LCTC TC4W

Contents

LCTC TC4W PID Temperature Controller Instruction Manual

Model: TC4W

1. Introduction

The LCTC TC4W is a versatile digital PID temperature controller designed for precise temperature regulation in various industrial and laboratory applications. It features advanced ramp and soak intelligent regulation, multiple input types for thermocouples (K, E, J, S, R, B, N, T) and thermal resistances (Pt100, Cu50), and flexible output options including SSR, Relay, and 4-20mA. Its compact 96x48mm panel size makes it suitable for integration into control panels.

2. Features

  • Digital PID Temperature Control with Ramp and Soak Functionality
  • Multiple Input Types: Thermocouple (K, E, J, S, R, B, N, T) and Thermal Resistance (Pt100, Cu50)
  • Dual Output Modes: SSR + Relay, or 4-20mA (DC4-20mA)
  • Alarm Methods: One group output (ALM1) or Two group outputs (ALM1 and ALM2)
  • High Accuracy: ±0.5%FS or ±1.0%FS
  • Control Method: Continuous PID control or position control
  • Compact Panel Size: 96x48mm
  • Wide Power Supply Range: 100-240VAC, 50/60Hz

3. Specifications

ParameterValue
ModelTC4W
Power Supply100-240VAC, 50/60Hz
Power Consumption< 10VA
Input TypeK, E, J, S, R, B, N, T Thermocouple; Pt100, Cu50 Thermal Resistance (adjustable, full input)
Output TypeTwo output modes: (SSR+relay), (DC4-20mA) output
Size (Dimensions)96mm (W) x 48mm (H) x 75mm (D)
Opening Size92mm (W) x 45mm (H)
Use EnvironmentTemperature: 0~50°C, Humidity: 30~85%RH (non-condensing, without corrosive gas)
Alarm RangeFree setting of full scale
Product Accuracy±0.5%FS or ±1.0%FS
Control MethodContinuous PID control or position control

4. Model Definition Selection

The TC4W series offers various configurations. Use the table below to understand the model naming convention:

SequenceNameIllustration
①Meter size (mm)S=48x48x75, opening size 45x45
H=48x96x75, opening size 45x92
W=96x48x75, opening size 92x45
M=72x72x75, opening size 68x68
L=96x96x75, opening size 92x92
②Output typeR=Relay contact output (RELAY)
Q=voltage pulse output (SSR)
8=Current output (DC4-20mA)
③Alarm method1=One group output (ALM1)
2=Two group outputs (ALM1 and ALM2)
④Input typeTC=Thermocouple (K, E, J, S, R, B, N, T)
Rt=Thermal resistance (Pt100, Cu50)

Note: The meter has two outputs (SSR+relay) but the two output methods cannot be used at the same time. Please select the appropriate model based on your application requirements.

5. Setup and Wiring

Proper wiring is crucial for the safe and correct operation of the temperature controller. Always ensure power is disconnected before performing any wiring.

5.1. Dimensions and Terminal Layout

Refer to the diagram below for the physical dimensions and the layout of the terminal block on the back of the controller.

LCTC TC4W PID Temperature Controller Dimensions and Terminal Layout

Figure 1: Controller Dimensions and Terminal Layout

5.2. Wiring Diagrams

Below are the wiring diagrams for different output types. Choose the diagram that corresponds to your controller's output configuration.

5.2.1. Relay Contact Output (RELAY) Wiring Diagram

Relay Contact Output Wiring Diagram for TC4W

Figure 2: Relay Output Wiring Diagram

  • Connect AC220V power supply to terminals 8 and 9.
  • Short-circuit terminals 1 and 3.
  • Connect thermocouple blue wire to terminal 5.
  • Connect thermocouple red wire to terminal 6.
  • For thermal resistance (Pt100/Cu50) with three wires: connect the red wire to terminal 7, and the other two wires to terminals 5 and 6 (interchangeable).

5.2.2. Voltage Pulse Output (SSR) Wiring Diagram

Voltage Pulse (SSR) Output Wiring Diagram for TC4W

Figure 3: SSR Output Wiring Diagram

  • Connect AC220V power supply to terminals 8 and 9.
  • Connect SSR '+' to terminal 1.
  • Connect SSR '-' to terminal 2.
  • Connect thermocouple blue wire to terminal 5.
  • Connect thermocouple red wire to terminal 6.
  • For thermal resistance (Pt100/Cu50) with three wires: connect the red wire to terminal 7, and the other two wires to terminals 5 and 6 (interchangeable).

