMS communication, ensure the battery uses the PACE or PYLONTECH communication protocol.
4. Operation
4.1 Power ON/OFF
Once the unit is properly installed and batteries are connected, simply press the On/Off switch (located on the bottom of the case) to turn on the unit.
4.2 Operation and Display Panel
The operation and display panel is on the front of the inverter. It includes three indicators, four function keys, and an LCD display to show operating status and input/output power information.

Image showing the LCD display and function buttons on the front panel of the inverter.
LED Indicator Messages:
| LED Indicator | Color | Messages |
|---|---|---|
| INV/AC | Green | Solid On: Output is powered by utility in Line mode. Flashing: Output is powered by battery or PV in battery mode. |
| CHG | Green | Solid On: Battery is fully charged. Flashing: Battery is charging. |
| FAULT | Red | Solid On: Fault occurs in the inverter. Flashing: Warning condition occurs in the inverter. |
Function Keys:
| Function Key | Description |
|---|---|
| ESC | To exit setting mode |
| UP | To go to previous selection |
| DOWN | To go to next selection |
| ENTER | To confirm the selection in setting mode or enter setting mode |
4.3 LCD Display Icons
The LCD display uses various icons to convey information about input source, configuration, output, battery, load, and mode of operation. These include indicators for AC input, PV input, input/output voltage, frequency, current, load percentage, and fault/warning codes.
4.4 LCD Setting
To enter setting mode, press and hold the ENTER button for 3 seconds. Use UP/DOWN to select programs and ENTER to confirm, or ESC to exit. Key settings include:
- Program 00: Exit setting mode (One-button restore setting options available).
- Program 01: Output source priority (Utility first, Solar first, SBU priority).
- Program 02: Maximum charging current (10A to 60A, default 60A).
- Program 03: AC input voltage range (Appliances: 90-280VAC, UPS: 170-280VAC).
- Program 05: Battery type (AGM, Flooded, User-Defined, Lithium battery).
- Program 06: Auto restart when overload occurs (Enable/Disable).
- Program 07: Auto restart when over temperature occurs (Enable/Disable).
- Program 09: Output frequency (50Hz/60Hz).
- Program 10: Output voltage (220V, 230V, 240V).
- Program 11: Maximum utility charging current (2A to 30A, default 30A).
- Program 12: Setting voltage point back to utility source (21.0V to 25.5V for 3.6KW/4.2KW; 42V to 51V for 6.2KW).
- Program 13: Battery fully charged voltage (24V to 29V for 3.6KW/4.2KW; 48V to 54V for 6.2KW).
- Program 16: Charger source priority (Solar first, Solar and Utility, Only Solar).
- Program 18: Alarm control (Alarm on/off).
- Program 19: Auto return to default display screen (Enable/Disable).
- Program 20: Backlight control (Backlight on/off).
- Program 22: Beeps while primary source is interrupted (Alarm on/off).
- Program 23: Overload bypass (Enable/Disable).
- Program 25: Record Fault code (Enable/Disable).
- Program 26: Bulk charging voltage (C.V voltage) (28.2V for 3.6KW/4.2KW; 56.4V for 6.2KW).
- Program 27: Floating charging voltage (27.0V for 3.6KW/4.2KW; 54.0V for 6.2KW).
- Program 29: Low DC cut-off voltage (20.0V for 3.6KW/4.2KW; 40.0V for 6.2KW).
- Program 30: Battery equalization (Enable/Disable).
- Program 31: Battery equalization voltage (29.2V for 3.6KW/4.2KW; 58.4V for 6.2KW).
- Program 33: Battery equalized time (60min, adjustable).
- Program 34: Battery equalized timeout (120min, adjustable).
- Program 35: Equalization interval (30 days, adjustable).
- Program 36: Equalization activated immediately (Enable/Disable).
- Program 37: GRID-tie operation (Off grid, Hybrid).
- Program 38: GRID-tie current (10A, adjustable).
- Program 39: Led pattern light (On/Off).
- Program 41: Dual output (Disable/Use).
- Program 42: Enter the dual output functional voltage point (22.0V for 3.6KW/4.2KW; 44.0V for 6.2KW).
4.5 Display Setting
The LCD display information can be cycled by pressing the "UP" or "DOWN" key. Information includes input voltage, frequency, PV voltage, charging current, power, battery voltage, output voltage, load percentage, load in Watt/VA, DC discharging current, and main CPU Version.
