EARUELETRIC EA771, EA777

Contents

EARUELETRIC Three-Phase Four-Wire Electronic Energy Meter Instruction Manual

Models: EA771, EA777

Brand: EARUELETRIC

1. Product Overview

The EARUELETRIC Three-Phase Multifunctional Electronic Energy Meter (Models EA771 and EA777) is a state-of-the-art device designed for accurate measurement of electrical energy. Utilizing microelectronic technology, imported large-scale integrated circuits, digital acquisition, and SMT processes, these meters offer reliable performance and precise data collection.

They comply with national standards GB/T117215.321-2008 (IEC 62053-21:2003, IDT) and GB/T17215.322-2008 (IEC 62053-22:2003, IDT) for Class 1 or 0.5S accuracy. The meters are capable of directly and accurately measuring AC voltage with a rated frequency of 50/60Hz. They display total active electric energy, total reactive electric energy, input/output active/reactive electric energy, three-phase voltage, current, total/phase active power, total/phase power factor, and frequency via an LCD.

Key advantages include high reliability, compact size, light weight, aesthetic design, and flexible installation.

Comparison of EA771 and EA777 Energy Meters

Figure 1: Comparison of EA771 and EA777 Energy Meters. EA771 displays total power consumption only, while EA777 features backlight, active/reactive power, current/voltage, RS485, power factor, frequency, manual switching, bi-directional measurement, and zeroing capability.

2. Specifications

Feature Comparison Table: EA771 vs EA777

Figure 2: Detailed feature comparison between EA771 and EA777 models.

ParameterEA771EA777
Model NumberEA771EA777
MaterialMetal + ABS
Reference Voltage3x127/220V, 3x220/380V, 3x230/400V
Reference Current3x10(100A)3x5(80)A
Accuracy Class1.01.0
Rated Frequency50/60 Hz
Constant Pulse400imp/kWh
Display TypeLCD 6+1 (999999.9 kWh)
Power Consumption≤2W, 10VA
Starting Current0.004Ib0.4%Ib
Operating Temperature-10°C to +55°C
Storage Temperature-25°C to +70°C
Operating Voltage Range0.9-1.1 Rated Voltage
Utmost Voltage Range0.7-1.2 Rated Voltage
Average Annual Humidity≤75%
TypeThree Phase Four Wire Electronic Type
Degree of ProtectionIP20
WeightApproximately 400g
Dimensions (EA771)100mm (H) x 75mm (W) x 65mm (D)N/A
Dimensions (EA777)N/A100mm (H) x 72mm (W) x 66mm (D)
Output VoltageAC
Power SupplyAC
CertificationCE
EA771 Dimensions Diagram

Figure 3: EA771 Dimensions (100mm Height, 75mm Width, 65mm Depth).

EA777 Dimensions Diagram

Figure 4: EA777 Dimensions (100mm Height, 72mm Width, 66mm Depth).

3. Features

  • DIN Rail Mounting: 35mm DIN standard rail mounting, compliant with DIN EN-50022. Can be installed directly in household lighting distribution boxes.
  • High Accuracy: Accurate measurement of active electric energy (Level 1) and reactive electric energy (Level 2).
  • LCD Display: Clear 6+1-bit LCD display (999999.9 kWh) for easy reading.
  • Pulse Output: Passive pulse output conforming to DIN43864 standard, with LED indication.
  • Parameter Query: Quick query function for various electrical parameters.
  • RS485 Communication (EA777): Equipped with an RS485 communication interface, supporting Modbus communication protocol or DL/645-2007 communication protocol (optional).
  • Reactive Energy Measurement: Capable of measuring reactive energy.
  • Comprehensive Display: Displays current, voltage, and power factors.
  • Power-off Memory: Data is not zeroed in the event of a power failure, preventing measurement errors and data loss.
  • Bi-Directional Measurement (EA777): Supports bi-directional energy measurement.
  • Zeroable (EA777): The EA777 model allows for zeroing of certain parameters.
  • Backlight Display (EA777): Enhanced visibility with a backlight display.
EA771 Front View (3x230/400V)

Figure 5: Front view of EA771 model, showing total active electric energy display.

