PowMr PS-3K-110V

Contents

PowMr 3KVA Hybrid Solar Inverter User Manual

Model: PS-3K-110V

1. Introduction

1.1 Purpose and Scope

This manual describes the assembly, installation, operation, and troubleshooting of the PowMr 3KVA Hybrid Solar Inverter. Please read this manual carefully before installation and operation. Keep this manual for future reference. This manual provides safety and installation guidelines, as well as information on tools and wiring.

1.2 Features

  • Pure sine wave inverter
  • Configurable input voltage range for home appliances and personal computers via LCD setting
  • Configurable battery charging current based on applications via LCD setting
  • Configurable AC/Solar Charger priority via LCD setting
  • Compatible with mains voltage or generator power
  • Auto restart while AC is recovering
  • Overload, over temperature, and short circuit protection
  • Smart battery charger design for optimized battery performance
  • Cold start function
  • Built-in PWM solar charge controller

1.3 Basic System Architecture

The PowMr 3KVA Hybrid Solar Inverter is a multi-function inverter/charger designed to provide uninterruptible power support. It integrates an inverter, solar charger, and battery charger. The system can be configured to work with various power sources and loads.

Hybrid Power System Diagram
Figure 1: Hybrid Power System Diagram. Shows connections for Solar Power, Generator/Utility, Inverter, Battery (24V lithium/Lead-Acid), and Home Appliances (single phase 110V output 2.4kW). Max VOC: 80V DC, PV Array MPPT Voltage Range: 30-80V DC, Max PV Array Power: 1200W, Max Charging current: 50A (AC charger + solar charger).

This inverter can power various appliances in home or office environments, including motor-type appliances such as tube lights, fans, refrigerators, and air conditioners.

1.4 Product Overview

The inverter features a comprehensive LCD display and user-friendly buttons for configuration and monitoring. Key components include AC input/output, PV input, battery input, communication ports, and an ON/OFF switch.

Product Views
Figure 2: Various views of the inverter, showing front, side, and bottom panels with connection ports.
Bottom Panel Connections
Figure 3: Detailed view of the bottom panel connections, including AC Input, AC Output, COM, NC C NO, PV Input, DC Input, ON/OFF switch, and Input Breaker.

2. Safety Instructions

WARNING: This chapter contains important safety and operating instructions. Read and keep this manual for future reference.

  1. Before using the unit, read all instructions and cautionary markings on the unit, the batteries, and all appropriate sections of this manual.
  2. CAUTION – To reduce risk of injury, charge only deep-cycle lead acid type rechargeable batteries. Other types of batteries may burst, causing personal injury and damage.
  3. Do not disassemble the unit. Take it to a qualified service center when service or repair is required. Incorrect re-assembly may result in a risk of electric shock or fire.
  4. To reduce risk of electric shock, disconnect all wirings before attempting any maintenance or cleaning. Turning off the unit will not reduce this risk.
  5. CAUTION – Only qualified personnel can install this device with battery.
  6. NEVER charge a frozen battery.
  7. For optimum operation of this inverter/charger, please follow required specifications to select appropriate cable size. It's very important to correctly operate this inverter/charger.
  8. Be very cautious when working with metal tools on or around batteries. A potential risk exists to drop a tool to spark or short circuit batteries or other electrical parts and could cause an explosion.
  9. Please strictly follow installation procedure when you want to disconnect AC or DC terminals. Please refer to the INSTALLATION section of this manual for details.
  10. Fuses (6 pieces of 40A, 32VDC for 3KVA) are provided as over-current protection for the battery supply.
  11. GROUNDING INSTRUCTIONS - This inverter/charger should be connected to a permanent grounded wiring system. Be sure to comply with local requirements and regulations to install this inverter.
  12. NEVER cause AC output and DC input short circuits. Do NOT connect to the mains when DC input short circuits.
  13. Warning!! Only qualified service persons are able to service this device. If errors still persist after following troubleshooting table, please send this inverter/charger back to local dealer or service center for maintenance.

3. Installation

3.1 Unpacking and Inspection

Before installation, please inspect the unit. Be sure that nothing inside the package is damaged. You should have received the following items:

  • The unit x 1
  • User manual x 1
  • Communication cable x 1
  • Software CD x 1

3.2 Preparation

Before connecting all wirings, remove the bottom cover by removing two screws.

