1. Introduction
This is a multifunctional solar inverter, integrating an MPPT solar charge controller, a high-frequency pure sine wave inverter, and a UPS function module into one machine. It is designed to offer uninterruptible power support with a portable size. This inverter is ideal for off-grid backup power and self-consumption applications and can operate with or without batteries.
The complete system requires additional components such as PV modules, a generator, or a utility grid. The built-in WiFi module allows users to monitor the status of the PV system from a mobile phone or website anytime, anywhere.
Figure 1: POWLAND 6.5KW Hybrid Solar Inverter
2. Safety Instructions
This chapter contains important safety and operating instructions. Please read and keep this manual for future reference to ensure personal safety and proper operation of the inverter.
WARNING!
- High Voltage: Above 50Vac or 75Vdc. Do not disconnect under load.
- Electrical Hazard: Start maintaining the INVERTER at least 5 minutes after disconnecting from all external power supplies.
- All wiring must be performed by qualified personnel.
- Do not disassemble the unit. Refer to a qualified service center for service or repair.
- Disconnect all wirings before attempting any maintenance or cleaning.
- NEVER charge a frozen battery.
- Do NOT connect to the mains when DC input short circuits.
- Ensure the inverter is completely assembled before operation.
CAUTION!
- Ensure you know the battery system type (lithium or lead-acid) to prevent malfunction.
- All electrical installations must comply with local electrical safety standards.
- When installing PV modules during daytime, cover them with opaque materials to avoid high terminal voltage.
- Charge only deep-cycle lead-acid or lithium batteries. Other battery types may burst.
- Use appropriate cable sizes as specified in this manual for optimum operation and to reduce risk of injury.
- Be cautious when working with metal tools near batteries to prevent short circuits.
- Strictly follow installation procedures when disconnecting AC or DC terminals.
- This inverter must be connected to a permanently grounded wiring system.
3. Setup
3.1 Unpacking and Inspection
Products are strictly tested before leaving the factory. Upon receipt, inspect the outer packaging for any damage. If the product or packaging is damaged, contact your local distributor immediately. Open the box and check the internal equipment for damage.
Figure 2: Inverter in packaging
Figure 3: Inverter and accessories in box
3.2 Installation Tools
The following tools are recommended for installation:
- Multi-meter
- Protective gloves
- Insulated anti-smashing shoes
- Safety glasses
- ESD wrist strap
- Hammer drill
- Electric screwdriver
- Cross screwdriver
- Rubber mallet
- Spirit level
- Wire cutter / stripper
- Terminal crimping tool
3.3 Mounting Unit
Consider the following points when selecting an installation location:
- Do not mount the inverter on flammable construction materials.
- Mount on a solid surface.
- Install at eye level for easy LCD display reading.
- Ambient temperature should be between -10°C and 60°C.
- Mount vertically on the wall.
- Ensure sufficient clearance for heat dissipation and wiring (30cm top/bottom, 30cm sides).
WARNING! Inverter is suitable for mounting on concrete or other non-combustible surfaces only.
Installation Steps:
- Use an Ø8 drilling bit to drill holes on the mounting surface. The distance between the two holes should be 160mm. Insert the expansion screw tube (M6 expansion screw is suggested).
- Align the inverter's top screw holes with the installed expansion screw tubes and fix the inverter to the mounting surface.
- Before connecting wiring, remove the bottom cover by unscrewing four screws.
Figure 4: Mounting the Unit and System Diagram
3.4 AC Input / Output Connection
CAUTION!
- Install a separate AC breaker (recommended 40A) between the inverter and AC input source.
- Do NOT mis-connect input and output connectors.
- Ensure correct AC cable polarity (L and N wires not connected together).
- Use appropriate cable sizes: 10 AWG (5.26 mm²) for AC input, 12 AWG (4 mm²) for AC output.
- Make sure AC power is disconnected before connecting.
AC Input Connection Steps:
- Open the AC circuit breaker.
