PowMr 2400W Hybrid Solar Inverter User Manual

Model: PS-3K-110V | Brand: PowMr

1. Introduction

This manual describes the assembly, installation, operation, and troubleshooting of the PowMr PS-3K-110V Hybrid Solar Inverter. Please read this manual carefully before installation and operation. Keep this manual for future reference.

1.1. Product Overview

The PowMr PS-3K-110V is a multi-function inverter/charger, combining the functionalities of an inverter, solar charger, and battery charger to provide uninterrupted power support in a compact size. Its comprehensive LCD display allows for user-configurable and easily accessible button operation, enabling adjustments for battery charging current, AC/solar charger priority, and acceptable input voltage based on various applications.

PowMr 2400W Hybrid Solar Inverter front view
Front view of the PowMr 2400W Hybrid Solar Inverter.

1.2. Key Features

  • Pure sine wave inverter.
  • Configurable input voltage range for home appliances and personal computers via LCD setting.
  • Configurable battery charging current based on applications via LCD setting.
  • Configurable AC/Solar Charger priority via LCD setting.
  • Compatible with mains voltage or generator power.
  • Auto restart while AC is recovering.
  • Overload/Over temperature/short circuit protection.
  • Smart battery charger design for optimized battery performance.
  • Built-in PWM solar charge controller.
  • Cold start function.

1.3. Basic System Architecture

The inverter/charger can power various appliances in home or office environments, including motor-type appliances such as tube lights, fans, refrigerators, and air conditioners. A complete running system typically includes the inverter/charger, a generator or utility power source, and optional PV modules.

Hybrid Power System Diagram
Diagram illustrating a typical hybrid power system setup with solar, utility/generator, battery, and home appliances.

The diagram shows how solar power (optional), a generator, or utility power can feed into the inverter, which then charges a 24V lithium or lead-acid battery and supplies single-phase 110V output to home appliances.

2. Safety Instructions

WARNING: This chapter contains important safety and operating instructions. Read and keep this manual for future reference.

  1. Before using the unit, read all instructions and cautionary markings on the unit, the batteries, and all appropriate sections of this manual.
  2. CAUTION: To reduce the risk of injury, charge only deep-cycle lead-acid type rechargeable batteries. Other types of batteries may burst, causing personal injury and damage.
  3. Do not disassemble the unit. Take it to a qualified service center when service or repair is required. Incorrect re-assembly may result in a risk of electric shock or fire.
  4. To reduce the risk of electric shock, disconnect all wirings before attempting any maintenance or cleaning. Turning off the unit will not reduce this risk.
  5. CAUTION: Only qualified personnel can install this device with a battery.
  6. NEVER charge a frozen battery.
  7. For optimum operation of this inverter/charger, please follow the required specifications to select appropriate cable size. It is very important to correctly operate this inverter/charger.
  8. Be very cautious when working with metal tools on or around batteries. A potential risk exists to drop a tool to spark or short circuit batteries or other electrical parts and could cause an explosion.
  9. Please strictly follow the installation procedure when you want to disconnect AC or DC terminals. Please refer to the INSTALLATION section of this manual for details.
  10. Fuses (4 pieces of 40A, 32VDC for 1KVA/2KVA, 6 pieces of 40A, 32VDC for 3KVA) are provided as over-current protection for the battery supply.
  11. GROUNDING INSTRUCTIONS: This inverter/charger should be connected to a permanent grounded wiring system. Be sure to comply with local requirements and regulations to install this inverter.
  12. NEVER cause AC output and DC input short circuits. Do NOT connect to the mains when DC input short circuits.
  13. Warning!! Only qualified service persons are able to service this device. If errors still persist after following the troubleshooting table, please send this inverter/charger back to a local dealer or service center for maintenance.

