ANERN AN-SCI-MAX

Contents

Anern Hybrid Solar Inverter User Manual

Model: AN-SCI-MAX (10.2KW/6.2KW)

Brand: ANERN

1. Introduction

1.1 Purpose

This manual describes the assembly, installation, operation, and troubleshooting of the Anern Hybrid Solar Inverter. Please read this manual carefully before installations and operations. Keep this manual for future reference.

1.2 Scope

This manual provides safety and installation guidelines as well as information on tools and wiring for the Anern Hybrid Solar Inverter. This multi-function inverter/charger combines the functions of an inverter, solar charger, and battery charger to offer uninterruptible power support in a portable size. Its comprehensive LCD display offers user-configurable and easy-accessible button operation for settings such as battery charging current, AC/solar charger priority, and acceptable input voltage based on different applications.

1.3 Key Features

  • Pure Sine Wave Inverter
  • Configurable input voltage range for home appliances and personal computers via LCD setting
  • Configurable battery charging current based on applications via LCD setting
  • Configurable AC/Solar Charger priority via LCD setting
  • Compatible with mains voltage or generator power
  • Auto restart while AC is recovering
  • Overload/Over temperature/Short circuit protection
  • Smart battery charger design for optimized battery performance
  • Cold start function
  • Built-in 160A MPPT solar controller (for 10.2KW), 140A (for 8.2KW)
  • Max 7500W & 10800W solar input power respectively
  • Wide PV input voltage range (90-450VDC)
  • Built-in anti-dust kit for harsh environments
  • Dual PV Input & AC output (Only MAX 10200W models have dual MPPT)
  • WIFI available for IOS and Android systems
  • Compatible battery types: Lead-acid/Lithium iron phosphate (LiFePO4)/Colloid/Lithium battery
Anern Hybrid Solar Inverter with key features highlighted
Anern Hybrid Solar Inverter with a summary of its key features.

1.4 Basic System Architecture

The following illustration shows a basic application for this inverter/charger. It includes the following devices for a complete running system: Generator or Utility, and PV modules. Consult with your system integrator for other possible system architectures depending on your requirements. This inverter can power all kinds of appliances in home or office environments, including motor-type appliances such as tube lights, fans, refrigerators, and air conditioners.

System Diagram of Hybrid Power System
Figure 1: Hybrid Power System Diagram showing connections between solar panels, inverter, generator/utility, battery packs, and home appliances.

2. Safety Instructions

WARNING: This chapter contains important safety and operating instructions. Read and keep this manual for future reference.

  1. Before using the unit, read all instructions and cautionary markings on the unit, the batteries, and all appropriate sections of this manual.
  2. CAUTION: To reduce risk of injury, charge only deep-cycle lead acid type rechargeable batteries. Other types of batteries may burst, causing personal injury and damage.
  3. Do not disassemble the unit. Take it to a qualified service center when service or repair is required. Incorrect re-assembly may result in a risk of electric shock or fire.
  4. To reduce risk of electric shock, disconnect all wirings before attempting any maintenance or cleaning. Turning off the unit will not reduce this risk.
  5. CAUTION: Only qualified personnel can install this device with battery.
  6. NEVER charge a frozen battery.
  7. For optimum operation of this inverter/charger, please follow required specifications to select appropriate cable size. It's very important to correctly operate this inverter/charger.
  8. Be very cautious when working with metal tools on or around batteries. A potential risk exists to drop a tool to spark or short circuit batteries or other electrical parts and could cause an explosion.
  9. Please strictly follow the installation procedure when you want to disconnect AC or DC terminals. Please refer to the INSTALLATION section of this manual for the details.
  10. One piece of 150A fuse is provided as over-current protection for the battery supply.
  11. GROUNDING INSTRUCTIONS: This inverter/charger should be connected to a permanent grounded wiring system. Be sure to comply with local requirements and regulations to install this inverter.
  12. NEVER cause AC output and DC input short circuits. Do NOT connect to the mains when DC input short circuits.
  13. Warning!! Only qualified service persons are able to service this device. If errors still persist after following the troubleshooting table, please send this inverter/charger back to a local dealer or service center for maintenance.