- Remove 12mm of insulation from cable heads, shorten conductor to 10mm. Insert into tubular terminal and crimp tightly.
- Insert AC input cables according to polarities (PE first, then L, N) and tighten terminal screws.
AC Output Connection Steps: Follow the same steps as AC input connection for L (LINE) and N (Neutral) cables.
NOTE: Appliances like air conditioners require 2-3 minutes to restart. Ensure they have a time-delay function to prevent damage from power fluctuations.
Figure 5: Inverter Ports Overview
Figure 6: Inverter Rear Connections
3.5 PV Connection
WARNING!
- Install a separate DC circuit breaker between the inverter and PV modules.
- Do not ground the positive or negative terminals of the PV modules.
- Exposure to sunlight can generate lethal high voltages.
- Connect PV terminals to corresponding ports; reversing polarity can damage the inverter.
- Use appropriate 10 AWG (5.26 mm²) cable for PV module connection.
PV Module Selection Parameters:
- Max. PV Array Open Circuit Voltage (Voc): Must not exceed 500Vdc.
- Open Circuit Voltage (Voc): Must be higher than the start-up voltage (80Vdc).
- PV Array MPPT Voltage Range: 60Vdc~450Vdc.
PV Module Connection Steps:
- Open the DC circuit breaker.
- Remove 12mm of insulation from cable heads, shorten conductor to 10mm. Insert into tubular terminal and crimp tightly.
- Use a multi-meter to check polarities.
- Insert PV cables according to polarities (PV+ red, PV- black) and tighten terminal screws.
Figure 7: Solar System Connection Diagram
Figure 8: Solar Panel Wiring Methods (Series/Parallel)
3.6 Battery Connection
WARNING! Shock Hazard: Installation must be performed with care due to high battery voltage in series.
3.6.1 Lead-acid Battery Connection:
- Use a 48V nominal deep-cycle lead-acid battery (AGM or FLD type).
- Install a separate DC over-current protector or disconnect device (recommended 150A).
- Use appropriate 2 AWG (25 mm²) cable. Recommended charge current is 0.3C.
3.6.2 Lithium Battery Connection:
- Check protocol compatibility for the lithium battery.
- Connect the RJ45 terminal of the battery communication cable to the BMS communication port (RS485 or CAN) on the inverter.
- Set the battery type to 'LIT' or 'FEL' in LCD Setting Program 17.
Battery Connection Steps (for both types):
- Unscrew pre-fixed screws on battery poles. Prepare 2 DT terminals (for AWG2 cables).
- Remove 12mm insulation, shorten conductor to 10mm, insert into DT terminal, and crimp tightly.
- Pass the battery cable through the bottom shell, ensure correct polarity (+ to +, - to -), and tighten terminal screws.
- Connect all battery packs as required (suggested at least 200Ah capacity).
Figure 9: Battery Connection Diagram
3.7 Smart Communication Stick Connection (Optional)
The smart communication stick (WiFi) connects the inverter to the cloud platform for remote monitoring. Insert the stick directly into the COM port. Refer to the solar APP quick configuration guide for models with built-in WiFi monitoring.
Figure 10: WiFi Monitoring Setup
4. Operation
4.1 Power ON/OFF
Once the inverter is properly installed and batteries are connected, press the ON/OFF switch (located on the bottom of the case) to turn on the unit.
4.2 Operation and Display Panel
The front panel features an LCD display, four indicators, and four function keys to show operating status and power information.
Figure 11: Product Overview - LCD and Function Keys
LED Indicators:
- AC / INV (Green): Solid On - Output is powered by utility in Line mode. Flashing - Output is powered by battery or PV in battery mode.
- Charging (Yellow): Solid On - Battery is fully charged. Flashing - Battery is charging.
- Fault (Red): Solid On - Fault occurs. Flashing - Warning condition occurs.
Function Keys:
- ESC: To exit setting mode.
