EARU Automatic Transfer Switch (ATS) User Manual

Model: ATS (2P/4P, 80A, AC 230V/110V)

1. Introduction

The EARU Automatic Transfer Switch (ATS) is designed to ensure an uninterrupted power supply by automatically switching between a primary power source and a backup power source during outages. This device is crucial for maintaining continuous operation of electrical loads in residential, commercial, and industrial settings. It supports various power configurations including City Grid-Generator, City Grid-City Grid, and City Grid-PV Energy.

Diagram illustrating the function of an Automatic Transfer Switch, showing rapid conversion between Primary Power Supply and Backup Power Supply when power is out or on.
Figure 1: Automatic Transfer Switch Functionality

Key Features:

  • Millisecond Switching: Ensures rapid power transfer (20ms) to minimize disruption.
  • Uninterruptible Power Supply: Automatically switches to backup power during outages.
  • PC Level Protection: Provides robust protection for connected systems.
  • Flame Retardant Material: Constructed with PA66 flame-retardant material for safety.
  • Low Energy Consumption: Efficient design for reduced power usage.
  • High Precision: Reliable and accurate operation.
  • Small Volume & Large Space: Space-optimized design for efficient installation.
  • Industrial Silver Contacts: Utilizes industrial-grade silver contacts for enhanced lifespan and conductivity.
  • 35MM Rail Mounting: Easy installation on standard DIN rails with securing clips.
  • Visualization Window: Clearly visible and aesthetically designed for functional clarity.

2. Product Specifications

The EARU ATS is available in 2-pole (2P) and 4-pole (4P) configurations, designed for various electrical systems.

Diagram showing dimensions of the 2P and 4P ATS models, including overall height, width, and depth, along with a table of product parameters.
Figure 2: Product Dimensions and Parameters
Technical Specifications
ParameterValue
Pole Configuration2P / 4P
Rated Voltage (L+N)AC230V / AC110V
Frequency50/60Hz
Rated Working Current80A
Insulation Voltage690V
Impulse Withstand Voltage8kV
Transfer Action Time20ms
Mechanical Durability≥6000 Times
Electrical Endurance≥1500 Times
Utilization CategoryAC-31B
Tse ClassPC
Installation35MM Din Rail
CertificationCE
Terminal Wiring Area1-25mm²
Wire Connection ScrewM5
Torque2.5N.m

3. Installation

The EARU ATS is designed for easy installation on a standard 35MM Din Rail, commonly found in household lighting distribution boxes.

Image showing multiple ATS units installed side-by-side on a 35MM Din Rail within a distribution box.
Figure 3: 35MM Standard Rail Installation

3.1 Wiring Diagrams

Ensure all wiring is performed by a qualified electrician and adheres to local electrical codes and safety regulations. Incorrect wiring can lead to serious injury or damage to the device.

Detailed wiring diagram for a 2P Automatic Transfer Switch, labeling Backup Power Neutral Wire, Backup Power Live Wire, Common Power Neutral Wire, Common Power Live Wire, Common Power Supply with Electricity Indication, Backup Power Supply with Electricity Indication, Auto/Manual Switch, Load Closing Indication, Operation Handle, Common/Backup Power Supply, and Load Output Live Wire.
Figure 4: 2P ATS Wiring Diagram
Detailed wiring diagram for a 4P Automatic Transfer Switch, labeling Backup Power Neutral Wire, Backup Power Live Wire, Common Power Neutral Wire, Common Power Live Wire, Common Power Supply with Electricity Indication, Backup Power Supply with Electricity Indication, Auto/Manual Switch, Load Closing Indication, Operation Handle, Common/Backup Power Supply, and Load Output Live Wire.
Figure 5: 4P ATS Wiring Diagram

Terminal Details:

  • Wire Connection: Suitable for wires ranging from 1mm² to 25mm².
  • Screw Type: M5
  • Tightening Torque: 2.5 N.m
  • Bottom Terminals: These terminals are for the Load Output Live Wire, connecting the switched power to your electrical loads.