3. Product Overview

Product Overview with labeled components
Product Overview: Front and rear views of the inverter with labeled components.
  1. LCD display
  2. Status indicator
  3. Charging indicator
  4. Fault indicator
  5. Touch Function buttons
  6. Power on/off switch
  7. AC input
  8. Main output
  9. Second output
  10. PV1 and PV2 input
  11. WIFI communication/RS-232 port
  12. Battery communication/RS-485 port
  13. Battery input
  14. Anti dust kit

4. Installation

4.1 Unpacking and Inspection

Before installation, please inspect the unit. Be sure that nothing inside the package is damaged. You should have received the following items inside the package:

  • The unit x 1
  • User manual x 1
  • Ring terminal x 1
  • Mc4 terminal head x 2

4.2 Preparation

Before connecting all lines, remove the screws under the machine and remove the bottom cover plate.

4.3 Mounting the Unit

Consider the following points before selecting where to install:

  • Do not mount the inverter on flammable construction materials.
  • Mount on a solid surface.
  • Install this inverter at eye level in order to allow the LCD display to be read at all times.
  • For proper air circulation to dissipate heat, allow a clearance of approx. 20 cm to the side and approx. 50 cm above and below the unit.
  • The ambient temperature should be between 0°C and 55°C to ensure optimal operation.
  • The recommended installation position is to be adhered to the wall vertically.
  • Make sure that other objects and surfaces are left with enough space from the machine to ensure adequate heat dissipation and that there is enough room to remove the wires.

SUITABLE FOR MOUNTING ON CONCRETE OR OTHER NON-COMBUSTIBLE SURFACE ONLY.

Install the unit by screwing two screws. It's recommended to use M4 or M5 screws.

4.4 Battery Connection

CAUTION: For safety operation and regulation compliance, it's requested to install a separate DC over-current protector or disconnect device between battery and inverter. It may not be requested to have a disconnect device in some applications, however, it's still requested to have over-current protection installed. Please refer to the typical amperage in the table below as required fuse or breaker size.

WARNING! All wiring must be performed by qualified personnel.

WARNING! It's very important for system safety and efficient operation to use appropriate cable for battery connection. To reduce risk of injury, please use the proper recommended cable as below.

Model Wire Size Cable (mm²) Torque value (max)
8.2KW/10.2KW 1 x 2AWG 25 2 Nm

Battery Connection Steps:

  1. Remove insulation sleeve 18 mm for positive and negative conductors.
  2. Suggest to put bootlace ferrules on the end of positive and negative wires with a proper crimping tool.
  3. Connect all battery packs as shown in the chart below.
  4. Insert the battery wires flatly into battery connectors of the inverter and make sure the bolts are tightened with a torque of 2 Nm in a clockwise direction. Make sure polarity at both the battery and the inverter/charger is correctly connected and conductors are tightly screwed into the battery terminals. Recommended tool: #2 Pozi Screwdriver.
Battery Connection Diagram
Diagram showing battery connection for the inverter (8.2KW/10.2KW models) with multiple 12V batteries in series.

WARNING: Shock Hazard! Installation must be performed with care due to high battery voltage in series.

CAUTION!! Before making the final DC connection or closing the DC breaker/disconnector, be sure positive (+) must be connected to positive (+) and negative (-) must be connected to negative (-).

4.5 AC Input/Output Connection

CAUTION!! Before connecting to an AC input power source, please install a separate AC breaker between the inverter and the AC input power source. This will ensure the inverter can be securely disconnected during maintenance and fully protected from overcurrent of AC input. The recommended spec of AC breaker is 63A for 8.2KW/10.2KW.

CAUTION!! There are two terminal blocks with "IN" and "OUT" markings. Please do NOT mis-connect input and output connectors.

WARNING! All wiring must be performed by qualified personnel.

WARNING! It's very important for system safety and efficient operation to use appropriate cable for AC input connection. To reduce risk of injury, please use the proper recommended cable size as below.

Suggested cable requirement for AC wires:

Model Gauge Cable (mm²) Torque Value
8.2KW/10.2KW 10 AWG 6 1.2 Nm

AC Input/Output Connection Steps:

  1. Before making AC input/output connection, be sure to open the DC protector or disconnector first.
  2. Remove insulation sleeve 10mm for six conductors. Shorten phase L and neutral conductor N by 3 mm.
  3. Insert AC input wires according to polarities indicated on the terminal block and tighten the terminal screws. Be sure to connect the PE protective conductor (Ground - yellow-green) first.
  4. Then, insert AC output wires according to polarities indicated on the terminal block and tighten the terminal screws (L - Line (brown or black), N - Neutral (blue)).
  5. Make sure the wires are securely connected.
AC Input/Output Wiring Diagram
Diagram illustrating the AC input and output wiring connections for the inverter.

