ETEK EKL13

ETEK EKL13 Residual Automatic Circuit Breaker User Manual

Model: EKL13 | Brand: ETEK

1. Introduction

This manual provides essential information for the safe and effective installation, operation, and maintenance of the ETEK EKL13 Residual Automatic Circuit Breaker (RCBO). The EKL13 is a combined residual current device (RCD) and miniature circuit breaker (MCB), designed to provide comprehensive protection against earth leakage faults, short circuits, and overcurrents in electrical installations. It is a Type A and C curve device, suitable for various applications.

ETEK RCBO A Type Circuit Breaker

Figure 1: ETEK EKL13 RCBO (A Type)

2. Safety Information

WARNING: Electrical shock hazard. Installation and maintenance should only be performed by qualified electricians in accordance with local and national electrical codes.

  • Always disconnect power at the main supply before installing or servicing the RCBO.
  • Ensure proper grounding and wiring connections.
  • Do not operate the device if it appears damaged.
  • The RCBO is designed for specific voltage and current ratings. Do not exceed these limits.
  • Regularly test the device as instructed to ensure proper functioning.
  • The housing is flame retardant, but proper installation and ventilation are still crucial.
RCBO with Flame Retardant Housing

Figure 2: Flame Retardant Housing for enhanced safety.

3. Product Overview

The ETEK EKL13 RCBO integrates multiple protection functions into a compact unit. Key components and features include:

Product parameters with labeled components: Product handle, Test Button, Product Wiring Diagram, CE certification mark

Figure 3: Key components of the EKL13 RCBO.

  • Product Handle: Used to manually switch the circuit breaker ON or OFF.
  • Test Button: For verifying the residual current protection function.
  • Product Wiring Diagram: Provides guidance for electrical connections.
  • CE Certification Mark: Indicates compliance with European safety standards.
  • Indicator Window: Visual indication of ON (green) or OFF (red) status.
  • Silver Alloy Contact Terminal Blocks: Ensure excellent conductivity and large load current capacity.
Silver Alloy Contact Terminal Blocks

Figure 4: Silver alloy contact terminal blocks for reliable connections.

The EKL13 offers:

  • Flame retardant housing
  • Compact size
  • Short circuit protection
  • Overload protection
  • Leakage protection
  • Isolation function
Icons representing Flame Retardant Housing, Compact Size, Short Circuit Protection, Overload Protection, Leakage Protection, Isolation Function. Also images of Short Circuit Hazard, Overload Hazard, Line Overload.

Figure 5: Integrated protection features and common hazards prevented by the RCBO.

4. Specifications

The ETEK EKL13 RCBO conforms to IEC/EN61009-1 standards. Detailed specifications are provided below:

Detailed product specifications table including Standard, No. of poles, Rated current, Type of protection, Rated sensitivity currents, Residual current off-time, Rated voltage, Rated frequency, Rated breaking capacity, Rated impulse voltage, Thermal-magnetic characteristic, Electrical life.

Figure 6: EKL13 RCBO Technical Specifications.

ParameterValueParameterValue
StandardIEC/EN61009-1Rated voltage (Ue)230/240V~
No. of poles1P+NRated frequency50/60Hz
Rated current6-63A (e.g., 40A model)Rated breaking capacity6,000A
Type of protectionAC, ARated impulse voltage (Uimp)4,000V
Rated sensitivity currents (IΔn)10, 30, 100, 300mAThermal-magnetic characteristicB, C
Residual current off-time under IΔn≤0.1sElectrical life4,000 Cycles

Product Dimensions:

RCBO dimensions: 81.8mm height, 36mm width (front view); 49.8mm length, 35mm height, 46.1mm width (side view)

Figure 7: EKL13 RCBO dimensions.

  • Front View: Height 81.8mm, Width 36mm
  • Side View: Length 49.8mm, Height 35mm, Width 46.1mm

5. Installation

IMPORTANT: Installation must be carried out by a qualified electrician. Ensure all power is disconnected before commencing installation.

  1. Mounting: The EKL13 RCBO is designed for DIN rail mounting. Securely attach it to the DIN rail within your electrical distribution board.
  2. Wiring: Refer to the product wiring diagram (Figure 3) for correct connections.
    • Connect the incoming live (L) and neutral (N) wires to the top terminals.
    • Connect the outgoing live (L) and neutral (N) wires to the bottom terminals.
    • Ensure all terminal screws are tightened securely to prevent loose connections and overheating.
  3. Verification: After wiring, double-check all connections for correctness and tightness.
Product wiring diagram showing connections for Live (L) and Neutral (N) lines.

Figure 8: EKL13 RCBO Wiring Diagram.

6. Operation

  1. Switching ON/OFF:
    • To switch the circuit ON, push the product handle upwards to the "ON" position. The indicator window will show green.
    • To switch the circuit OFF, push the product handle downwards to the "OFF" position. The indicator window will show red.
  2. Automatic Tripping: In the event of an earth leakage fault, short circuit, or overload, the RCBO will automatically trip to the "OFF" position, disconnecting the power supply to the protected circuit.
Indicator window showing ON (green) and OFF (red) states, with corresponding line connected/disconnected status.