3.3 Mounting the Unit

Consider the following points when selecting where to install:

  • Do not mount the inverter on flammable construction materials.
  • Mount on a solid surface.
  • Install this inverter at eye level to allow the LCD display to be read at all times.
  • For proper air circulation to dissipate heat, allow a clearance of approximately 20 cm to the side and approximately 50 cm above and below the unit.
  • The ambient temperature should be between 0°C and 55°C to ensure optimal operation.
  • The recommended installation position is to be adhered to the wall vertically.
  • Be sure to keep other objects and surfaces clear as shown in the diagram to guarantee sufficient heat dissipation and enough space for removing wires.

SUITABLE FOR MOUNTING ON CONCRETE OR OTHER NON-COMBUSTIBLE SURFACE ONLY.

3.4 Battery Connection

CAUTION: For safety and regulation compliance, it's requested to install a separate DC over-current protector or disconnect device between the battery and inverter.

WARNING! All wiring must be performed by qualified personnel. It's very important for system safety and efficient operation to use appropriate cable for battery connection. To reduce risk of injury, use the proper recommended cable and terminal size.

The 3KVA model supports a 24VDC system. It's suggested to connect at least a 100Ah capacity battery.

Recommended Battery Cable and Terminal Size
ModelTypical AmperageBattery capacityWire SizeCable mm²Torque value
3KVA100A100AH1*4AWG222~3 Nm
200AH2*8AWG142~3 Nm

Follow these steps to implement battery connection:

  1. Assemble battery ring terminal based on recommended battery cable and terminal size.
  2. Connect all battery packs as shown in the diagram.
  3. Insert the ring terminal of the battery cable flatly into the battery connector of the inverter and make sure the bolts are tightened with a torque of 2-3 Nm. Ensure polarity is correct at both the battery and the inverter/charger.

WARNING: Shock Hazard. Installation must be performed with care due to high battery voltage in series.

CAUTION!! Do not place anything between the flat part of the inverter terminal and the ring terminal. Otherwise, overheating may occur.

CAUTION!! Do not apply anti-oxidant substance on the terminals before terminals are connected tightly.

CAUTION!! Before making the final DC connection or closing DC breaker/disconnector, be sure positive (+) must be connected to positive (+) and negative (-) must be connected to negative (-).

3.5 AC Input/Output Connection

CAUTION!! Before connecting to an AC input power source, please install a separate AC breaker between the inverter and the AC input power source. This will ensure the inverter can be securely disconnected during maintenance and fully protected from overcurrent of AC input. The recommended specification for the AC breaker is 45A for 3KVA.

CAUTION!! There are two terminal blocks with "IN" and "OUT" markings. Please do NOT mis-connect input and output connectors.

WARNING! All wiring must be performed by qualified personnel. It's very important for system safety and efficient operation to use appropriate cable for AC input connection. To reduce risk of injury, use the proper recommended cable size.

Suggested Cable Requirement for AC Wires
ModelGaugeTorque Value
3KVA10 AWG1.2~1.6 Nm

Follow these steps to implement AC input/output connection:

  1. Before making AC input/output connection, be sure to open the DC protector or disconnector first.
  2. Remove insulation sleeve 10mm for six conductors. Shorten phase L and neutral conductor N by 3mm.
  3. Insert AC input wires according to polarities indicated on the terminal block and tighten the terminal screws. Be sure to connect the PE protective conductor (Ground, yellow-green) first.
  4. Then, insert AC output wires according to polarities indicated on the terminal block and tighten terminal screws. Be sure to connect the PE protective conductor first.
  5. Make sure the wires are securely connected.

WARNING: Be sure that the AC power source is disconnected before attempting to hardwire it to the unit.

CAUTION: Important. Be sure to connect AC wires with correct polarity. If L and N wires are connected reversely, it may cause utility short-circuited when these inverters are worked in parallel operation.

CAUTION: Appliances such as air conditioners require at least 2-3 minutes to restart because it's required to have enough time to balance refrigerant gas inside of circuits. If a power shortage occurs and recovers in a short time, it will cause damage to your connected appliances. To prevent this kind of damage, please check the manufacturer of the air conditioner if it's equipped with a time-delay function before installation. Otherwise, this inverter/charger will trigger an overload fault and cut off output to protect your appliance, but sometimes it still causes internal damage to the air conditioner.

3.6 PV Connection (Only for models with solar charger)

CAUTION: Before connecting to PV modules, please install separately a DC circuit breaker between the inverter and PV modules.

WARNING! All wiring must be performed by qualified personnel. It's very important for system safety and efficient operation to use appropriate cable for PV module connection. To reduce risk of injury, use the proper recommended cable size.