WARNING: Be sure that the AC power source is disconnected before attempting to hardwire it to the unit.

4.6 PV Connection

CAUTION: Before connecting to PV modules, please install separately a DC circuit breaker between the inverter and PV modules.

WARNING! It's very important for system safety and efficient operation to use appropriate cable for PV module connection. To reduce risk of injury, please use the proper recommended cable size as below.

Suggested cable requirement for PV wires:

Model Wire Size Cable (mm²) Torque value (max)
8.2KW/10.2KW 1 x 10AWG 6 1.2 Nm

PV Module Selection:

When selecting proper PV modules, please be sure to consider the below parameters:

  1. Open circuit Voltage (Voc) of PV modules not exceeding the max. PV array open circuit voltage of the inverter.
  2. Open circuit Voltage (Voc) of PV modules should be higher than the min. battery voltage.
INVERTER MODEL 8.2KW/10.2KW
Max. PV Array Open Circuit Voltage 500Vdc
PV Array MPPT Voltage Range 90Vdc-450Vdc

Take a 250Wp PV module as an example. After considering the above two parameters, the recommended module configurations are listed in the table below:

Solar Panel Spec. (reference) SOLAR INPUT (Min in serial: 6 pcs, max. in serial: 13 pcs) Q'ty of panels Total input power
250Wp
Vmp: 30.1Vdc
Imp: 8.3A
Voc: 37.7Vdc
Isc: 8.4A
Cells: 60
6 pcs in serial 6 pcs 1500W
8 pcs in serial 8 pcs 2000W
12 pcs in serial 12 pcs 3000W
13 pcs in serial 13 pcs 3250W
12 pieces in serial and 3 sets in parallel 36 pcs 8200W
10 pieces in serial and 4 sets in parallel 40 pcs 10200W

PV Module Wire Connection:

  1. Check the input voltage of PV array modules. The acceptable input voltage of the inverter is 120VDC - 500VDC. Please make sure that the maximum current load of each PV Input connector is 10A.

CAUTION: Exceeding the maximum input voltage can destroy the unit!! Check the system before wire connection.

  1. Disconnect the DC circuit breaker.
  2. Assemble provided PV connectors with PV modules by following the steps below.
Components for PV connectors and Tools:
Component Image Component Image
Female connector housing Female connector housing Male terminal Male terminal
Female terminal Female terminal Crimping tool and spanner Crimping tool and spanner
Male connector housing Male connector housing
Cable preparation and connector assembly process:

Strip one cable 8 mm on both end sides and be careful NOT to nick conductors.

PV Cable Preparation and Assembly
Illustrations for stripping cable, inserting into female terminal, assembling into female housing, inserting into male terminal, and assembling into male housing.

Then, use a spanner to screw the pressure dome tightly to the female connector and male connector as shown above.

  1. Check the correct polarity of the connection cable from PV modules and PV input connectors. Then, connect the positive pole (+) of the connection cable to the positive pole (+) of the PV input connector. Connect the negative pole (-) of the connection cable to the negative pole (-) of the PV input connector.

4.7 Final Assembly

After connecting all wirings, please put the bottom cover back by screwing two screws as shown below.

4.8 Communication Connection

1. Wi-Fi cloud communication (option):

Please use the supplied communication cable to connect to the inverter and Wi-Fi module. Download the APP and install it from the APP store, and refer to the "Wi-Fi Plug Quick Installation Guideline" to set up the network and register. The inverter status will be shown by the mobile phone APP or webpage of the computer.

2. GPRS cloud communication (option):

Please use the supplied communication cable to connect to the inverter and GPRS module, and then apply external power to the GPRS module. Download the APP and install it from the APP store, and refer to the "GPRS RTU Quick Installation Guideline" to set up the network and register. The inverter status will be shown by the mobile phone APP or webpage of the computer.

3. Battery communication:

The communication between the battery and the inverter can be realized through the battery communication interface, so that the inverter and the lithium battery can exchange information (Baud rate: 9600).

