1. Introduction
The KONLEN WIFI intelligent water level controller (Model: KL-W1WL-Tuya) is designed for precise water level monitoring and control. It integrates with the Tuya Smart or Smart Life App, enabling remote management of water supplement or drainage, high and low water level alarm notifications, and historical data logging.
This device is suitable for various applications including HVAC systems, hot water processes, municipal drainage, boilers, water towers, storage tanks, and irrigation systems.
Video: Product demonstration of the KONLEN Smart Water Level Controller showing real-time level detection and app synchronization.
2. Product Components

Image: KONLEN Smart Level Controller and a set of 6 water level probes.
2.1 Controller Overview

Image: Front, side, and back views of the KONLEN Smart Level Controller with dimensions (89mm x 55mm x 44mm).
The controller features an LED display for current water level, configuration buttons, and status indicators.
- A: WIFI Configuration Button / Manual Switch of Relay Output 1
- B: Manual Switch of Relay Output 2
- C: WIFI Configuration Indicator / Relay Output 1 Status Indicator
- D: Relay Output 2 Status Indicator
- E: Display Current Water Level
- F: Built-in Buzzer for high/low water level local alarm.
2.2 Water Level Probes
The system includes 6 water level probes for detecting different water levels. These probes are connected to specific terminals on the controller:
- Terminal 1: 100% water level
- Terminal 2: 80% water level
- Terminal 3: 60% water level
- Terminal 4: 40% water level
- Terminal 5: 20% water level
- Terminal 6: 0% water level, Common Terminal (COM)
3. Setup Instructions
3.1 Probe Installation
Install the 6 water level probes at the desired percentage levels within your tank or container. Connect each probe to its corresponding terminal (1-6) on the controller as indicated above. Terminal 6 is the common terminal and should be placed at the lowest point or reference level.
3.2 Electrical Wiring
Important: Ensure power is disconnected before performing any wiring. The relay outputs (CH1/CH2) act as common power switches and do not output voltage. Connect your pump, valve, or other devices to the relays as you would a normal switch.

Image: General wiring diagram showing probe connections (1-6), power supply (AC90V-250V or DC5V), and relay outputs (7-8 for Relay 1, 9-10 for Relay 2).
- Relay Output 1 (CH1): Connect your primary control device (e.g., water pump for adding/draining) to Terminals 7 and 8.
- Relay Output 2 (CH2): Connect your secondary control device (e.g., siren, second pump, heater) to Terminals 9 and 10.
- Power Supply: Connect the appropriate power source to Terminals 11 and 12. Two versions are available: AC90V-250V or DC5V. Ensure you use the correct power supply for your model.

Image: KONLEN Smart Level Controller showing AC90V to AC250V power input terminals.
3.3 App Integration (Tuya Smart / Smart Life)
To connect your controller to the mobile application:
- Download the Tuya Smart or Smart Life App from your device's app store.
- Register or log in to your account.
- Power on the KONLEN Smart Water Level Controller.
- Press and hold the WIFI configuration button (A) on the controller until the WIFI configuration indicator (C) starts blinking, indicating pairing mode.
- In the app, follow the on-screen instructions to add a new device. Select the appropriate device type (e.g., 'Water Sensor' or 'Controller').
- Complete the pairing process. Once connected, the WIFI indicator will become solid.
4. Operating Instructions
4.1 Water Level Display
The current water level is displayed both on the controller's LED panel (E) and within the Tuya Smart/Smart Life App. The display shows 6 stages: 0%, 20%, 40%, 60%, 80%, and 100%.
- Water Level Rising: As water reaches each probe level (20%, 40%, etc.), the display will update accordingly.
- Water Level Reducing: As water drops below each probe level, the display will update.

Image: System overview demonstrating real-time water level display on both the controller's LED panel and the connected mobile application.
4.2 App Interface and Controls
The app provides comprehensive control and monitoring features. Key controls and settings for Relay CH1 and CH2 are available.

Image: Tuya Smart App interface showing various settings for the KONLEN water level controller, including work mode, level settings, and alarm options.
4.3 Relay CH1 Control Modes (Water Pump Control)
Relay CH1 is typically used for controlling a water pump to add or drain water. The app allows setting four working modes:
4.3.1 Add Water Mode
In this mode, the controller activates Relay CH1 to add water when the level falls below a set 'start up level' and deactivates it when the water reaches a 'stop level'.

Image: Illustration showing the 'Add Water' mode. When water level is below 20%, the pump starts to add water. When it reaches 100%, the pump turns off.
- Setting: Work Mode: Add. Set 'Level On1' (start adding) and 'Level Off1' (stop adding). Ensure 'Level On1' < 'Level Off1'.
4.3.2 Drain Water Mode
In this mode, the controller activates Relay CH1 to drain water when the level rises above a set 'start up level' and deactivates it when the water drops to a 'stop level'.

