LEFOO LFM11

Contents

LEFOO LFM11 Digital Display Differential Pressure Transmitter

Instruction Manual

1. Introduction

The LEFOO LFM11 series digital display differential pressure transmitter is designed for precise measurement of very low differential pressures. It is suitable for various applications in building automation, HVAC/R industry, pressure and flow monitoring, and medical devices. This manual provides essential information for the proper installation, operation, and maintenance of your LFM11 transmitter.

Front view of the LEFOO LFM11 Digital Display Differential Pressure Transmitter showing the LCD screen and pressure ports.
Figure 1: Front view of the LFM11 Transmitter

2. Features

  • Designed for low differential pressure measurement.
  • Available in various differential pressure ranges (e.g., LFM110, LFM112, LFM116).
  • Multiple output signals: 0~5VDC, 0~10VDC, 4~20mA, and RS-485 communication.
  • Wide input voltage range: 16~30Vac/Vdc.
  • Integrated LCD backlight digital display for clear readings.
  • Automatic zero calibration upon power-on.
  • Manual zero calibration capability.
  • Robust ABS industrial plastic housing with IP65 protection.
  • Accuracy: ±1.0%FS.
  • Operating Temperature: -10°C to +60°C.
  • Storage Temperature: -10°C to +70°C.

3. Applications

The LFM11 transmitter is ideal for:

  • Heating, Ventilation, and Air Conditioning (HVAC) systems.
  • Energy Management Systems.
  • Monitoring static duct pressure.
  • Clean room pressure monitoring.
  • Indoor air pressure monitoring.
  • Air filter monitoring.
  • Over pressurization and furnace draft control.
  • Measurement of air and neutral gases.

4. Model Selection Guide

The LFM11 series offers various configurations based on pressure range, display function, and output type. Refer to the model selection diagram and table below to choose the appropriate model for your application.

Diagram showing the structure of the LFM11 model number and its corresponding features.
Figure 2: LFM11 Model Selection Example
Table detailing LFM11 model codes: first digit for pressure range, second for display, third for output type, and fourth for accuracy.
Figure 3: LFM11 Model Code Explanation

Model Code Breakdown:

Position Description Options
Base Model LFM11
1st Digit (Pressure Range) Pressure Range 6: ±100Pa
0: ±1000Pa
2: ±10000Pa
2nd Digit (Display Function) Display Type 0: With Display
N: No Display
3rd Digit (Output Type) Output Signal A: 4~20mA & 0~10VDC (Simultaneous)
B: 4~20mA (2-wire, no backlight)
C: 0~10VDC (3-wire)
D: 0~5VDC (3-wire)
E: RS-485 Communication
F: 0~10VDC & RS485
4th Digit (Accuracy Level) Accuracy C: ±1.0%FS

5. Specifications

Parameter Value
Range (LFM110) ±1000Pa (Minimum 0~+100Pa)
Range (LFM112) ±10,000Pa (Minimum 0~+1000Pa)
Range (LFM116) ±100Pa (Minimum 0~+10Pa)
Accuracy ±1.0%FS
Pressure Unit Pa, mmH2O, mbar, inWG, mmHg, daPa, KPa, hPa
Output Signal 0~5VDC / 0~10VDC / 4~20mA / RS-485
Supply Voltage (2-wire output) 16~30VAC/VDC (can use 24VDC adaptor)
Supply Voltage (Current type 2-wire) Non-polarized 12~30VDC
Supply Voltage (Voltage type 3-wire) 16~30 VAC/VDC
Supply Voltage (RS-485 4-wire) 12~30 VAC/VDC
Power Consumption ≤1.5W
Material Industrial plastic, flame retarded rating: UL94-V0
Protection Grade IP65
Display LCD display: 50 x 22.5 mm
Number Height (Display) Test value at 10 mm, unit at 5 mm
Pressure Connection Metal barb connection, Ø 6.2 mm
Cable Connection Max diameter: Ø 8 mm
Weight 140g
Response Time 0.5s, 1s, 2s, 4s
Resolution (LFM110) 1Pa, 0.1mmH2O, 0.01mbar, 0.004inWG
Resolution (LFM112) 0.007mmHg, 0.1daPa, 0.001KPa, 0.01hPa
Resolution (LFM116) 0.1Pa, 0.01mmH2O, 0.01mbar, 0.01daPa, 0.001hPa
Zero Calibration Manual with push button or automatic at starting
Media Air and neutral gases
Tolerated Overpressure (LFM110) 15KPa
Tolerated Overpressure (LFM112) 150KPa
Tolerated Overpressure (LFM116) 4.5KPa
Operating Temperature -10~+60°C
Storage Temperature -10~+70°C

6. Installation

The LFM11 transmitter is designed for easy installation. It features mounting holes on the back for secure attachment to a flat surface. Ensure the mounting location is stable and free from excessive vibration.