Recommended PV Cable and Terminal Size
Typical AmperageGaugeTorque Value
50A8 AWG1.4~1.6 Nm

PV Module Selection:

When selecting proper PV modules, consider these requirements:

  1. Open circuit Voltage (Voc) of PV modules must not exceed the max PV array open circuit voltage of the inverter (80Vdc for 3KVA).
  2. Max. Power Voltage (Vmpp) of PV modules should be close to the best Vmp of the inverter or within the Vmp range to get the best performance.
Solar Charger Specifications (3KVA)
INVERTER MODEL3KVA
Charging Current50Amp
System DC Voltage24Vdc
Operating Voltage Range30~32Vdc
Max. PV Array Open Circuit Voltage80Vdc
Best Vmp and Vmp Range (3KVA)
ModelBest VmpVmp range
3KVA30Vdc30V~32V

Follow these steps to implement PV module connection:

  1. Remove insulation sleeve 10 mm for positive and negative conductors.
  2. Check correct polarity of connection cable from PV modules and PV input connectors. Connect positive pole (+) of connection cable to positive pole (+) of PV input connector. Connect negative pole (-) of connection cable to negative pole (-) of PV input connector.
  3. Make sure the wires are securely connected.

3.7 Final Assembly

After connecting all wirings, put the bottom cover back by screwing the two screws.

3.8 Communication Connection

Use the supplied communication cable to connect to the inverter and PC. Insert the bundled CD into a computer and follow the on-screen instructions to install the monitoring software. For detailed software operation, check the user manual of the software inside the CD.

3.9 Dry Contact Signal

There is one dry contact (3A/250VAC) available on the rear panel. It can be used to deliver a signal to an external device when the battery voltage reaches a warning level.

Dry Contact Signal Operation
Unit StatusConditionDry contact port: NC & CDry contact port: NO & C
Power OffUnit is off and no output is powered.CloseOpen
Power OnOutput is powered from Utility.CloseOpen
Battery voltage < Low DC warning voltageOpenClose
Program 01 set as Utility: Battery voltage > Setting value in Program 13 or battery charging reaches floating stageCloseOpen
Program 01 is set as SBU or Solar first: Battery voltage < Setting value in Program 12OpenClose
Program 01 is set as SBU or Solar first: Battery voltage > Setting value in Program 13 or battery charging reaches floating stageCloseOpen

4. Operation

4.1 Power ON/OFF

Once the unit has been properly installed and the batteries are connected, simply press the On/Off switch (located on the bottom of the case) to turn on the unit.

4.2 Operation and Display Panel

The operation and display panel, located on the front of the inverter, includes three indicators, four function keys, and an LCD display, showing the operating status and input/output power information.

LED Indicator Messages
LED IndicatorColorMessages
AC/INVGreenSolid On: Output is powered by utility in Line mode.
Flashing: Output is powered by battery or PV in battery mode.
CHGGreenSolid On: Battery is fully charged.
Flashing: Battery is charging.
FAULTRedSolid On: Fault occurs in the inverter.
Flashing: Warning condition occurs in the inverter.
Function Keys
Function KeyDescription
ESCTo exit setting mode
UPTo go to previous selection
DOWNTo go to next selection
ENTERTo confirm the selection in setting mode or enter setting mode

4.3 LCD Display Icons

The LCD display provides various information through icons and numerical values. These include input source information, configuration program and fault information, output information, battery information, load information, mode operation information, and mute operation status.

Input Source Information
IconFunction description
ACIndicates the AC input.
PVIndicates the PV input.
INPUTBATT (numerical)Indicates input voltage, input frequency, PV voltage, battery voltage, and charger current.
Configuration Program and Fault Information
IconFunction description
Program Number (numerical)Indicates the setting programs.
ERROR (numerical)Indicates the warning and fault codes.
ERROR (flashing numerical)Warning: flashing with warning code.
ERROR (solid numerical)Fault: lighting with fault code.
Output Information
IconFunction description
OUTPUTBATTLOAD (numerical)Indicates output voltage, output frequency, load percent, load in VA, load in Watt, and discharging current.
Battery Information
IconFunction description
CHARGING (battery bars)Indicates battery level by 0-24%, 25-49%, 50-74%, and 75-100% in battery mode and charging status in line mode.

4.4 LCD Setting

After pressing and holding the ENTER button for 3 seconds, the unit will enter setting mode. Use the "UP" or "DOWN" buttons to select setting programs, and then press "ENTER" to confirm the selection or "ESC" to exit.