3. Setup (Installation)

3.1. Unpacking and Inspection

Before installation, inspect the unit to ensure no damage occurred during shipping. The package should contain:

  • The unit x 1
  • User manual x 1 (Refer to the PDF manual for full details: User Manual PDF)
  • Communication cable x 1
  • Software CD x 1

3.2. Preparation

Before connecting any wiring, remove the bottom cover by unscrewing two screws.

3.3. Mounting the Unit

Consider the following points when selecting an installation location:

  • Do not mount the inverter on flammable construction materials.
  • Mount on a solid surface.
  • Install at eye level for easy LCD display reading.
  • Allow a clearance of approximately 20 cm to the sides and 50 cm above and below for proper air circulation and heat dissipation.
  • The ambient temperature should be between 0°C and 55°C for optimal operation.
  • The recommended installation position is vertically on the wall.
  • Ensure enough space for removing wires and adequate heat dissipation.

SUITABLE FOR MOUNTING ON CONCRETE OR OTHER NON-COMBUSTIBLE SURFACE ONLY.

3.4. Battery Connection

CAUTION: For safety and compliance, install a separate DC over-current protector or disconnect device between the battery and inverter. Refer to the table below for required fuse or breaker size.

WARNING: All wiring must be performed by qualified personnel. Use appropriate cable for battery connection to reduce risk of injury.

Recommended Battery Cable and Terminal Size
ModelTypical AmperageBattery CapacityWire SizeCable mm²Ring Terminal D (mm)Ring Terminal L (mm)Torque Value
1KVA/2KVA66A100AH1*6AWG146.429.22~3 Nm
2*10AWG86.423.8
3KVA100A100AH1*4AWG226.433.22~3 Nm
200AH2*8AWG146.429.2

Steps for Battery Connection:

  1. Assemble battery ring terminals based on the recommended cable and terminal size.
  2. The 1KVA model supports a 12VDC system, while 2KVA/3KVA models support a 24VDC system. Connect all battery packs as shown in the manual. It is suggested to connect at least a 100Ah capacity battery for 1-3KVA models.
  3. Insert the ring terminal of the battery cable flatly into the battery connector of the inverter and ensure the bolts are tightened with a torque of 2-3 Nm. Verify polarity at both the battery and the inverter/charger is correctly connected, and ring terminals are tightly screwed to the battery terminals.

WARNING: Shock Hazard! Installation must be performed with care due to high battery voltage in series.

CAUTION!! Do not place anything between the flat part of the inverter terminal and the ring terminal. Otherwise, overheating may occur.

CAUTION!! Do not apply anti-oxidant substance on the terminals before terminals are connected tightly.

CAUTION!! Before making the final DC connection or closing the DC breaker/disconnector, ensure positive (+) is connected to positive (+) and negative (-) is connected to negative (-).

Note: Only use sealed lead-acid batteries or sealed GEL/AGM lead-acid batteries.

3.5. AC Input/Output Connection

CAUTION!! Before connecting to an AC input power source, install a separate AC breaker between the inverter and the AC input power source. This ensures the inverter can be securely disconnected during maintenance and fully protected from overcurrent of AC input. Recommended AC breaker specs: 15A for 1KVA, 30A for 2KVA, 45A for 3KVA.

CAUTION!! There are two terminal blocks with "IN" and "OUT" markings. Do NOT mis-connect input and output connectors.

WARNING! All wiring must be performed by qualified personnel. Use appropriate cable for AC input connection to reduce risk of injury.

Suggested Cable Requirement for AC Wires
ModelGaugeTorque Value
1KVA14 AWG0.5~0.6 Nm
2KVA12 AWG0.8~1.0 Nm
3KVA10 AWG1.2~1.6 Nm

Steps for AC Input/Output Connection:

  1. Before making AC input/output connections, ensure the DC protector or disconnector is open.
  2. Remove 10mm of insulation sleeve for six conductors. Shorten phase L and neutral conductor N by 3mm.
  3. Insert AC input wires according to the indicated polarities on the terminal block and tighten the terminal screws. Ensure the PE protective conductor (ground) is connected first.
  4. Then, insert AC output wires according to the indicated polarities on the terminal block and tighten terminal screws. Ensure the PE protective conductor (ground) is connected first.
  5. Make sure all wires are securely connected.