EA777 Front View (3x127/220V)

Figure 6: Front view of EA777 model, showing LCD display with various measurement capabilities.

35mm DIN Rail Installation Example

Figure 7: Example of 35mm standard DIN rail installation in a household lighting distribution box.

EA777 First Level Accuracy Indication

Figure 8: The EA777 model offers first-level accuracy for precise measurements.

Power-off Memory Feature Demonstration

Figure 9: Power-off memory ensures data is retained even after power outages, preventing measurement errors.

4. Safety Information

Please read and understand all safety instructions before installation and operation. Failure to follow these instructions may result in electric shock, fire, or serious injury.

  • Installation and maintenance should only be performed by qualified personnel.
  • Ensure the power supply is completely disconnected before any wiring or maintenance.
  • Verify that the voltage and current ratings of the meter match your electrical system.
  • Do not operate the meter in wet or damp conditions.
  • Avoid exposing the meter to direct sunlight or extreme temperatures.
  • Use appropriate personal protective equipment (PPE) during installation.

5. Installation and Wiring

The energy meter is designed for 35mm DIN rail mounting. It can be easily installed in standard household lighting distribution boxes.

5.1. Physical Installation

  1. Ensure the main power supply is turned off at the circuit breaker.
  2. Locate a suitable 35mm DIN rail within your distribution box.
  3. Align the meter with the DIN rail and press firmly until it clicks into place.
  4. Verify that the meter is securely fastened to the rail.
EA777 Side View with DIN Rail Clip

Figure 10: Side view of EA777 showing the DIN rail mounting clip.

EA771 Side View with DIN Rail Clip

Figure 11: Side view of EA771 showing the DIN rail mounting clip.

5.2. Electrical Wiring

The meter is a three-phase four-wire type. Ensure correct phase (L1, L2, L3) and neutral (N) connections. The wiring can be configured as 'Up IN Down Out' or 'Up Out Down In'.

Wiring Direction Options (Up IN Down Out / Up Out Down In)

Figure 12: Wiring direction options for the energy meter.

EA777 Wiring Diagram (L1, L2, L3, N, RS485)

Figure 13: Detailed wiring diagram for the EA777 model, including L1, L2, L3, N connections and RS485 terminals (15, 16, 17, 18).

Wiring Terminals:

  • L1, L2, L3: Phase connections.
  • N: Neutral connection.
  • P1-, P1+: Pulse output terminals.
  • 485B, 485A: RS485 communication terminals (EA777 only).

Important: Ensure all connections are tight and correct to prevent malfunction or damage. Consult a qualified electrician if you are unsure about the wiring process.

6. Operating Instructions

After successful installation and power-up, the meter will display various parameters on its LCD screen. The EA777 model offers more detailed display options and a programming menu.

6.1. EA771 Display Navigation

The EA771 model primarily displays the total active electric energy. The display will cycle through the total kWh reading.

Video 1: Demonstration of EA771 display showing total active electric energy.

6.2. EA777 Display Navigation and Parameters

The EA777 model features a multifunctional LCD display. Use the 'SET' and 'PRESS' buttons to navigate through different parameters.

EA777 Display Parameters Flow

Figure 14: Flowchart of parameters displayed on the EA777 model, including active/reactive energy, voltage, current, power, power factor, and frequency.

Displayed Parameters (EA777):

  • Total Active Energy (kWh)
  • Positive Active Energy (kWh)
  • Reverse Active Energy (kWh)
  • Total Reactive Energy (kVarh)
  • Phase A, B, C Active Power (W)
  • Phase A, B, C Reactive Power (Var)
  • Phase A, B, C Voltage (V)
  • Phase A, B, C Current (A)
  • Phase A, B, C Power Factor (PF)
  • Frequency (Hz)
  • Communication Address (Id)
  • Constant (C)

Video 2: Demonstration of EA777 display navigation and parameter viewing.