4.6 Operating Mode Description
The inverter supports various operating modes, including Standby, Line mode, Battery mode, and Grid-Tie operation. Each mode has specific display characteristics and power flow behaviors.

Diagram illustrating the four charging modes (Only Solar, Mains First, Solar First, Mains & Solar) and three output modes (Solar First, Utility First, SBU First).
5. Maintenance
5.1 Clearance and Maintenance for Anti-Dust Kit
The inverter comes with a pre-installed anti-dust kit to protect internal components and enhance reliability, especially in harsh environments. The inverter automatically detects this kit and adjusts internal thermal sensors.
Maintenance Steps:
- Loosen the screw on the top of the inverter in a counterclockwise direction.
- Remove the dustproof case and take out the air filter foam.
- Clean the air filter foam and dustproof case.
- After cleaning, re-assemble the dust-kit back to the inverter.
NOTICE: The anti-dust kit should be cleaned from dust every one month.

Diagram showing the process of removing the anti-dust kit from the inverter for cleaning.
6. Troubleshooting
6.1 Fault Reference Code
The inverter's LCD display will show specific fault codes if an error occurs. Refer to the table below for common fault codes and their descriptions.
| Fault Code | Fault Event |
|---|---|
| 01 | Fan is locked when inverter is off. |
| 02 | Over temperature |
| 03 | Battery voltage is too high |
| 04 | Battery voltage is too low |
| 05 | Output short circuited or over temperature is detected by internal converter components. |
| 06 | Output voltage is too high. |
| 07 | Overload time out |
| 08 | Bus voltage is too high |
| 09 | Bus soft start failed |
| 51 | Over current or surge |
| 52 | Bus voltage is too low |
| 53 | Inverter soft start failed |
| 55 | Over DC voltage in AC output |
| 57 | Current sensor failed |
| 58 | Output voltage is too low |
| 59 | PV voltage is over limitation |
6.2 Warning Indicator
The inverter provides audible alarms and icon flashes for various warning conditions:
| Warning Code | Warning Event | Audible Alarm | Icon flashing |
|---|---|---|---|
| 01 | Fan is locked when inverter is on. | Beep three times every second | 01 icon |
| 03 | Battery is over-charged | Beep once every second | 03 icon |
| 04 | Low battery | Beep once every second | 04 icon |
| 07 | Overload | Beep once every 0.5 second | 07 icon |
| 10 | Output power derating | Beep twice every 3 seconds | 10 icon |
| 15 | PV energy is low. | Beep twice every 3 seconds | 15 icon |
| E9 | Battery equalization | None | E9 icon |
| 6P | Battery is not connected | None | 6P icon |
6.3 General Troubleshooting Table
| Problem | LCD/LED/Buzzer | Explanation / Possible cause | What to do |
|---|---|---|---|
| Unit shuts down automatically during startup process. | LCD/LEDs and buzzer active for 3 seconds then complete off. | The battery voltage is too low (<1.91V/Cell) | 1. Re-charge battery. 2. Replace battery. |
| No response after power on. | No indication. | 1. The battery voltage is far too low. (<1.4V/Cell) 2. Internal fuse tripped. | 1. Contact repair center for replacing the fuse. 2. Re-charge battery. 3. Replace battery. |
| Input voltage is displayed as 0 on the LCD and green LED is flashing. | Input protector is tripped | Check if AC breaker is tripped and AC wiring is connected well. | |
| Mains exist but the unit works in battery mode. | Green LED is flashing. | Insufficient quality of AC power. (Shore or Generator) | 1. Check if AC wires are too thin and/or too long. 2. Check if generator (if applied) is working well or if input voltage range setting is correct. (UPS Appliance) |
| Green LED is flashing. | Set "Solar First" as the priority of output source. | Change output source priority to Utility first. | |