CAUTION: Important! Ensure AC wires are connected with correct polarity. If L and N wires are connected reversely, it may cause utility short-circuiting when these inverters are operating in parallel.

CAUTION: Appliances like air conditioners require 2-3 minutes to restart to balance refrigerant gas. If a power shortage occurs and recovers quickly, it can damage connected appliances. Check the manufacturer's guidelines for time-delay functions before installation.

3.6. PV Connection (Only for models with solar charger)

CAUTION: Before connecting to PV modules, install a separate DC circuit breaker between the inverter and PV modules.

WARNING! All wiring must be performed by qualified personnel. Use appropriate cable for PV module connection to reduce risk of injury.

Suggested Cable Requirement for PV Wires
Typical AmperageGaugeTorque Value
50A8 AWG1.4~1.6 Nm

PV Module Selection:

When selecting PV modules, consider the following:

  1. The Open Circuit Voltage (Voc) of PV modules must not exceed the maximum PV array open circuit voltage of the inverter.
  2. The Max. Power Voltage (Vmpp) of PV modules should be close to the best Vmp of the inverter or within the Vmp range for optimal performance. If a single PV module cannot meet this requirement, multiple PV modules in series connection may be necessary.
Inverter Model Specifications for PV Connection
Inverter ModelSolar Charger Charging CurrentSystem DC VoltageOperating Voltage RangeMax. PV Array Open Circuit Voltage
1KVA50Amp12Vdc15~18Vdc40Vdc
2KVA/3KVA50Amp24Vdc30~32Vdc80Vdc

Steps for PV Module Connection:

  1. Remove 10mm of insulation sleeve for positive and negative conductors.
  2. Check the correct polarity of the connection cable from PV modules and PV input connectors. Connect the positive pole (+) of the connection cable to the positive pole (+) of the PV input connector. Connect the negative pole (-) of the connection cable to the negative pole (-) of the PV input connector.
  3. Make sure the wires are securely connected.
Rear panel connections of the inverter
Rear panel connections: 1. AC Input, 2. AC Output, 3. Circuit Breaker, 4. Safety (Earth) ground, 5. Battery positive, 6. Battery negative, 7. PV Input, 8. ON/OFF, 9. RS232 communication port.

3.7. Final Assembly

After connecting all wirings, replace the bottom cover by screwing the two screws back into place.

3.8. Communication Connection

Use the supplied communication cable to connect the inverter to a PC. Insert the bundled CD into the computer and follow the on-screen instructions to install the monitoring software. For detailed software operation, refer to the software's user manual on the CD.

3.9. Dry Contact Signal

A dry contact (3A/250VAC) is available on the rear panel. It can be used to deliver a signal to an external device when the battery voltage reaches a warning level.

Dry Contact Signal Conditions
Unit StatusConditionNC & CNO & C
Power OffUnit is off and no output is powered.CloseOpen
Output is powered from Utility.CloseOpen
Battery voltage < Low DC warning voltageOpenClose
Power OnOutput is powered from Battery or Solar (Program 01 set as Utility)Battery voltage > Setting value in Program 13 or battery charging reaches floating stageCloseOpen
Output is powered from Battery or Solar (Program 01 set as SBU or Solar first)Battery voltage < Setting value in Program 12OpenClose
Battery voltage > Setting value in Program 13 or battery charging reaches floating stageCloseOpen

4. Operating the Inverter

4.1. Power ON/OFF

Once the unit is properly installed and the batteries are connected, simply press the On/Off switch (located on the bottom of the case) to turn on the unit.

4.2. Operation and Display Panel

The front panel features an LCD display, three indicators (Status, Charging, Fault), and four function buttons (ESC, UP, DOWN, ENTER) to show operating status and input/output power information.

