1. Introduction

This manual provides essential information for the installation, operation, and maintenance of the Kinco GL100 and GL100E 10-inch Human Machine Interface (HMI). The Kinco HMI is designed for industrial control applications, offering a user-friendly interface for monitoring and controlling various processes.

The GL100 and GL100E models are part of the Kinco Green Series, known for their robust design and cost-effectiveness. Key features include a non-hollow mask for enhanced protection against oil pollution and an ultra-thin body design.

Note on Models:

  • GL100: This model does not include an Ethernet interface. It is a direct replacement for the discontinued MT4532T model, sharing the same installation hole size.
  • GL100E: This model features a 10/100M adaptable Ethernet interface. It is a direct replacement for the discontinued MT4532TE model, sharing the same installation hole size.

2. Setup

2.1 Physical Overview

The Kinco GL100/GL100E HMI features a 10-inch display and various communication ports on its rear panel.

Rear view of Kinco GL100E HMI showing DC24V, COM0/COM2, USB Slave, USB Host, and Ethernet ports.
Rear view of Kinco GL100E HMI, highlighting the various connection ports.
Rear view of Kinco GL100 HMI showing DC24V, COM0/COM2, USB Slave, and USB Host ports.
Rear view of Kinco GL100 HMI, showing connection ports (without Ethernet).

2.2 Mechanical Dimensions and Cutout Size

Ensure proper space and cutout dimensions for installation. The overall dimensions and required cutout size are critical for secure mounting.

Mechanical dimensions and cutout size diagram for Kinco GL100 and GL100E HMIs.
Mechanical dimensions (Unit: mm) and cutout size for GL100/GL100E.

2.3 Wiring and Connections

The HMI requires a DC24V power supply. Connect the power, ground (GND), and functional ground (FG) terminals as indicated on the rear panel. The HMI supports various communication interfaces:

  • DC24V GND FG: Power input terminals.
  • COM0/COM2: 9-pin D-SUB connector for serial communication.
  • USB SLAVE: For connecting to a PC for program download.
  • USB HOST: For connecting USB devices (e.g., USB flash drives).
  • Ethernet (GL100E only): 10/100M adaptable Ethernet interface for network communication.

COM0/COM2 Pin Assignment:

Pin assignment table for COM0/COM2 ports on Kinco GL/GL100/GL100E HMIs.
Pin assignment of the 9-pin male, D-SUB, COM0/COM2 connector.

Note: COM0/COM2 supports RS232/485/422 communication functions. COM2 specifically supports RS232 communication function.

3. Operating Instructions

3.1 User Interface

The Kinco HMI features a touchscreen display for intuitive interaction. The interface allows users to monitor processes, input data, and control connected equipment.

Kinco HMI touchscreen interface with a hand interacting.
Interacting with the Kinco HMI touchscreen.

3.2 Language Support

The HMI supports multiple languages, including English, Deutsch, Turkish, Chinese, and Korean.

3.3 Software and Programming

The Kinco HMI uses Kinco DTools V3.3 and above for configuration and programming. Programming of MT4000 can be used for Green series HMI after edited by DTools.

For related file downloads, including software and manuals, please visit the official Kinco website: http://en.kinco.cn/download/download.html

4. Maintenance

4.1 Environmental Conditions

To ensure optimal performance and longevity, operate the HMI within the specified environmental conditions:

  • Operating Ambient Temperature: 0°C to 50°C
  • Operating Ambient Humidity: 10% to 90% non-condensing
  • Storage Ambient Temperature: -20°C to 60°C
  • Storage Ambient Humidity: 10% to 90% non-condensing
  • Vibration: 10~500Hz, 30m/s², X, Y, Z direction/hour
  • Cooling Mode: Natural air cooling

4.2 Cleaning

The HMI features a non-hollow mask, which is effective against oil pollution. For cleaning, use a soft, damp cloth. Avoid abrasive cleaners or solvents that could damage the screen or casing.

5. Troubleshooting

5.1 PLC Communication Issues

Kinco HMI supports standard universal protocols such as Codesys, Omron Tag Protocol, CANopen, and Modbus. This allows communication with over 300 PLC manufacturers, including Siemens, Mitsubishi, Keyence, AB, and Delta.

However, communication connection methods may vary between different PLC manufacturers and Kinco HMI. If you encounter communication problems, it is recommended to:

  1. Download the free Kinco software.
  2. Within the software, select your specific HMI model and then choose the PLC family you intend to connect with to verify compatibility and connection settings.

5.2 Discontinued Products

Please note that some older models, such as MT4532T and MT4532TE, have been discontinued. The GL100 and GL100E models serve as direct replacements with the same installation hole sizes.