| When the unit is turned on, internal relay is switched on and off repeatedly. | LCD display and LEDs are flashing | Battery is disconnected. | Check if battery wires are connected well. |
| Fault code 07 | Overload error. The inverter is overload 110% and time is up. | Reduce the connected load by switching off some equipment. | |
| Fault code 05 | Output short circuited. | Check if wiring is connected well and remove abnormal load. | |
| Fault code 02 | Temperature of internal converter component is over 120°C. Internal temperature of inverter component is over 100°C. | Check whether the air flow of the unit is blocked or whether the ambient temperature is too high. | |
| Buzzer beeps continuously and red LED is on. | Fault code 03 | Battery is over-charged. The battery voltage is too high. | Check if spec and quantity of batteries are meet requirements. |
| Fault code 01 | Fan fault | Replace the fan. | |
| Fault code 06/58 | Output abnormal (Inverter voltage below than 190Vac or is higher than 260Vac) | 1. Reduce the connected load. 2. Return to repair center. | |
| Fault code 08/09/53/57 | Internal components failed. | Return to repair center. | |
| Fault code 51 | Over current or surge. | Restart the unit, if the error happens again, please return to repair center. | |
| Fault code 52 | Bus voltage is too low. | ||
| Fault code 55 | Output voltage is unbalanced. |
7. Specifications
7.1 Line Mode Specifications
| INVERTER MODEL | 3.6KW | 4.2KW | 6.2KW |
|---|---|---|---|
| Input Voltage Waveform | Sinusoidal (utility or generator) | ||
| Nominal Input Voltage | 230Vac | ||
| Low Loss Voltage | 170Vac±7V (UPS); 90Vac±7V (Appliances) | ||
| Low Loss Return Voltage | 180Vac±7V (UPS); 100Vac±7V (Appliances) | ||
| High Loss Voltage | 280Vac±7V | ||
| High Loss Return Voltage | 270Vac±7V | ||
| Max AC Input Voltage | 300Vac | ||
| Nominal Input Frequency | 50Hz / 60Hz (Auto detection) | ||
| Low Loss Frequency | 40±1Hz | ||
| Low Loss Return Frequency | 42±1Hz | ||
| High Loss Frequency | 65±1Hz | ||
| High Loss Return Frequency | 63±1Hz | ||
| Output Short Circuit Protection | Circuit Breaker | ||
| Efficiency (Line Mode) | >95% (Rated R load, battery full charged) | ||
| Transfer Time | 10ms typical (UPS); 20ms typical (Appliances) | ||
| Output power derating: When AC input voltage drops to 170V, the output power will be derated. | ![]() | ||
7.2 Inverter Mode Specifications
| INVERTER MODEL | 3.6KW | 4.2KW | 6.2KW |
|---|---|---|---|
| Rated Output Power | 3.6KW | 4.2KW | 6.2KW |
| Output Voltage Waveform | Pure Sine Wave | ||
| Output Voltage Regulation | 230Vac±5% | ||
| Output Frequency | 50Hz | ||
| Peak Efficiency | 93% | ||
| Overload Protection | 3s@≥150% load; 5s@101%~150% load | ||
| Surge Capacity | 2* rated power for 5 seconds | ||
| Nominal DC Input Voltage | 24Vdc | 48Vdc | |
| Cold Start Voltage | 23.0Vdc | 46.0Vdc | |
| Low DC Warning Voltage @ load < 50% | 22.0Vdc | 44.0Vdc | |
| Low DC Warning Voltage @ load ≥ 50% | 21.0Vdc | 42.0Vdc | |
| Low DC Warning Return Voltage @ load < 50% | 22.5Vdc | 45.0Vdc | |
| Low DC Warning Return Voltage @ load ≥ 50% | 22.0Vdc | 44.0Vdc | |
| Low DC Cut-off Voltage @ load < 50% | 20.5Vdc | 41.0Vdc | |
| Low DC Cut-off Voltage @ load ≥ 50% | 20.0Vdc | 40.0Vdc | |
| High DC Recovery Voltage | 32Vdc | 62Vdc | |
| High DC Cut-off Voltage | 33Vdc | 63Vdc | |
| No Load Power Consumption | 30W | 35W | 50W |
7.3 Two Load Output Power
| INVERTER MODEL | 3.6KW | 4.2KW | 6.2KW |
|---|---|---|---|
| Full Load | 3600W | 4200W | 6200W |
| Maximum Main Load | 3600W | 4200W | 6200W |
| Maximum Second Load (battery model) | 1200W | 1400W | 2066W |
| Main Load Cut Off Voltage | 26VDC | 52VDC | |
| Main Load Return Voltage | 27VDC | 54VDC | |
7.4 Charge Mode Specifications
| INVERTER MODEL | 3.6KW | 4.2KW | 6.2KW |