  • The device is fixed on a backboard using the provided mounting points.
  • Ensure adequate space around the device for proper air circulation and access to connections.
  • The IP65 protection rating ensures resistance against dust and water jets, making it suitable for various environments.
  • Connect pressure tubes to the metal barb connections (Ø 6.2 mm) on the front of the device.
Angled view of the LFM11 transmitter showing the two pressure ports and the cable gland for electrical connections.
Figure 4: Pressure Ports and Cable Gland
Rear view of the LFM11 transmitter showing the four mounting screw holes and the cable gland entry point.
Figure 5: Rear view with Mounting Points

7. Wiring

Proper wiring is crucial for the correct operation of the LFM11 transmitter. Refer to the diagram below and the specifications for your specific model's output type.

Wiring diagram for the LFM11 transmitter, showing terminals for V+, V-, OUT, and RS485 A/B connections.
Figure 6: LFM11 Wiring Diagram

Wiring Guidelines:

  • Power Supply: Connect the power supply (16~30Vac/Vdc or 12~30VDC depending on model) to the designated terminals (e.g., V+ and V-). For current type 2-wire output, the input power is non-polarized.
  • Analog Output (0-5VDC / 0-10VDC / 4-20mA): Connect the output signal wire(s) to the 'OUT' terminal and the common/ground. Voltage type outputs typically use 3 wires, while current type can be 2-wire.
  • Digital Output (RS-485): Connect the RS-485 A and B lines to the corresponding terminals. This is a 4-wire connection.
  • Ensure all connections are secure and properly insulated.
  • Use appropriate cable diameter (max Ø 8 mm) for the cable gland.

8. Operation

Power On and Initial Display:

Upon applying power, the transmitter will perform an automatic zero calibration. The LCD will then display the measured differential pressure in the configured unit.

Reading the Display:

The LCD display (50 x 22.5 mm) shows the test value with a height of 10 mm and the unit (e.g., Pa) with a height of 5 mm for clear visibility.

Zero Calibration:

  • Automatic Zero Calibration: This occurs automatically when the device is powered on. Ensure that both pressure ports are at the same pressure (e.g., open to atmosphere) during power-up for accurate auto-calibration.
  • Manual Zero Calibration: The device supports manual zero calibration via a push button. Consult the device's physical interface for the exact location and procedure of the zero calibration button. This is useful for re-calibrating in the field if needed.

Pressure Unit Selection:

The LFM11 supports various pressure units including Pa, mmH2O, mbar, inWG, mmHg, daPa, KPa, and hPa. The specific method for selecting or configuring the display unit may vary by model. Refer to the device's interface or advanced configuration options if available.

9. Maintenance

The LEFOO LFM11 differential pressure transmitter is designed for reliable operation with minimal maintenance. Adhere to the following guidelines:

  • Cleaning: Keep the exterior of the device clean. Use a soft, damp cloth for cleaning. Do not use abrasive cleaners or solvents.
  • Environment: Ensure the operating environment remains within the specified temperature range (-10°C to +60°C) and that the media being measured consists of air or neutral gases.
  • Pressure Connections: Periodically check the pressure tube connections for any leaks or blockages.
  • Wiring: Inspect wiring connections for any signs of wear or damage.
  • IP65 Protection: While the device is IP65 rated, avoid prolonged exposure to harsh conditions or direct high-pressure water jets to maximize its lifespan.

10. Troubleshooting

If you encounter issues with your LFM11 transmitter, consider the following common troubleshooting steps:

Problem Possible Cause Solution
No display/No power Incorrect power supply voltage or wiring; power failure. Verify power supply voltage (16~30Vac/Vdc or 12~30VDC) and wiring connections. Check power source.
Inaccurate readings Incorrect zero calibration; pressure port blockage; sensor damage. Perform manual zero calibration. Check pressure lines for obstructions. If problem persists, contact support.
No output signal Incorrect wiring for output type; receiver device issue. Check output wiring against the diagram (Figure 6) and specifications. Verify the receiving device is correctly configured.
Display shows 'OVER' or 'UNDER' Pressure exceeds or falls below the configured range. Ensure the measured pressure is within the transmitter's specified range. Check for overpressure conditions.

11. Warranty and Support