Table listing alternative and discontinued Kinco HMI products.
Description of alternative and discontinued products.

6. Specifications

The following table details the technical specifications for the Kinco GL100 and GL100E Human Machine Interfaces:

Detailed specifications table for Kinco GL100 and GL100E HMIs.
Kinco GL100 and GL100E Technical Specifications.
Kinco GL100 / GL100E Specifications
CategoryParameterGL100GL100E
Performance SpecificationsDisplay size10.1" TFT
Display area222.72mm(W) * 125.28mm(H)
Resolution1024 * 600 pixels
Display color16.7M true color
Display angle of view70/70/60/70 (left/right/up/down)
Contrast ratio500:1
BacklightLED
Brightness460cd/m²
Backlight lifeMore than 30000 hours
Touch panel4 line precision resistance network (surface hardness 4H)
CPUARM RISC 328K 800MHz
Storage128MB NAND Flash Memory + 128MB DDR3 Memory
RTCBuilt-in
Extensible memory1 USB Host
Print portUSB Host/Serial port
EthernetNone10/100M self-adaption
Program downloadUSB Slave (Micro USB)/U diskUSB Slave (Micro USB)/U disk/Ethernet
Communication portCOM0:RS232/RS485/RS422
COM2:RS232
Electrical SpecificationsInput power supplyDC10V ~ DC28V
Rated power6W @24V DC
Allowable loss of power<3ms
Insulation resistanceOver 50MΩ@500V DC
Hi-pot test500 VAC 1 minute
Structure SpecificationsPCBNone of spraying
Shell materialEngineering plastic
Shape size280*193*36 mm
Cutout size261*180 mm
Weight0.9kg
Environmental SpecificationsOperating ambient temperature0°C ~ 50°C
Operating ambient humidity10% to 90% non-condensing
Storage ambient temperature-20°C ~ 60°C
Storage ambient humidity10% to 90% non-condensing
Sine vibration test10~500Hz, 30m/s², X, Y, Z direction/hour
Cooling modeNatural air cooling
Product CertificationPanel protection gradeConforming to IP65 certification (4208-93)
CE authenticationEN61000-6-4:2007+A1:2011, EN61000-6-2:2005
SoftwareConfiguration softwareKinco DTools V3.3 and above

7. User Tips

  • When connecting to a PLC, always refer to the Kinco software for specific communication settings and protocols to ensure proper integration.
  • For models without Ethernet (GL100), use the USB Slave port for program downloads from your PC.
  • The non-hollow mask design helps protect against oil, making it suitable for environments where oil pollution is a concern.

8. Warranty and Support

For technical support, software downloads, and additional documentation, please visit the official Kinco website: http://en.kinco.cn/download/download.html

For product inquiries or assistance, you may also contact the seller, Hengnais (Guangzhou) Trading Co., Ltd. They specialize in automation products and are designated agents for Kinco.

All products are guaranteed to be brand new. For any questions, please allow up to 24 hours for a response.

Related Documents - GL100 GL100E

Preview Kinco MT070/MT070E HMI Installation Instructions
This document provides installation instructions for the Kinco MT070 and MT070E HMI devices, covering environmental requirements, power specifications, external interfaces, and after-sales service information.
Preview Kinco MT100/MT100E HMI Installation Instructions
This document provides installation instructions for the Kinco MT100/MT100E HMI, covering environmental requirements, power specifications, external interfaces, and after-sales service information.
Preview Kinco GL043/GL043E HMI Installation Instructions
Comprehensive installation guide for Kinco GL043 and GL043E Human Machine Interface (HMI) devices, covering environmental and power requirements, external interfaces, and mounting procedures.
Preview Kinco GH043/GH043E HMI Installation Guide
This document provides installation instructions and technical specifications for the Kinco GH043 and GH043E Human-Machine Interface (HMI) units, covering environmental requirements, power specifications, installation procedures, and external interface details.
Preview Kinco GT070E/GT070E-4G/GT070E-WiFi HMI Installation Instructions
Installation guide for Kinco GT070E, GT070E-4G, and GT070E-WiFi Human Machine Interface (HMI) devices, covering environmental requirements, power, and external interfaces.
Preview Kinco FD Series Servo User Manual - Installation, Operation, and Troubleshooting
Comprehensive user manual for Kinco FD Series Servo Drivers and Motors. Covers product details, installation, configuration, operation modes (Pulse, Speed, Torque, Homing), software (KincoServo), communication (RS232, RS485, CANopen), parameter settings, performance tuning, alarms, and troubleshooting for industrial automation.