GEYA SUL180N

Contents

GEYA SUL180N Mechanical Timer Switch Instruction Manual

Model: SUL180N

1. Introduction

The GEYA SUL180N Mechanical Timer Switch is designed to control any electrical installation through daily programs. This manual provides essential information for safe installation, operation, maintenance, and troubleshooting of your timer switch.

Front view of the GEYA SUL180N Mechanical Timer Switch
Figure 1: GEYA SUL180N Mechanical Timer Switch

2. Important Safety Warnings

⚠ Caution: Electrical devices must be installed and assembled by a qualified and authorized installer. All electrical connections must comply with appropriate safety standards. Ensure the product is used with a 16A circuit breaker upstream.

  • Install the timer in switchboard cabinets made of 35 mm symmetric sections, in accordance with EN 50022.
  • The timer is internally protected against interference by a safety device. However, strong electromagnetic fields may affect its operation.
  • To avoid interference, do not install the device near inductive loads (motors, transformers, contactors, etc.).
  • A separate power line is recommended, equipped with a network filter if necessary.
  • Inductive loads should be equipped with interference suppressors (varistor, RC filter).
  • If used with other devices, verify that no parasitic disturbances will be caused.

3. Installation

The GEYA SUL180N is designed for DIN rail mounting. Follow the diagrams and instructions below for proper installation.

3.1 Dimensions

Dimensions of the GEYA SUL180N Timer Switch, showing 90mm height and 18mm width for the main unit, and 68mm depth.
Figure 2: Dimensions (mm) of the SUL180N Timer Switch. The main unit is 90mm high and 18mm wide. The side view shows a depth of 68mm.

3.2 Wiring Connection

Ensure all wiring is performed by a qualified electrician following local electrical codes.

Wiring connection diagram for the SUL180N Timer Switch, showing upper and bottom wiring installation steps.
Figure 3: Wiring Connection Diagram. This diagram illustrates how to connect the timer switch, including details for upper and bottom wiring installations.
Various wiring diagrams for the GEYA SUL180N Timer Switch, showing connections with MCB and load for different configurations.
Figure 4: Detailed Wiring Diagrams. Includes single-phase and three-phase wiring examples with MCB and load connections.

When the timer is used for a load exceeding its rated capacity, it is essential to combine the timer with one or more magnetic contactors, selected according to the specific load requirements.

4. Operation

4.1 Setting Daily Programs

To set the daily program, move the pins on the programming dial.

  • Move pins to the right (Off) for periods when the connected device should be off.
  • Move pins to the left (On) for periods when the connected device should be on.

The contact 1-2 will close during the "On" times.

Diagram showing how to move pins on the timer dial for ON/OFF settings.
Figure 5: Pin Movement for ON/OFF Settings (refer to the small diagrams on the right side of the image for visual guidance).

4.2 Hour Update

Turn the main dial until the index points to the current time.

4.3 Manual Mode

The timer features a manual operating switch with two positions:

  • ○ (Automatic functioning): The timer operates according to the set daily program.
  • I (Permanent connection): The connected device remains continuously on, overriding the daily program.
Diagram showing the manual mode switch with Automatic and Permanent connection settings.
Figure 6: Manual Mode Switch (refer to the small diagrams on the right side of the image for visual guidance).

5. Technical Specifications

FeatureSpecification
Model NumberSUL180N
TheoryMechanical
TypeMini
UseTimer Switch
Product NameSUL180N 24hour Programm Timer Switch Mechanical
FunctionTime Control Switch, Automatic Cycle
Ampere16A
Rated Working Voltage85V~250VAC
Rated Frequency45~60Hz
DriveQuartz-controlled stepper motor
Power Reserve100 hours
Type of DialDaily: 96 pins
Minimum Setting Unit15 Minutes
Functioning Temperature-10°C to +50°C
Protection CategoryIP 20 as per IEC/EN 60529
Protection ClassII as per IEC/EN60335 under Correct assembling conditions
InstallationDin Rail
Battery IncludedYes

5.1 Certifications

GEYA products are certified to required industry standards, including CE, CB, SAA, SEMKO, TUV, and Rosh.

Image showing various international certifications like CE, CB, SAA, SEMKO, TUV, and Rosh for GEYA products.
Figure 7: Product Certifications

6. User Tips

  • Initial Charge: Before first use, charge the timer for at least 2 hours to ensure normal operation, especially if it has been stored for a while.
  • Professional Installation: Always have the timer installed by a qualified electrician to ensure safety and compliance with electrical standards.
  • Circuit Protection: It is recommended to use the timer in conjunction with a 16A circuit breaker upstream for added protection.
  • Load Management: If connecting loads that exceed the timer's rated capacity, ensure to use appropriate magnetic contactors to handle the excess load.
  • Quality Assurance: GEYA products are generally regarded for good quality and value.

7. Maintenance

The SUL180N timer switch contains a non-removable battery for power reserve. This battery must not be disposed of as urban waste. Please ensure proper recycling to protect the environment. No other user-serviceable parts are inside.

8. Troubleshooting

  • Timer Not Functioning: If the timer does not work normally upon initial setup or after a long period of inactivity, ensure it has been charged for at least 2 hours.
  • Unexpected Operation: If the timer's operation is erratic or not as programmed, check for strong electromagnetic fields nearby. Relocate the timer or the inductive loads if possible. Ensure inductive loads are equipped with interference suppressors.
  • Interference with Other Devices: If the timer causes or experiences parasitic disturbances when combined with other devices, verify the compatibility and proper installation of all components in the electrical group.

9. Warranty and Support

For warranty claims, technical support, or further assistance, please contact your retailer or the manufacturer directly. Refer to the product packaging or official GEYA website for contact information.

10. Environmental Disposal

This product contains a non-removable battery and should not be disposed of with general household waste. Please follow local regulations for the recycling of electronic products and batteries to protect the environment.

Waste electrical and electronic equipment (WEEE) symbol indicating separate collection of electrical and electronic equipment.
Figure 8: WEEE Symbol (refer to the symbol on the product image for visual guidance)

11. GEYA Company Overview

Watch this video for an overview of GEYA's manufacturing process and commitment to quality.

Video: GEYA Company Introduction and Manufacturing Process

12. Additional Resources

A detailed user manual in PDF format is also available for download. You can find it at the following link: GEYA SUL180N User Manual (PDF).

Ask a question about this manual

Ask about setup, troubleshooting, compatibility, parts, safety, or missing instructions. Manuals+ will review the question and use this page’s manual context to help answer it.

After a successful submission, we securely hash the supplied account or form email before sending it to Microsoft Advertising for conversion attribution. Privacy details.