4. Lithium battery and inverter connection:

Use power cables, communication cables for lithium batteries, and inverters to connect. Note: For lithium battery and inverter positive and negative positions, check the correct installation. The RJ45 connector of the communication cable connects to the BMS port of the inverter, and the other RJ45 connector connects to the RS485 port of the lithium battery. Before connecting, make sure that the lithium battery and inverter are turned off. (It is recommended to install a circuit breaker for the power cables of the lithium battery and the inverter battery interface. Otherwise, a spark may occur.)

Lithium Battery Communication Cable Interface
Diagram showing the lithium battery communication cable interface with RJ45 connections to BMS and RS485 ports.

5. Operation

5.1 Power ON/OFF

Once the unit has been properly installed and the batteries are connected well, simply press the On/Off switch (located on the button of the case) to turn on the unit.

5.2 Operation and Display Panel

The operation and display panel, shown in the product overview, is on the front panel of the inverter. It includes three indicators, four function keys, and an LCD display, indicating the operating status and input/output power information.

LED Indicator Messages:

Indicator Color State Messages
INV/AC Green Solid On Output is powered by utility in Line mode.
Flashing Output is powered by battery or PV in battery mode.
CHG Green Solid On Battery is fully charged.
Flashing Battery is charging.
FAULT Red Solid On Fault occurs in the inverter.
Flashing Warning condition occurs in the inverter.

Function Keys:

Function Key Description
ESC To exit setting mode
UP To go to previous selection
DOWN To go to next selection
ENTER To confirm the selection in setting mode or enter setting mode

5.3 LCD Display Icons

Icon Function description
AC Input Icon Indicates the AC input.
PV Input Icon Indicates the PV input.
Numeric Display Indicate input voltage, input frequency, PV voltage, charger current (if PV in charging for 10.2KW models), charger power, battery voltage.
Setting Programs Icon Indicates the setting programs.
Warning/Fault Codes Icon Indicates the warning and fault codes.
Output Information Icon Indicate output voltage, output frequency, load percent, load in VA, load in Watt and discharging current.
Battery Information Icon Indicates battery status.
Overload Icon Indicates overload.
Mains Connection Icon Indicates unit connects to the mains.
PV Panel Connection Icon Indicates unit connects to the PV panel.
AC Bypass Icon Indicates load is supplied by utility power.
Utility Charger Circuit Icon Indicates the utility charger circuit is working.
DC/AC Inverter Circuit Icon Indicates the DC/AC inverter circuit is working.
Mute Icon Indicates unit alarm is disabled.

5.4 LCD Setting

After pressing and holding the ENTER button for 3 seconds, the unit will enter setting mode. Press "UP" or "DOWN" button to select setting programs. Then, press "ENTER" button to confirm the selection or ESC button to exit.

Setting Programs Overview:

The manual provides detailed tables for various setting programs, including:

  • Program 00: Exit setting mode (Escape, One-button restore).
  • Program 01: Output source priority (Utility first, Solar first, SBU priority, MKS priority).
  • Program 02: Maximum charging current (10A to 160A).
  • Program 03: AC input voltage range (Appliances, UPS).
  • Program 05: Battery type (AGM, Flooded, User-Defined, LIB, LIC, LIL).
  • Program 06: Auto restart when overload occurs (Disable, Enable).
  • Program 07: Auto restart when over temperature occurs (Disable, Enable).
  • Program 09: Output frequency (50Hz, 60Hz).
  • Program 10: Output voltage (220V, 230V, 240V).
  • Program 11: Maximum utility charging current (2A to 20A).
  • Program 12: Setting voltage point back to utility source when selecting "SBU priority" or "Solar first" in program 01 (42V to 51V, and percentage options).
  • Program 13: Setting voltage point back to battery mode when selecting "SBU priority" or "LIP" or "LIL" in program 05 (Battery fully charged, 48V to 58V, and percentage options).
  • Program 16: Charger source priority (Solar first, Solar and Utility, Only Solar).
  • Program 18: Alarm control (Alarm on, Alarm off).
  • Program 19: Auto return to default display screen (Enable, Disable).
  • Program 20: Backlight control (On, Off).
  • Program 22: Beeps while primary source is interrupted (Alarm on, Alarm off).
  • Program 23: Overload bypass (Disable, Enable).
  • Program 25: Record Fault code (Enable, Disable).
  • Program 26: Bulk charging voltage (C.V voltage) (48.0V to 61.0V).
  • Program 27: Floating charging voltage (48.0V to 61.0V).
  • Program 29: Low DC cut-off voltage (40.0V to 48.0V).
  • Program 30: Battery equalization (Enable, Disable).
  • Program 31: Battery equalization voltage (48.0V to 61.0V).
  • Program 33: Battery equalized time (5min to 900min).
  • Program 34: Battery equalized timeout (5min to 900 min).
  • Program 35: Equalization interval (0 to 90 days).
  • Program 36: Equalization activated immediately (Enable, Disable).
  • Program 37: GRID-tie operation (Off grid, Hybrid).
  • Program 38: GRID-tie current (10A to 160A).
  • Program 39: Led pattern light (Off, On).
  • Program 41: Dual output (Disable, Enable).
  • Program 42: Enter the power point of dual output function (5% to 30%).
  • Program 43: BMS Communication address 48-70 setting.
  • Program 44: Delayed grid access (Disable, Enable).
  • Program 45: Maximum Second Load (20%~70%).

