1. Introduction
This manual provides essential information for the safe and effective use of your EARU EAPDX-63AVE-RGB Multi-Function Protector. Please read it thoroughly before installation and operation, and keep it for future reference.
The EARU EAPDX-63AVE-RGB is an instrument and equipment used to measure, record, display, and analyze parameters related to electric energy. It is widely applied in various stages of the power system, including power generation, transmission, distribution, and consumption. It features adjustable over-voltage, under-voltage, and over-current protection, along with automatic on/off, automatic reset, and real-time display of voltage, current, and kWh.
2. Important Safety Instructions
WARNING
This product does not feature an explosion-proof structure and must not be used in flammable environments, such as those containing flammable gases, liquids, or explosives.
SAFETY INFORMATION
- Please use this product in accordance with the instructions in this manual.
- Do not disassemble this product by yourself.
- Pay attention to the rated voltage for use.
3. Specifications
The EARU EAPDX-63AVE-RGB Multi-Function Protector is designed for reliable performance and protection in electrical systems. Key features include:
- kWh Display: Monitors energy consumption.
- Automatic On/Off: For convenient operation.
- Automatic Reset: Recovers automatically after protection events.
- Undervoltage Protection: Adjustable range from 80V-210V.
- Overvoltage Protection: Adjustable range from 230V-300V.
- Current Display: Real-time current monitoring.
- Overcurrent Protection: Adjustable range from 1A-63A.

Figure 3.1: Product Dimensions and Parameters
Technical Parameters
| Parameter | Value |
|---|---|
| Rated Supply Voltage | AC 220V |
| Operating Voltage Range | AC 80V-400V |
| Operating Frequency | 50/60Hz |
| Overcurrent Setting Range | 1-63A |
| Voltage Setting Range | 230-300V (Over-voltage), 80-210V (Under-voltage) |
| Tolerance Range | 2% |
| Protection Action Delay Time | 0.5s |
| Reset/Start Delay | 1s-600s |
| Measurement Accuracy | 1% (Not exceeding 1% of the overall range) |
| Insulation Voltage | 400V |
| Output Contact | 1NO |
| Contact Electrical Life | 104 |
| Mechanical Life of Contacts | 106 |
| Protection Class | IP20 |
| Pollution Level | 3 |
| Altitude | <2000m |
| Operating Temperature | -50℃~55℃ |
| Humidity | <50%@40℃ |
| Storage Temperature | -30℃~70℃ |

Figure 3.2: Detailed Technical Parameters and Settings Menu Flowchart
4. Setup
4.1 Physical Installation
The EARU Multi-Function Protector is designed for easy installation on a standard DIN rail. Ensure the DIN rail is securely mounted in your electrical panel.

Figure 4.1: DIN Rail Installation
4.2 Wiring Installation
Refer to the wiring diagram below for correct connection. Ensure all connections are secure and comply with local electrical codes. The device has clearly marked IN (input) and OUT (output) terminals for Neutral (N) and Live (L) wires.

Figure 4.2: Wiring Installation Diagram
The wiring diagram illustrates connecting the protector between the main power source (IN) and the load (OUT), typically alongside circuit breakers (e.g., DZ47LE-63 and DZ47-63 as shown in the diagram).
5. Operating Instructions
5.1 Display Overview
The device features a clear digital display showing real-time voltage (V), current (A), and accumulated energy consumption (kWh).

Figure 5.1: Display Interface
5.2 Setting Parameters
To enter the setting state, press and hold the 'SET' button for more than 3 seconds. Use the 'UP' and 'DOWN' arrow buttons to adjust different values. The settings menu allows configuration of various protection parameters and delays.

Figure 5.2: Settings Menu Flowchart
The settings menu includes:
- PL (Power-on delay time): 1s-600s
- rE (Protection recovery delay): 1s-600s
- OUr (Over-voltage protection setting): 230V-300V
- OUr (Over-voltage recovery setting): 225V-295V
- Undervoltage protection setting: 80V-210V
- Undervoltage recovery setting: 85V-215V
- UEE (Over-under-voltage protection action delay time): 0.1s-10s
- URd (Calibration Voltage Value): -9.9V~9.9V
- oFF (Over current protection value): 1-63A
- CtE (Overcurrent protection action time): 0.1s-60s
- CtE (Overcurrent protection continuous times): 0-20
- CAd (Current Calibration): -9.9A~9.9A
- PE (Power range setting): 1-999
- CLP (Reset mode): CLP 003 Reset setting, CLP 006 Reset power level, CLP 009 Restore Factory Settings
5.3 Automatic Detection and Protection
The device features automatic detection. When the voltage is too high or too low, the load side power supply will be automatically disconnected and detected. After the line voltage returns to normal, it will automatically shut down and restore power supply.

Figure 5.3: Automatic Detection
5.4 Video Demonstration
Video 5.1: Demonstration of setting adjustments and display functions.
6. Maintenance
The EARU Multi-Function Protector is designed for durability with a shell made of new PC material, which is impact-resistant, drop-resistant, and has a long service life. It also incorporates intelligent anti-interference capabilities.
- Keep the device clean and free from dust and moisture.
- Do not expose the device to extreme temperatures or direct sunlight.
- Regularly check wiring connections for tightness and signs of wear.
- If the device requires cleaning, use a dry, soft cloth. Do not use abrasive cleaners or solvents.

Figure 6.1: Product Material and Design Features
7. Troubleshooting
If you encounter issues with your Multi-Function Protector, consider the following:
- No Display/Power: Check the input power supply and wiring connections. Ensure the device is receiving the rated voltage.
- Frequent Tripping: Review your set over-voltage, under-voltage, and over-current protection values. They might be set too sensitively for your load or power conditions. Adjust the protection action delay times if necessary.
- Incorrect Readings: If voltage or current readings appear inaccurate, consider performing a calibration using the 'URd' (Voltage Calibration) or 'CAd' (Current Calibration) settings in the menu.
- Device Not Resetting: Check the 'rE' (Protection recovery delay) setting. If it's set to a long duration, the device will wait before attempting to restore power. Also, ensure the fault condition (over/under voltage, over current) has cleared.
- Device Malfunction: If the device behaves unexpectedly and troubleshooting steps do not resolve the issue, you may try restoring factory settings via the 'CLP 009' option in the settings menu.
For complex issues, consult a qualified electrician.
8. User Tips
- Initial Setup: When first installing, double-check all wiring connections to prevent damage to the device or connected appliances.
- Parameter Adjustment: Take time to understand the adjustable parameters (over-voltage, under-voltage, over-current, delays) and set them according to your specific electrical system requirements and connected load characteristics.
- Monitoring: Regularly observe the real-time display for voltage, current, and kWh to understand your power consumption patterns and identify any anomalies.
- Factory Reset: If you make too many changes and are unsure of the correct settings, use the 'Restore Factory Settings' option (CLP 009) as a last resort to revert to default parameters.
9. Warranty and Support
For warranty information and technical support, please refer to the documentation provided with your purchase or contact EARU customer service. Keep your purchase receipt as proof of purchase.
For additional information or to download the full user manual in PDF format, please visit the official EARU website or refer to the provided PDF link: User manual (PDF).