- UP: To go to previous selection.
- DOWN: To go to next selection.
- ENTER: To confirm selection or enter setting mode.
4.3 LCD Display Icons and Information
The LCD displays various icons and information related to the inverter's status. These include:
- Battery Information (icon, type, voltage, charging/discharging current)
- AC Input Information (icon, UPS/APP mode, voltage, frequency)
- PV Input Information (icon, power, voltage, current)
- Output Information (voltage, apparent power, active power, frequency)
- Battery Capacity and Load Capacity
- AC OUTPUT2 Information
- Parameter Query, Function Setting, Fault/Alarm Information
- Other Information (Mute, WiFi connected, PV+Grid status)
Figure 12: LCD Display Icons and Meanings
4.4 LCD Settings
To enter setting mode, press and hold the ENTER button for 2 seconds. Use UP/DOWN to navigate, ENTER to confirm, and ESC to exit. Key settings include:
- Output Voltage: 230V (default), adjustable from 208V to 240V.
- Output Frequency: 50Hz/60Hz.
- Output Source Priority: Grid first, Solar first, MKS (Generator priority), PBG (PV, Battery, Grid).
- Input Mode: APP (Appliance), UPS (Computer), GEN (Generator).
- Charger Source Priority: PV and Grid, Only PV, PV first.
- Charging Currents: Grid charging current (2A-120A), Maximum charging current (2A-120A).
- Battery Settings: Battery type (AGM, Flooded, Lithium Ternary, Lithium Iron, User-Defined), low voltage alarm, shutdown voltage, constant voltage mode, floating charge mode, equalization settings.
- System Features: Auto restart (overload/over temperature), main input cut warning, energy-saving mode, overload transfer to bypass, silent mode, grid-tie inverter function, BMS communication.
4.5 Display Information
The LCD cycles through various information screens (P1-P9) by pressing UP or DOWN. If idle, it displays daily PV power generation. Information includes:
- Daily and total PV power generation.
- Lithium battery voltage, current, temperature, SOC, rated capacity, remaining capacity.
- Lithium battery maximum charging/minimum discharging voltage and current.
- Lithium battery alarm and fault information.
- Inverter firmware version.
5. Maintenance
Regular maintenance ensures the longevity and optimal performance of your inverter. Always observe safety precautions before performing any maintenance tasks.
- Power Disconnection: Before any maintenance, disconnect the inverter from all external power supplies (AC, DC, and batteries) and wait at least 5 minutes to allow internal components to discharge.
- Cleaning: Regularly check and clean the dust filter to prevent excessive dust accumulation, which can hinder heat dissipation.
- Visual Inspection: Periodically inspect all wiring connections for tightness and signs of wear or damage.
- Environmental Check: Ensure the installation area remains within the recommended temperature and humidity ranges and has adequate clearance for ventilation.
6. Troubleshooting
6.1 Fault Reference Codes
If a fault occurs, the Fault indicator (red LED) will be solid ON, and the buzzer will sound for 10 seconds then stop. The LCD will display a fault code. The system will attempt to restart automatically. If it fails after six attempts, the inverter will remain in fault status. Power off the unit or wait 30 minutes to restart.
NOTE: Contact the manufacturer for troubleshooting if the issue persists.
Common fault codes include:
- Fault 1: Bus boost fail - Grid soft start process starts but bus voltage does not reach set value.
- Fault 2: Bus over voltage - Bus voltage is higher than set value.
- Fault 5: System over temperature - PFC temperature is higher than set value or fan is not connected.
- Fault 14: Over load - The load current is higher than the set value.
- Fault 18: PV reverse connection - PV cables connected with incorrect polarity.
- Fault 26: BMS fault - Error code in BMS message.
6.2 Alarm Reference Codes
If an alarm occurs, the red LED will flash, and the LCD will display an alarm code. The inverter does not enter fault mode during an alarm.