7. Programming Menu (EA777 Only)

The EA777 model features an upgraded multifunctional version that allows setting parameters such as address, baud rate, data format, and current magnification via buttons.

EA777 Programming Menu Options

Figure 15: EA777 Programming Menu options and navigation.

To access and configure the programming menu:

  1. Press and hold the 'SET' button for 5 seconds to enter the menu.
  2. Use the 'SET' button to switch between menu items (Address, Baud Rate, Data Format, Current Magnification).
  3. Use the 'PRESS' button to increase the value of the selected parameter.
  4. Once the desired value is set, press and hold the 'SET' button to save the data and exit the menu.

Configurable Parameters:

  • Address: Range 1-247
  • Baud Rate: 2400bps, 4800bps, 9600bps (optional)
  • Data Format: N.8.1, O.8.1, E.8.1
  • Current Magnification: Range 1-9999

8. Remote Meter Reading (EA777 Only)

The EA777 model supports remote meter reading and centralized management via its RS485 communication interface.

Remote Meter Reading System Diagram

Figure 16: Diagram illustrating remote meter reading with an RS485 collector and server.

Setup for Remote Reading:

  • Connect the EA777 meters to an RS485 collector using RS485 cables.
  • The collector uploads data and receives control commands from a server.
  • Access and control the meters through computer login to the server.

Note: Each RS485 collector can typically collect data from up to 32 meters.

9. Maintenance

To ensure the longevity and accurate operation of your energy meter, follow these maintenance guidelines:

  • Cleaning: Keep the meter clean and free from dust. Use a soft, dry cloth for cleaning. Do not use abrasive cleaners or solvents.
  • Environment: Ensure the installation environment is dry and free from excessive moisture or corrosive gases.
  • Inspection: Periodically inspect the wiring connections to ensure they are secure and free from damage.
  • Avoid Impact: Protect the meter from physical impact or vibration.
  • Temperature: Operate the meter within the specified operating temperature range (-10°C to +55°C).

10. Troubleshooting

If you encounter issues with your energy meter, refer to the following common troubleshooting steps:

  • No Display/Blank Screen:
    • Check the power supply to the meter. Ensure it is correctly connected and receiving power.
    • Verify that the voltage is within the specified operating range.
  • Incorrect Readings:
    • Ensure all wiring connections (phases and neutral) are correct and secure according to the wiring diagram.
    • For EA777, check the 'Current Magnification' setting in the programming menu.
  • Communication Issues (EA777 with RS485):
    • Verify RS485 wiring (485A and 485B terminals).
    • Check the communication address and baud rate settings in the programming menu to ensure they match the collector/server configuration.
    • Ensure the RS485 cables are not damaged and are properly terminated.
  • Meter Not Recording Energy:
    • Confirm that current is flowing through the meter.
    • Check for any error codes or indicators on the display.

If the problem persists after performing these checks, please contact customer support for further assistance.

11. User Tips

  • Zeroing Function (EA777): The EA777 model supports a zeroing function for certain parameters. Refer to the 'Programming Menu' section for details on how to access and use this feature.
  • Wiring Compatibility: These meters are designed for three-phase four-wire electrical systems. If your network configuration differs (e.g., 2 phases + 1 neutral), ensure it is compatible with a 3-phase 4-wire meter or consult a qualified electrician for proper adaptation and wiring.
  • Data Retention: Both EA771 and EA777 models feature power-off memory, meaning your energy consumption data will be retained even during power outages.

12. Warranty and Support

For warranty information, technical support, or service inquiries, please contact the seller or manufacturer directly. Keep your purchase receipt or order details handy when contacting support.

Ask a question about this manual

Ask about setup, troubleshooting, compatibility, parts, safety, or missing instructions. Manuals+ will review the question and use this page’s manual context to help answer it.

After a successful submission, we securely hash the supplied account or form email before sending it to Microsoft Advertising for conversion attribution. Privacy details.