5.2.3. Current Output (4-20mA) Wiring Diagram

4-20mA Output Wiring Diagram for TC4W

Figure 4: 4-20mA Output Wiring Diagram

  • Connect AC220V power supply to terminals 8 and 9.
  • Connect 4-20mA output to terminals 1 and 2.
  • Connect thermocouple blue wire to terminal 5.
  • Connect thermocouple red wire to terminal 6.
  • For thermal resistance (Pt100/Cu50) with three wires: connect the red wire to terminal 7, and the other two wires to terminals 5 and 6 (interchangeable).

6. Operating Instructions

The TC4W controller features a clear digital display and intuitive buttons for operation. The top display (PV) shows the current process value (e.g., temperature), and the bottom display (SV) shows the set value.

6.1. Basic Operation

  • Power On: Connect the controller to the specified power supply (100-240VAC, 50/60Hz). The display will light up.
  • Viewing Current Temperature: The PV display shows the real-time temperature measured by the connected sensor.
  • Setting Temperature: Use the 'SET' button to enter the setting mode. Use the arrow keys (up/down) to adjust the set value (SV). Press 'SET' again to confirm and exit.
  • Mode Button: The 'MODE' button is typically used to cycle through different parameters and settings menus. Refer to the full programming manual for detailed parameter adjustments.

6.2. PID Control Demonstration

The video below demonstrates the PID control functionality of a similar temperature controller, showing how it regulates power to maintain a set temperature. The oscilloscope displays the output waveform as the controller adjusts the heating element.

Video 1: PID Control Demonstration with Oscilloscope Output

7. User Tips

  • Verify Wiring: Always double-check all wiring connections against the provided diagrams before applying power to prevent damage to the controller or connected equipment.
  • Sensor Compatibility: Ensure the connected temperature sensor (thermocouple or RTD) is compatible with the controller's input type setting. Incorrect sensor type selection will lead to inaccurate readings.
  • Environmental Conditions: Operate the controller within the specified temperature (0~50°C) and humidity (30~85%RH) ranges to ensure optimal performance and longevity.

8. Troubleshooting

If you encounter issues with your LCTC TC4W temperature controller, consider the following common troubleshooting steps:

  • No Power/Display: Check the power supply connections (terminals 8 and 9) and ensure the voltage is within the 100-240VAC range. Verify the fuse if accessible.
  • Inaccurate Temperature Reading (PV):
    • Ensure the temperature sensor is correctly connected to the input terminals (5, 6, 7).
    • Verify that the input type setting in the controller matches the type of sensor being used (e.g., K-type thermocouple, Pt100 RTD).
    • Check the sensor for damage or loose connections.
  • Output Not Activating:
    • Confirm the output wiring is correct for your chosen output type (SSR, Relay, or 4-20mA).
    • Check the set temperature (SV) and ensure it is within the desired control range relative to the process value (PV).
    • Inspect the connected load (e.g., heating element, SSR) for proper function.
  • Unstable Control: If the temperature is oscillating or not stabilizing, the PID parameters may need adjustment. Refer to the detailed programming manual for guidance on tuning PID settings.

For persistent issues, contact technical support.

9. Maintenance

To ensure the longevity and reliable operation of your LCTC TC4W PID Temperature Controller, follow these maintenance guidelines:

  • Cleaning: Keep the controller clean and free from dust and debris. Use a soft, dry cloth for cleaning. Avoid using abrasive cleaners or solvents.
  • Environmental Protection: Ensure the operating environment adheres to the specified temperature and humidity ranges. Protect the controller from excessive vibration, moisture, and corrosive gases.
  • Connection Checks: Periodically inspect all wiring connections for tightness and signs of wear or corrosion.
  • Ventilation: Ensure adequate ventilation around the controller to prevent overheating, especially if mounted in an enclosure.

10. Warranty and Support

For information regarding warranty coverage, technical support, or service, please refer to the documentation provided with your purchase or contact the seller directly. Keep your purchase receipt or order details handy when seeking support.


Documents and downloads

Ask a question about this manual

Ask about setup, troubleshooting, compatibility, parts, safety, or missing instructions. Manuals+ will review the question and use this page’s manual context to help answer it.

After a successful submission, we securely hash the supplied account or form email before sending it to Microsoft Advertising for conversion attribution. Privacy details.