Inverter LCD display and control buttons
LCD display and function buttons for inverter control.
LED Indicator Messages
LED IndicatorColorMessages
AC/INVGreenSolid On: Output is powered by utility in Line mode.
Flashing: Output is powered by battery or PV in battery mode.
CHGGreenSolid On: Battery is fully charged.
Flashing: Battery is charging.
FAULTRedSolid On: Fault occurs in the inverter.
Flashing: Warning condition occurs in the inverter.
Function Keys
Function KeyDescription
ESCTo exit setting mode
UPTo go to previous selection
DOWNTo go to next selection
ENTERTo confirm the selection in setting mode or enter setting mode

4.3. LCD Display Icons

The LCD displays various icons to indicate the inverter's status and information. These include input source information (AC, PV, INPUTBATT), configuration program and fault information, output information (OUTPUTBATTLOAD), and battery information (CHARGING).

For a detailed explanation of each icon and its meaning, please refer to pages 15-16 of the full user manual PDF.

4.4. LCD Setting

To enter setting mode, press and hold the ENTER button for 3 seconds. Use the UP or DOWN buttons to select programs, and ENTER to confirm or ESC to exit. Key settings include:

  • Program 01: Output source priority (Solar first, Utility first, SBU priority)
  • Program 02: Maximum charging current (10A, 20A, 30A, 40A, 50A, 60A)
  • Program 03: AC input voltage range (Appliances, UPS)
  • Program 04: Power saving mode enable/disable
  • Program 05: Battery type (AGM, Flooded)
  • Program 06: Auto restart when overload occurs
  • Program 07: Auto restart when over temperature occurs
  • Program 09: Output frequency (50Hz, 60Hz)
  • Program 11: Maximum utility charging current
  • Program 12: Setting voltage point back to utility source
  • Program 13: Setting voltage point back to battery mode
  • Program 16: Charger source priority (Solar first, Utility first, Solar and Utility, Only Solar)
  • Program 18: Alarm control (Alarm on, Alarm off)
  • Program 19: Auto return to default display screen (Return to default, Stay at latest screen)
  • Program 20: Backlight control (Backlight on, Backlight off)
  • Program 22: Beeps while primary source is interrupted (Alarm on, Alarm off)
  • Program 23: Overload bypass (Bypass disable, Bypass enable)
  • Program 25: Record Fault code (Record enable, Record disable)
  • Program 26: Bulk charging voltage (C.V voltage)
  • Program 27: Floating charging voltage
  • Program 29: Low DC cut-off voltage
  • Program 30: Battery equalization (Enable, Disable)
  • Program 31: Battery equalization voltage
  • Program 33: Battery equalized time
  • Program 34: Battery equalized timeout
  • Program 35: Equalization interval
  • Program 36: Equalization activated immediately

For detailed values and options for each program, refer to pages 17-23 of the full user manual PDF.

4.5. Operating Mode Description

The inverter operates in several modes:

  • Standby Mode / Power Saving Mode: In standby, the inverter is off but can charge the battery without AC output. Power saving mode turns off inverter output if the connected load is very low.
  • Fault Mode: Occurs due to internal circuit errors or external reasons like over-temperature or output short circuits.
  • Line Mode: The unit provides output power from the mains and charges the battery.
  • Battery Mode: The unit provides output power from the battery and/or PV power.

For detailed LCD display behavior in each mode, refer to pages 26-27 of the full user manual PDF.

4.6. Battery Equalization

Battery equalization is a function added to the charge controller to reverse negative chemical effects like stratification and remove sulfate crystals, which can reduce battery capacity. It is recommended to equalize batteries periodically.

To apply equalization:

  1. Enable the battery equalization function in LCD setting program 30.
  2. Then, either set the equalization interval in program 35 or activate equalization immediately in program 36.

The equalization process involves a bulk charging stage, absorption stage, and float stage, with specific voltage and time parameters. Refer to pages 27-28 of the full user manual PDF for detailed diagrams and explanations.