Common alarm codes include:
- Alarm 50: Battery open - Battery disconnected for <10 minutes.
- Alarm 51: Battery under voltage - Battery voltage is lower than BAU set value.
- Alarm 56: BMS loss - Communication failure after BMS communication function is enabled.
- Alarm 58: Fan error - No fan speed signal detected.
- Alarm 62: PV energy weak - PV power is lower than load demand.
6.3 Troubleshooting Table
| Problem | Fault Event | Trigger Conditions | What to do |
|---|---|---|---|
| LED screen display fault code 2 | Bus voltage high | Total rated voltage of PV string exceeds Max. PV open circuit voltage of inverter. | Reduce the PV module number. |
| LED screen display fault code 3 | Bus voltage low | Too many impact loads. | Remove some loads from the inverter. |
| LED screen display fault code 5 | Over temperature | Fan not rotating, dirty dust filter, insufficient clearance, high ambient temperature. | Check fan/wiring, clean filter, ensure clearance, avoid direct sunlight. |
| LED screen display fault code 56 | BMS loss | Communication cable unplugged, battery dial switch setting inconsistent, BMS protocol mismatch. | Check cable connection, verify battery settings, replace cable/battery/inverter if needed. |
| LED screen display fault code 58 | Fan abnormal alarm | Fan rotation abnormal, foreign object, fan not connected, damaged fan. | Check for obstructions, ensure connection, replace fan. |
| LED screen display fault code 62 | PV Energy Weak | PV power is not normal or lower than load demand. | Repair PV system if abnormal, remove part of the load. |
7. Specifications
| Feature | Specification |
|---|---|
| Model Number | ISolar-SMS-6.5KP-WIFI |
| Rated Power | 6500VA / 6500W |
| Max PV Array Power | 9000W |
| PV Array MPPT Voltage Range | 60VDC-500VDC |
| Max. Charge Current | 120A |
| Output Type | SINGLE |
| Output Frequency | 50HZ/60HZ |
| Output Voltage Range | 230VAC |
| Surge Power | 12KVA |
| Battery Type | Lifepo4, Lithium, Flooded, Gel, Lead-acid Batteries |
| Lithium battery Communication | YES (RS485) |
| Feature | Support wifi module |
| Is Smart Device | Yes |
| Size | 445x385x165mm |
| Weight | 8.8kg |
| EU LVD Voltage | High voltage: Above 50Vac or 75Vdc |
| Certification | CE |
| Operation Temperature | -10°C ~ 60°C |
| Relative Humidity | 5% ~ 95% (Non-condensing) |
| Max. Operating Altitude | 4000m (Derating above 2000m) |
| Interface | Standard: RS232; CAN & RS485; WiFi |
| Safety Standard | EN/IEC62109-1, EN/IEC62109-2 |
Figure 13: Certifications
8. User Tips
Here are some helpful tips based on user experiences:
- Fan Noise: The inverter's fans may run continuously and can be audible. This is normal operation for cooling.
- Manual Language: This manual is provided in English. Please read it carefully to ensure full understanding of all instructions and safety guidelines.
- Display/PV Issues: If you encounter issues with the display or PV charging (e.g., fluctuating voltage, missing symbols), first verify all PV connections, check for any fault/alarm codes on the LCD, and ensure all settings are correctly configured according to this manual.
- WiFi Monitoring: For remote monitoring, ensure the WiFi module is properly inserted into the COM port and configured using the Wattseek APP. Check your internet connection if data logging is not working.
- Parallel Compatibility: If planning to use the inverter in a parallel configuration, ensure compatibility with other inverters and carefully follow specific parallel connection instructions, as not all setups may be compatible.
9. Warranty and Support
This product comes with a 1-year warranty from the store.
For more detailed information, including comprehensive diagrams and advanced settings, please refer to the complete User Manual PDF available at: User Manual (PDF).
If you have any problems or require technical assistance, please contact the seller or a qualified service technician.