1. Introduction
The GEYA GYHO9 Manual Transfer Switch (MTS) is designed to manually transfer power between a main power source and an alternate source, such as a backup generator. This ensures continuous power supply to loads during utility failures or planned maintenance. This device features clearly marked power positions with indicator lights for easy status monitoring and a label window for clear identification of power sources.
2. Safety Information
Always observe the following safety precautions to prevent injury or damage to the device:
- Installation and maintenance should only be performed by qualified electricians.
- Ensure all power sources are disconnected before installation, wiring, or maintenance.
- Verify correct wiring and connections before applying power.
- Do not operate the switch if it appears damaged or faulty.
- Adhere to all local and national electrical codes and regulations.
3. Specifications
| Feature | Specification |
|---|---|
| Brand Name | GEYA |
| Model Number | GYHO9 MTS |
| Type | Mini Circuit Breaker, Manual Transfer Isolating Switch |
| Is Smart Device | No |
| Rated Voltage Ue | AC220/400V |
| Rated Current | 63A, 100A, 125A |
| Poles | 1P, 2P, 3P, 4P |
| Rated Frequency | 50/60Hz |
| Standard | IEC/EN60947-3 |
| Mounting | Din Rail |
| Mechanical Life | 10000 Cycles |
| Cable Size (63A) | Max 10mm² |
| Cable Size (100A/125A) | Max 50mm² |
| Certification | CE |
Dimensions (Unit: mm)
63A Models:
- 1P Width: 18mm
- 2P Width: 36mm
- 3P Width: 54mm
- 4P Width: 72mm
- Depth: 75mm
- Height (from top of rail to top of device): 83mm
- Total Height: 85mm

Figure 3.1: Dimensions for 63A models.
100A/125A Models:
- 1P Width: 36mm
- 2P Width: 72mm
- 3P Width: 108mm
- 4P Width: 144mm
- Depth: 75mm
- Height (from top of rail to top of device): 83mm
- Total Height: 85mm

Figure 3.2: Dimensions for 100A and 125A models.
4. Setup and Installation
Mounting
The GEYA GYHO9 Manual Transfer Switch is designed for Din Rail mounting. Ensure the Din Rail is securely installed in your electrical panel according to standard practices.
Wiring Instructions
Refer to the circuit diagram and the product video for a visual guide. The switch features clearly labeled terminals for load (output) and two separate power inputs (Input I and Input II).
- Load (Output) Connections: Connect the load wires to terminals 1, 5, 9, and 13 (depending on the number of poles). For a 2P model, connect to terminals 1 and 5.
- Input I Connections: Connect the wires from the first power source (e.g., main utility power) to terminals 2, 6, 10, and 14 (depending on the number of poles). For a 2P model, connect to terminals 2 and 6.
- Input II Connections: Connect the wires from the second power source (e.g., backup generator) to terminals 4, 8, 12, and 16 (depending on the number of poles). For a 2P model, connect to terminals 4 and 8.
Ensure all connections are tight and secure. The upper end of the switch has a wiring diagram for quick reference.

Figure 4.1: Top view of the switch showing the integrated wiring diagram.

Figure 4.2: Detailed circuit diagrams for 1P, 2P, 3P, and 4P models.
Installation Video Guide
Watch this video for a step-by-step guide on unboxing and basic wiring of the GEYA GYHO9 Manual Transfer Switch:
Video 4.1: Unboxing and basic operation/wiring demonstration of the GYHO9 switch.
5. Operating Instructions
The GYHO9 Manual Transfer Switch features a rotary knob for selecting the power source and indicator windows to display the current status.
Knob Positions and Indicator Lights
- Position '1' (Main Power ON): The switch connects the load to Input I (Main Power). The indicator window will show Red.
- Position 'O' (OFF): The switch disconnects the load from both Input I and Input II. The indicator window will show Green. This is the disconnected, safe position.
- Position '2' (Standby Power ON): The switch connects the load to Input II (Standby Power). The indicator window will show Yellow.

Figure 5.1: Close-up of the GYHO9 switch showing indicator lights and knob positions.

Figure 5.2: GYHO9 switch with indicator window showing gear position.
6. Maintenance
Regular maintenance helps ensure the longevity and safe operation of your manual transfer switch.
- Visual Inspection: Periodically inspect the switch for any signs of physical damage, loose connections, or discoloration.
- Cleaning: Keep the switch free from dust and debris. Use a dry, non-abrasive cloth for cleaning. Do not use liquid cleaners.
- Terminal Check: Ensure all terminal screws remain tight. Loose connections can lead to overheating and potential hazards.
- Operational Check: Test the switch periodically by manually transferring between power sources to ensure smooth operation.
Always disconnect power before performing any maintenance or inspection.
7. Troubleshooting
If you encounter issues with your GEYA GYHO9 Manual Transfer Switch, consider the following basic troubleshooting steps:
- No Power to Load:
- Check if the switch is in the correct 'ON' position (1 or 2).
- Verify that the selected power source (Input I or Input II) is active and supplying power.
- Inspect all wiring connections for looseness or damage.
- Switch is Stiff or Hard to Operate:
- Ensure there is no physical obstruction preventing the knob from turning.
- Do not force the switch. If it remains stiff, contact a qualified electrician for inspection.
- Indicator Light Not Working:
- The indicator lights are designed to show the switch position. If a light is not illuminating in an 'ON' position, it may indicate a fault with the indicator or the power supply to that input.
For persistent issues or complex problems, consult a qualified electrician.
8. User Tips
- Clear Labeling: Utilize the label window on the switch to clearly mark which power source corresponds to Input I (e.g., 'Utility Grid') and Input II (e.g., 'Generator'). This helps prevent confusion during operation.
- Regular Testing: If using for backup power, periodically test your generator and the transfer switch operation to ensure readiness during an actual outage.
- Smooth Operation: Always operate the switch knob with a firm but smooth motion to ensure proper contact engagement and disengagement.
9. Warranty and Support
For warranty information, technical support, or service inquiries, please contact GEYA customer service or your authorized dealer. Keep your purchase receipt as proof of purchase.