5. Troubleshooting

This section provides solutions for common problems encountered with the inverter. If issues persist after following these steps, contact a qualified service person or the service center.

Troubleshooting Guide
ProblemLCD/LED/Buzzer IndicationExplanation / Possible CauseWhat to Do
Unit shuts down automatically during startup process.LCD/LEDs and buzzer active for 3 seconds then off.Battery voltage is too low (<1.91V/Cell)1. Re-charge battery.
2. Replace battery.
No response after power on.No indication.1. Battery voltage too low (<1.4V/Cell).
2. Battery polarity reversed.
1. Check battery/wiring.
2. Re-charge battery.
3. Replace battery.
Input voltage displayed as 0 on LCD, green LED flashing.Input protector tripped.Check AC breaker and wiring.
Mains exist but unit works in battery mode.Green LED flashing.Insufficient quality of AC power (Shore or Generator).1. Check AC wires.
2. Check generator/input voltage range setting.
Green LED flashing."Solar First" set as priority of output source.Change output source priority to Utility first.
When unit is turned on, internal relay switches on and off repeatedly.LCD display and LEDs flashing.Battery is disconnected.Check if battery wires are connected.
Buzzer beeps continuously and red LED is on.Fault code 07Overload error. Inverter overloaded 110% and time is up.Reduce connected load.
Fault code 05Output short circuited.Check wiring and remove abnormal load.
Fault code 02Internal converter component temperature over 120°C (1-3KVA models) or inverter component over 100°C.Check air flow and ambient temperature.
Fault code 03Battery is over-charged or battery voltage too high.Return to repair center or check battery specs.
Fault code 01Fan fault.Replace the fan.
Fault code 06Output abnormal (Inverter voltage below 100Vac or higher than 135Vac).1. Reduce connected load.
2. Return to repair center.
Fault code 08/09Internal components failed.Return to repair center.

5.1. Warning Indicator

The inverter provides warning indicators for various conditions:

Warning Indicator Guide
Warning CodeWarning EventAudible AlarmIcon Flashing
01Fan is locked when inverter is on.Beep three times every second01 icon
03Battery is over-chargedBeep once every second03 icon
04Low batteryBeep once every second04 icon
07OverloadBeep once every 0.5 second07 icon
10Output power deratingBeep twice every 3 seconds10 icon

6. Specifications

The PowMr PS-3K-110V Hybrid Solar Inverter has detailed technical specifications for various operating modes and general characteristics.

6.1. Line Mode Specifications

Table 1: Line Mode Specifications
Inverter Model1KVA2KVA3KVA
Input Voltage WaveformSinusoidal (utility or generator)
Nominal Input Voltage120Vac
Low Loss Voltage95 Vac±7V (UPS); 65 Vac±7V (Appliances)
Low Loss Return Voltage100Vac±7V (UPS); 70Vac±7V (Appliances)
High Loss Voltage140Vac±7V
High Loss Return Voltage135Vac±7V
Max AC Input Voltage150 Vac
Nominal Input Frequency50Hz / 60Hz (Auto detection)
Low Loss Frequency40±1Hz
Low Loss Return Frequency42±1Hz
High Loss Frequency65±1Hz
High Loss Return Frequency63±1Hz
Output Short Circuit ProtectionCircuit Breaker
Efficiency (Line Mode)>95% (Rated R load, battery full charged)
Transfer Time10ms typical (UPS); 20ms typical (Appliances)