Image: Illustration showing the 'Drain Water' mode. When water level is at 100%, the pump starts to drain water. When it reaches 0%, the pump stops.
- Setting: Work Mode: Drain. Set 'Level On1' (start draining) and 'Level Off1' (stop draining). Ensure 'Level On1' > 'Level Off1'.
4.3.3 Time-Limited Adding Water Mode
This mode adds water for a preset duration. Relay CH1 activates to add water and simultaneously starts a timer. The relay automatically disconnects when the limited running time is reached, stopping water addition.

Image: App settings for 'Time-limited adding water' mode, showing 'Limited Time' (e.g., 60 Min) and 'Ch1 Delay' (e.g., 15 Sec).
- Setting: Work Mode: Add_limited. Set 'Limited Time' (0-720 minutes) and 'Ch1 Delay' (0-300 seconds) via the App.
4.3.4 Time-Limited Draining Water Mode
Similar to time-limited adding, this mode drains water for a preset duration. Relay CH1 activates to drain water and starts a timer. The relay automatically disconnects when the limited running time is reached, stopping water drainage.

Image: App settings for 'Time-limited draining water' mode, showing 'Limited Time' (e.g., 120 Min) and 'Ch1 Delay' (e.g., 15 Sec).
- Setting: Work Mode: Drain_limited. Set 'Limited Time' (0-720 minutes) and 'Ch1 Delay' (0-300 seconds) via the App.
4.4 Relay CH2 Functions (Supplementary Control)
Relay CH2 offers supplementary functions and can be configured for various purposes:
- Manual: Allows manual control of CH2 via the app.
- Alarm: Activates an external siren or flash light for local high/low water level alarms.
- L_On, H_Off: Relay CH2 turns ON when water level is Low, and OFF when water level is High.
- L_Off, H_On: Relay CH2 turns OFF when water level is Low, and ON when water level is High. This can be used for a second water pump (add/drain) or for anti-dry boiling protection with a heater.
4.5 Manual Switches
The physical buttons A (for CH1) and B (for CH2) on the controller allow for manual activation/deactivation of the respective relays. These manual switches are only effective when the current water level is between the preset start and stop-water level values configured in the app.
4.6 Emergency Main Switch (No.17 in App)
In case of a water pump or water probe malfunction, the 'Main Switch' (No.17 in the app) can be set to 'Off'. This temporarily disables both relays, preventing unintended operations. The water level display will continue to function normally.
5. Maintenance
- Cleaning: Regularly inspect and clean the water level probes to ensure accurate readings. Mineral buildup or debris can affect their performance.
- Controller: Keep the controller unit dry and free from dust. Avoid exposing it to direct sunlight or extreme temperatures.
- Wiring: Periodically check all wiring connections for any signs of wear, corrosion, or looseness.
6. Troubleshooting
6.1 Alarms
The system provides both remote (App push notification) and local (built-in buzzer or external siren) alarms for high and low water levels. You can configure which alarms are active (high, low, or both) in the app.

Image: App screenshots illustrating 'Over water alarm!' (high level) and 'Low water alarm!' notifications.
6.2 Common Issues
- No Water Level Display: Check probe connections (Terminals 1-6) and ensure the common terminal (Terminal 6) is properly submerged. Verify the controller has power.
- Relay Not Activating:
- Check the app settings for the specific relay (CH1 or CH2) and its work mode.
- Ensure the water level is within the configured 'start up' and 'stop' levels for automatic operation.
- Verify the 'Main Switch' (No.17 in App) is set to 'On'.
- Check the physical wiring of the connected device (pump, valve, etc.) to the relay output terminals.
- App Connectivity Issues:
- Ensure your Wi-Fi network is 2.4GHz (5G is not supported).
- Check your Wi-Fi signal strength at the controller's location.
- Re-attempt the Wi-Fi configuration process if necessary.
- Buzzer Alarm Not Working: Check if the buzzer alarm is enabled in the app settings for high/low water levels.
7. Specifications
| Feature | Specification |
|---|---|
| Product Size | 89mm x 55mm x 44mm (3.5 x 2.16 x 1.73 inches) |
| Controller Power Supply | Version 1: AC90V-250V Version 2: DC5V |
| Power Consumption | Less than 2W |
| Relay Outputs | Two (CH1 and CH2), Normal Open (NO) |
| Each Relay Max Load | 10A for resistive load 2A for inductive load Max control: 2000W resistive load or 500W motor/water pump Note: For larger loads, an AC contactor is required to prevent damage. |
| CH1 Limited Running Time | 0 to 720 minutes (settable via App) |
| CH1 Time Delay Setting | 0 to 300 seconds (settable via App) |
| Relay Lifespan | 100,000 times |
| Working Environment | -10℃ to 50℃ |
| WIFI Connectivity | Wi-Fi 2.4GHZ B/G/N (5G not supported) |
8. User Tips
- Cable Extension: The water level probe cables can be extended by the user if needed. The maximum recommended extension length is 50 to 80 meters (approximately 200ft to 260ft).
- Application: This controller is specifically designed for water level detection and control. It is not recommended for use with other liquids like diesel fuel, as its sensors are calibrated for water.
- Pump Compatibility: The relays can directly control water pumps up to 500W. For pumps with higher wattage, an external AC contactor must be used to prevent damage to the controller.
9. Warranty and Support