Figure 9: Visual indicator for ON/OFF status.

7. Maintenance

Regular maintenance ensures the continued reliable operation of your EKL13 RCBO.

  1. Monthly Test: Press the "Test Monthly" button (marked 'T') on the front of the RCBO. The device should trip immediately, indicating that the residual current protection mechanism is functioning correctly.
    • If the device does not trip, it may be faulty and should be replaced by a qualified electrician.
    • After testing, reset the RCBO by pushing the handle to the "ON" position.
  2. Visual Inspection: Periodically inspect the RCBO for any signs of physical damage, discoloration, or loose connections.
  3. Cleaning: Keep the device clean and free from dust and debris. Use a dry, soft cloth for cleaning. Do not use liquids or abrasive cleaners.
RCBO with Test Button highlighted, indicating it should be pressed monthly.

Figure 10: Location of the "Test Monthly" button.

8. Troubleshooting

ProblemPossible CauseSolution
RCBO trips frequentlyEarth leakage fault, short circuit, or overload in the protected circuit.
  1. Disconnect all appliances from the protected circuit.
  2. Reset the RCBO. If it holds, reconnect appliances one by one to identify the faulty one.
  3. If it still trips with no load, there might be a wiring fault. Consult a qualified electrician.
RCBO does not trip when test button is pressedFaulty RCBO.Immediately replace the RCBO with a new one. Consult a qualified electrician.
RCBO cannot be switched ONPersistent fault in the circuit, or internal damage to the RCBO.
  1. Ensure there are no active faults (leakage, short, overload).
  2. If the fault is cleared and it still won't reset, the RCBO may be damaged. Replace it.

9. User Tips

Based on common inquiries and user experiences:

  • Type A vs. Type C: The EKL13 is specified as both "A Type" and "C Curve". "Type A" refers to the residual current detection capability (detects AC and pulsating DC residual currents), while "C Curve" refers to the tripping characteristic of the overcurrent protection (suitable for general purpose circuits with moderate inrush currents).
  • Professional Installation: While the device is user-friendly, electrical work can be dangerous. Always opt for professional installation to ensure safety and compliance.

10. Warranty and Support

ETEK products are manufactured to high-quality standards. For warranty information, please refer to the terms and conditions provided at the point of purchase or contact ETEK customer support.

For technical assistance or support, please contact your local ETEK distributor or visit the official ETEK website.

© 2023 ETEK. All rights reserved.

Related Documents - EKL13

Preview EATON 11/25 IL019140ZU Instruction Leaflet: RCCB and RCBO Installation Guide
Detailed installation instructions and technical specifications for EATON PL6, PL7, HN, PF6, PF7, and HNC series Residual Current Circuit Breakers (RCCBs) and Residual Current Breakers with Overcurrent Protection (RCBOs), including wiring diagrams and electrical data.
Preview ETEK Type B, B HP, B+, EV RCDs & RCBOs: Residual Current Devices
Discover ETEK's advanced AC-DC sensitive Residual Current Devices (RCDs) and Residual Current Circuit Breakers with Overcurrent Protection (RCBOs). Featuring Type B, Type B HP, Type B+, and Type EV models, these devices offer comprehensive protection against various fault currents for residential, commercial, and industrial applications.
Preview EARU Miniature Current Circuit Breaker Instruction Manual - Safety and Operation Guide
This instruction manual from EARU ELECTRIC provides essential safety information and operational guidance for Miniature Current Circuit Breakers (MCBs), including models like AFDD-63 and EAB6L, ensuring safe and optimal performance in low-voltage power distribution systems.
Preview ETEK ETL3-63 Series RCCB with Overcurrent Protection (RCBO) Usage Manual
User manual for ETEK ETL3-63, ETL3-63H, ETL3-63M, and ETL3-63MH RCCB with Overcurrent Protection (RCBO). Provides technical data, characteristics, dimensions, and circuit diagrams for installation and operation.
Preview ETEK EKR3L Series Smart RCBO: Features, Specifications, and Applications
Comprehensive overview of the ETEK EKR3L Series Smart RCBO, detailing its overload, short-circuit, and leakage protection capabilities, advanced smart features including remote control via Tuya APP and RS485, and technical specifications for electrical installations.
Preview ETEK EKR3L Series Smart RCBO: Features, Specifications & Applications
Discover the ETEK EKR3L Series Smart RCBO, offering advanced overload, short-circuit, and leakage protection with remote control via Tuya APP and RS485. Learn about its features, technical specifications, and applications in smart homes and industrial environments.

Ask a question about this manual

Ask about setup, troubleshooting, compatibility, parts, safety, or missing instructions. Manuals+ will review the question and use this page’s manual context to help answer it.