Important Installation Note: The common/standby power supply should be 230V AC. If you are using a DC or low voltage power supply (e.g., from solar panels), an inverter is required to convert it to 230V AC. This inverter functionality is only applicable for the 'City Grid-PV Energy' configuration. 'City Grid-Generator' and 'City Grid-City Grid' configurations cannot be used with an inverter for conversion.

4. Operation

The ATS offers both automatic and manual operation modes, allowing flexibility in managing your power supply.

Image showing the ATS with labels pointing to Manual/Automatic Adjustment Buttons and the Manual Handle.
Figure 6: Two Modes of Adjustment

4.1 Automatic Mode

In automatic mode, the ATS continuously monitors the primary power supply. In the event of a primary power failure, it will automatically switch to the backup power supply with a rapid transition time of less than 20 milliseconds. When the primary power is restored, the system automatically switches back.

To activate automatic mode, ensure the mode selection switch is set to 'AUTO'.

Two ATS units demonstrating automatic switching after power failure, highlighting the <= 20ms transfer time.
Figure 7: Automatic Switching After Power Failure

4.2 Manual Mode

For manual control, set the mode selection switch to 'MANU'. In this mode, you can manually adjust the power supply using the operation handle. This is useful for testing or specific maintenance scenarios.

WARNING: Do NOT switch the grey button handle manually while the device is in 'AUTO' mode. Doing so may damage the internal coil.

4.3 Operation Demonstration Video

Video 1: Demonstration of Automatic and Manual Switching Modes

5. Maintenance

To ensure the longevity and reliable operation of your EARU ATS, follow these maintenance guidelines:

  • Regular Inspection: Periodically inspect the ATS for any signs of physical damage, loose connections, or overheating.
  • Cleanliness: Keep the device clean and free from dust and debris. Use a dry, soft cloth for cleaning. Do not use liquid cleaners.
  • Terminal Check: Ensure all terminal connections are tight and secure. Loose connections can cause resistance, heat buildup, and potential failure.
  • Functionality Test: Periodically test the automatic transfer function by simulating a power outage (if safely possible and recommended by a qualified electrician).
  • Professional Servicing: For any complex issues or internal inspections, consult a qualified electrician or service technician.

6. Troubleshooting

If you encounter issues with your ATS, refer to the following common problems and solutions:

  • ATS does not switch automatically:
    • Check if the mode selection switch is set to 'AUTO'.
    • Verify that both primary and backup power sources are functioning correctly.
    • Inspect wiring for loose connections or damage.
  • ATS does not switch manually:
    • Ensure the mode selection switch is set to 'MANU'.
    • Check for any mechanical obstruction preventing the handle from moving.
  • Power is not reaching the load after switching:
    • Confirm that the selected power source (primary or backup) is active and supplying voltage.
    • Check the load output wiring for continuity and secure connections.
    • Verify that the bottom terminals (Load Output Live Wire) are correctly connected.
  • Device appears to be damaged or overheating:
    • Immediately disconnect power to the device.
    • Do not attempt to repair it yourself. Contact a qualified electrician for inspection and repair.

7. User Tips

  • Power Source Compatibility: Remember that the ATS requires 230V AC for both common and standby power supplies. If using a DC or low voltage source like solar panels, an appropriate inverter is essential to convert it to 230V AC. This inverter use is specifically for 'City Grid-PV Energy' configurations.
  • Rapid Transfer: The ATS is designed for a very fast transfer time of 20 milliseconds, ensuring minimal interruption. It does not have a built-in delay of several seconds for switching.
  • Manual Operation Caution: Always ensure the mode selection switch is in the 'MANU' position before attempting to manually operate the handle. Forcing the handle in 'AUTO' mode can cause damage.
  • Terminal Identification: The terminals at the bottom of the unit are specifically for connecting the Load Output Live Wire to your electrical loads.