6.2. Inverter Mode Specifications

Table 2: Inverter Mode Specifications
Inverter Model1KVA2KVA3KVA
Rated Output Power1KVA/0.8KW2KVA/1.6KW3KVA/2.4KW
Output Voltage WaveformPure Sine Wave
Output Voltage Regulation120Vac±5%
Output Frequency60Hz
Peak Efficiency90%
Overload Protection5s@≥150% load; 10s@110%~150% load
Surge Capacity2* rated power for 5 seconds
Nominal DC Input Voltage12Vdc24Vdc
Cold Start Voltage11.5Vdc23.0Vdc
Low DC Warning Voltage @ load < 20%11.0Vdc22.0Vdc
Low DC Warning Voltage @ 20% ≤ load < 50%10.7Vdc21.4Vdc
Low DC Warning Voltage @ load ≥ 50%10.1Vdc20.2Vdc
Low DC Warning Return Voltage @ load < 20%11.5Vdc23.0Vdc
Low DC Warning Return Voltage @ 20% ≤ load < 50%11.2Vdc22.4Vdc
Low DC Warning Return Voltage @ load ≥ 50%10.6Vdc21.2Vdc
Low DC Cut-off Voltage @ load < 20%10.5Vdc21.0Vdc
Low DC Cut-off Voltage @ 20% ≤ load < 50%10.2Vdc20.4Vdc
Low DC Cut-off Voltage @ load ≥ 50%9.6Vdc19.2Vdc
High DC Recovery Voltage14.5Vdc29Vdc
High DC Cut-off Voltage15.5Vdc31Vdc
No Load Power Consumption<15W<20W
Saving Mode Power Consumption<5W<10W

6.3. Charge Mode Specifications

Table 3: Charge Mode Specifications
Inverter Model1KVA2KVA3KVA
Charging Algorithm3-Step
Utility Charging Mode
AC Charging Current10/20Amp20/30Amp (@VI/P=120Vac)
Bulk Charging Voltage (Flooded Battery)14.629.2
Bulk Charging Voltage (AGM / Gel Battery)14.128.2
Floating Charging Voltage13.5Vdc27Vdc
Solar Charging Mode
Charging Current (PWM)50Amp
System DC Voltage12Vdc24Vdc
Operating Voltage Range15~18Vdc30~32Vdc
Max. PV Array Open Circuit Voltage40Vdc80Vdc
Standby Power Consumption1W2W
DC Voltage Accuracy+/-0.3%
Joint Utility and Solar Charging
Max Charging Current50Amp
Default Charging Current50Amp

6.4. General Specifications

Table 4: General Specifications
Inverter Model1KVA2KVA3KVA
Safety CertificationCE
Operating Temperature Range0°C to 55°C
Storage Temperature-15°C~60°C
Dimension (D*W*H), mm95 x 240 x 316100 x 272 x 355
Net Weight, kg5.06.46.9

7. Maintenance

To ensure optimal performance and longevity of your PowMr Hybrid Solar Inverter, regular maintenance is recommended. Keep the unit clean and free from dust and debris, especially around ventilation openings, to prevent overheating. Periodically check all electrical connections for tightness and signs of corrosion. Ensure batteries are maintained according to their manufacturer's guidelines and that equalization is performed as needed (refer to section 4.6).

8. Warranty and Support

The PowMr Hybrid Solar Inverter comes with a 1-year warranty. For any technical support, service, or warranty claims, please contact your local dealer or the PowMr service center. Always refer to the complete user manual PDF for detailed warranty terms and conditions.

Product unboxing and overview video for the PowMr Hybrid Solar Inverter.

9. User Tips

Based on common user inquiries and feedback:

  • Battery Compatibility: This inverter is designed for deep-cycle lead-acid type rechargeable batteries, including sealed lead-acid, GEL, and AGM types. Ensure your battery type is compatible and correctly configured in the LCD settings (Program 05).
  • Proper Sizing: When connecting solar panels, ensure the PV array's open circuit voltage (Voc) and maximum power voltage (Vmpp) are within the inverter's specified ranges to prevent damage and ensure efficient charging.
  • Connection Security: Always double-check all wiring connections (battery, AC input/output, PV) for tightness and correct polarity. Loose connections can lead to poor performance or safety hazards.
  • Cooling: Ensure the inverter has adequate ventilation. Blocked vents can lead to overheating and trigger fault codes (e.g., Fault code 02).