Refer to the detailed tables in the PDF manual (pages 17-23) for specific LCD setting options, including output source priority, maximum charging current, AC input voltage range, power saving mode, battery type, auto restart settings, output frequency, maximum utility charging current, low DC cut-off voltage, battery equalization settings, and auto return to default display screen.

4.5 Display Setting

The LCD display information can be switched by pressing the “UP” or “DOWN” key. The selectable information includes input voltage, input frequency, PV voltage, charging current, battery voltage, output voltage, output frequency, load percentage, load in Watt, load in VA, DC discharging current, main CPU Version, and second CPU Version.

Refer to the detailed tables in the PDF manual (pages 24-25) for specific display setting options and their corresponding LCD icons.

4.6 Operating Mode Description

The inverter operates in various modes, including Standby, Power Saving, Fault, Line, and Battery Mode. Each mode has specific behaviors and charging characteristics.

Refer to the detailed tables in the PDF manual (pages 26-27) for specific operating mode descriptions and their corresponding LCD displays.

4.7 Battery Equalization

The equalization function helps reverse the buildup of negative chemical effects like stratification and removes sulfate crystals, which can reduce battery capacity. It's recommended to equalize the battery periodically.

To apply the equalization function, you must enable it in monitoring LCD setting program 30. Then, you can apply it by setting the equalization interval in program 35 or by activating equalization immediately in program 36.

5. Maintenance

Regular maintenance ensures the longevity and optimal performance of your PowMr Hybrid Solar Inverter.

  • Regular Inspection: Periodically inspect all wiring connections for tightness and signs of wear or corrosion.
  • Cleaning: Disconnect all power sources before attempting any maintenance or cleaning. Ensure the inverter's ventilation openings are clear of dust and debris to maintain proper airflow and prevent overheating.
  • Battery Care: Regularly check battery terminals for corrosion and ensure they are clean and tightly connected. Monitor battery voltage and perform equalization as needed, especially for deep-cycle lead-acid batteries.
  • Environmental Conditions: Ensure the inverter is operating within the recommended ambient temperature range (0°C to 55°C) and that there is adequate clearance for heat dissipation.

6. Troubleshooting

This section provides guidance for common issues. If problems persist, contact qualified service personnel.

Troubleshooting Guide
ProblemLCD/LED/BuzzerExplanation / Possible causeWhat to do
Unit shuts down automatically during startup process.LCD/LEDs and buzzer will be active for 3 seconds and then complete off.The battery voltage is too low (<1.91V/Cell)1. Re-charge battery.
2. Replace battery.
No response after power on.No indication.1. The battery voltage is far too low. (<1.4V/Cell)
2. Battery polarity is connected reversed.
1. Check if batteries and the wiring are connected well.
2. Re-charge battery.
3. Replace battery.
Input voltage is displayed as 0 on the LCD and green LED is flashing.Input protector is trippedCheck if AC breaker is tripped and AC wiring is connected well.
Mains exist but the unit works in battery mode.Green LED is flashing.Insufficient quality of AC power. (Shore or Generator)1. Check if AC wires are too thin and/or too long.
2. Check if generator (if applied) is working well or if input voltage range setting is correct. (UPS→Appliance)
Green LED is flashing.Set "Solar First" as the priority of output source.Change output source priority to Utility first.
When the unit is turned on, internal relay is switched on and off repeatedly.LCD display and LEDs are flashingBattery is disconnected.Check if battery wires are connected well.
Buzzer beeps continuously and red LED is on.Fault code 07Overload error. The inverter is overload 110% and time is up.Reduce the connected load by switching off some equipment.
Fault code 05Output short circuited.Check if wiring is connected well and remove abnormal load.
Fault code 02Temperature of internal converter component is over 120°C.Check whether the air flow of the unit is blocked or whether the ambient temperature is too high.
Fault code 03Battery is over-charged. The battery voltage is too high.Return to repair center. Check if spec and quantity of batteries are met.
Fault code 01Fan faultReplace the fan.
Fault code 06Output abnormal (Inverter voltage below than 100Vac or is higher than 135 Vac)1. Reduce the connected load.
2. Return to repair center
Fault code 08/09Internal components failed.Return to repair center.