|---|---|---|---|
| Utility Charging Mode | |||
| Charging Algorithm | 3-Step | ||
| AC Charging Current (Max) | 100Amp (@VI/P=230Vac) | ||
| Bulk Charging Voltage (Flooded Battery) | 29.2 | 58.4 | |
| Bulk Charging Voltage (AGM / Gel Battery) | 28.2 | 56.4 | |
| Floating Charging Voltage | 27Vdc | 54Vdc | |
| MPPT Solar Charging Mode | |||
| Max. PV Array Power | 6200W | 6500W | |
| Nominal PV Voltage | 240Vdc | 360Vdc | |
| PV Array MPPT Voltage Range | 60Vdc~500Vdc | ||
| Max. PV Array Open Circuit Voltage | 500Vdc | ||
| Max Charging Current (AC charger plus solar charger) | 120Amp | 120Amp | 120Amp |
7.5 Grid-Tie Operation
| INVERTER MODEL | 3.6KW | 4.2KW | 6.2KW |
|---|---|---|---|
| Nominal Output Voltage | 220/230/240 VAC | ||
| Feed-in Grid Voltage Range | 195~253VAC | ||
| Feed-in Grid Frequency Range | 49~51±1Hz/59~61±1Hz | ||
| Nominal Output Current | 15.7A | 18.2A | 26.9A |
| Power Factor Range | >0.99 | ||
| Maximum Conversion Efficiency (DC/AC) | 97% | ||
7.6 General Specifications
| INVERTER MODEL | 3.6KW | 4.2KW | 6.2KW |
|---|---|---|---|
| Safety Certification | CE | ||
| Operating Temperature Range | -10°C to 50°C | ||
| Storage temperature | -15°C~60°C | ||
| Humidity | 5% to 95% Relative Humidity (Non-condensing) | ||
| Dimension (D*W*H), mm | 358×442×116 | ||
| Net Weight, kg | 8.0 | 8.0 | 8.9 |
7.7 Approximate Back-up Time Table
The backup time depends on the quality, age, and type of battery. Specifications of batteries may vary depending on different manufacturers.
| Model | Load (W) | Backup Time @ 24Vdc 100Ah (min) | Backup Time @ 24Vdc 200Ah (min) |
|---|---|---|---|
| 3.6KW/4.2KW | 300 | 449 | 1100 |
| 600 | 222 | 525 | |
| 900 | 124 | 303 | |
| 1200 | 95 | 227 | |
| 1500 | 68 | 164 | |
| 1800 | 56 | 126 | |
| 2100 | 48 | 108 | |
| 2400 | 35 | 94 | |
| 2700 | 31 | 74 | |
| 3200 | 28 | 67 | |
| 3600 | 25 | 60 | |
| 4200 | 22 | 53 |
| Model | Load (W) | Backup Time @ 48Vdc 100Ah (min) | Backup Time @ 48Vdc 200Ah (min) |
|---|---|---|---|
| 6.2KW | 500 | 613 | 1288 |
| 1000 | 268 | 613 | |
| 1500 | 158 | 402 | |
| 2000 | 111 | 271 | |
| 2500 | 90 | 215 | |
| 3200 | 76 | 182 | |
| 3500 | 65 | 141 | |
| 4000 | 50 | 112 | |
| 4500 | 44 | 100 | |
| 5000 | 40 | 90 | |
| 6200 | 36 | 80 |
8. User Tips
- Battery Voltage Selection: Ensure you select the correct battery voltage (24V for 3.6KW/4.2KW models, 48V for 6.2KW models) during installation to prevent damage and ensure optimal performance.
- Wi-Fi Module for Remote Monitoring: If you intend to use remote monitoring via a mobile app, you will need to purchase a separate Wi-Fi module. The inverter has an RS232 communication port for this purpose. Ensure the inverter is near your router for connectivity.
- Lithium Battery BMS Communication: For lithium battery BMS communication, the inverter uses an RS485 port. It is crucial that your lithium battery supports either the PACE or PYLONTECH communication protocol for proper integration.
- Circuit Breaker Sizing: Always use appropriately sized circuit breakers for battery, PV input, AC input, and AC output connections as specified in the installation section to ensure safety and prevent damage.
- System Integration: This inverter is designed to work seamlessly with a utility network, allowing for automatic switching to grid power when alternative energy sources are insufficient. This is ideal for applications like caravans or homes requiring reliable backup.
9. Warranty and Support
For detailed warranty information, service, and support, please refer to the complete user manual PDF. The PDF manual contains comprehensive details regarding warranty terms, technical support contacts, and service procedures.
You can access the full user manual (PDF) for more information: Sumry Hybrid Inverter User Manual (PDF)