7. Specifications

7.1 Line Mode Specifications

Table 1: Line Mode Specifications (3KVA)
INVERTER MODEL3KVA
Input Voltage WaveformSinusoidal (utility or generator)
Nominal Input Voltage120Vac
Low Loss Voltage95 Vac±7V (UPS); 65 Vac±7V (Appliances)
Low Loss Return Voltage100Vac±7V (UPS); 70Vac±7V (Appliances)
High Loss Voltage140Vac±7V
High Loss Return Voltage135Vac±7V
Max AC Input Voltage150 Vac
Nominal Input Frequency50Hz / 60Hz (Auto detection)
Low Loss Frequency40±1Hz
Low Loss Return Frequency42±1Hz
High Loss Frequency65±1Hz
High Loss Return Frequency63±1Hz
Output Short Circuit ProtectionCircuit Breaker
Efficiency (Line Mode)>95% (Rated R load, battery full charged)
Transfer Time10ms typical (UPS); 20ms typical (Appliances)

7.2 Inverter Mode Specifications

Table 2: Inverter Mode Specifications (3KVA)
INVERTER MODEL3KVA
Rated Output Power3KVA/2.4KW
Output Voltage WaveformPure Sine Wave
Output Voltage Regulation120Vac±5%
Output Frequency60Hz
Peak Efficiency90%
Overload Protection5s@≥150% load; 10s@110%~150% load
Surge Capacity2* rated power for 5 seconds
Nominal DC Input Voltage24Vdc
Cold Start Voltage23.0Vdc
Low DC Warning Voltage @ load < 20%22.0Vdc
Low DC Warning Voltage @ 20% ≤ load < 50%21.4Vdc
Low DC Warning Voltage @ load ≥ 50%20.2Vdc
Low DC Warning Return Voltage @ load < 20%23.0Vdc
Low DC Warning Return Voltage @ 20% ≤ load < 50%22.4Vdc
Low DC Warning Return Voltage @ load ≥ 50%21.2Vdc
Low DC Cut-off Voltage @ load < 20%21.0Vdc
Low DC Cut-off Voltage @ 20% ≤ load < 50%20.4Vdc
Low DC Cut-off Voltage @ load ≥ 50%19.2Vdc
High DC Recovery Voltage29Vdc
High DC Cut-off Voltage31Vdc
No Load Power Consumption<20W
Saving Mode Power Consumption<10W

7.3 Charge Mode Specifications

Table 3: Charge Mode Specifications (3KVA)
INVERTER MODEL3KVA
Charging Algorithm3-Step
AC Charging Current20/30Amp (@VI/P=120Vac)
Bulk Charging Voltage (Flooded Battery)29.2
Bulk Charging Voltage (AGM / Gel Battery)28.2
Floating Charging Voltage27Vdc
Charging Current (PWM)50Amp
System DC Voltage24Vdc
Operating Voltage Range30~32Vdc
Max. PV Array Open Circuit Voltage80Vdc
Standby Power Consumption2W
DC Voltage Accuracy+/-0.3%
Max Charging Current (Joint Utility and Solar Charging)50Amp
Default Charging Current (Joint Utility and Solar Charging)50Amp

7.4 General Specifications

Table 4: General Specifications (3KVA)
INVERTER MODEL3KVA
Safety CertificationCE
Operating Temperature Range0°C to 55°C
Storage temperature-15°C~60°C
Dimension (D*W*H), mm100 x 272 x 355
Net Weight, kg6.9

8. User Tips

  • PV Panel Sizing: When connecting solar panels, always refer to the 'PV Connection' section (3.6) and the 'Charge Mode Specifications' (7.3) to ensure the number and wattage of your solar panels (e.g., 605W panels) do not exceed the inverter's maximum PV array open circuit voltage (80VDC) and maximum PV power input (1200W). Proper sizing is crucial for efficient operation and to prevent damage.
  • Battery Compatibility: Only use sealed lead-acid or sealed GEL/AGM lead-acid batteries with this inverter. Ensure the battery capacity is at least 100Ah for optimal performance.
  • Cable Sizing: Always use the recommended cable sizes for both battery and AC connections to prevent overheating and ensure safe operation.

9. Warranty and Support

For warranty information, technical support, or service inquiries, please contact your local dealer or the manufacturer directly. Ensure you have your product model number (PS-3K-110V) and serial number available when seeking support.

A user manual in PDF format is available for download for detailed item guides and documents. You can find it at: PowMr 3KVA Hybrid Solar Inverter User Manual (PDF)

10. Appendix: Approximate Back-up Time Table

Approximate Back-up Time Table (3KVA Model)
Load (VA)Backup Time @ 24Vdc 100Ah (min)Backup Time @ 24Vdc 200Ah (min)
3004491100
600222525
900124303
120095227
150068164
180056126
210048108
24003594
27003174
30002867

Note: Backup time depends on the quality of the battery, age of battery, and type of battery. Specifications of batteries may vary depending on different manufacturers.