5.5 Display Setting

The LCD display information will be switched in turns by pressing the "UP" or "DOWN" key. The selectable information is switched as below order: input voltage, input frequency, PV voltage, charging current, charging power, battery voltage, output voltage, output frequency, load percentage, load in Watt, load in VA, load in Watt, DC discharging current, main CPU Version.

Example Display Screens:

LCD Display Examples for Charged and Discharged States
Examples of LCD display screens showing various parameters in charged and discharged states, both with power less than 1KW and greater than 1KW.

5.6 Operating Mode Description

The inverter supports various operating modes, including Standby, Line, and Grid-Tie Operation. The LCD display will show different information based on the current mode and system status.

Operating Mode LCD Displays
LCD display examples for Standby mode, Line mode, and Grid-Tie Operation, showing input/output voltages, currents, and load information.

Lithium Battery Communication Display (LIC/LIP/LIL modes):

When using lithium batteries with communication, the LCD provides detailed information about the battery status.

Lithium Battery Communication Display
LCD display showing lithium battery information such as total voltage, residual capacity, charging/discharge current, rated capacity, charge cycles, and MOS temperatures.

5.7 Battery Equalization Description

The equalization function is added to the charge controller. It reverses the buildup of negative chemical effects like stratification, a condition where acid concentration is greater at the bottom of the battery than at the top. Equalization also helps to remove sulfate crystals that might have built up on the plates. If left unchecked, this condition, called sulfation, will reduce the overall capacity of the battery. Therefore, it's recommended to equalize the battery periodically.

How to Apply Equalization Function:

You must enable the battery equalization function in monitoring LCD setting program 30 first. Then, you may apply this function in the device by either one of the following methods:

  1. Setting equalization interval in program 35.
  2. Active equalization immediately in program 36.

When to Equalize:

In the float stage, when the setting equalization interval (battery equalization cycle) is arrived, or equalization is active immediately, the controller will start to enter the Equalize stage.

Battery Equalization Diagram
Diagram illustrating the battery equalization process, showing Bulk, Absorption, Float, and Equalize stages with corresponding voltage levels.

Equalize charging time and timeout:

In the Equalize stage, the controller will supply power to charge the battery as much as possible until the battery voltage raises to the battery equalization voltage. Then, constant-voltage regulation is applied to maintain the battery voltage at the battery equalization voltage. The battery will remain in the Equalize stage until the setting battery equalized time is arrived.

However, in the Equalize stage, when the battery equalized time is expired and the battery voltage doesn't rise to the battery equalization voltage point, the charge controller will extend the battery equalized time until the battery voltage achieves the battery equalization voltage. If the battery voltage is still lower than the battery equalization voltage when the battery equalized timeout setting is over, the charge controller will stop equalization and return to the float stage.

5.8 Mains and lithium battery activation function

  1. After 90s of mains power connection to the inverter, the machine is connected to the mains and starts to work.
  2. The inverter is in lithium battery mode (item 05 is LIP or LIL). After the mains is connected, the battery is not connected, and the mains activation function is automatically enabled.

5.9 Fault Reference Code

Fault Code Fault Event Icon on
01Fan is locked when inverter is off.01 ERROR
02Over temperature02 ERROR
03Battery voltage is too high03 ERROR
04Battery voltage is too low04 ERROR
05Output short circuited or over temperature is detected by internal converter components.05 ERROR
06Output voltage is too high.06 ERROR
07Overload time out07 ERROR
08Bus voltage is too high08 ERROR
09Bus soft start failed09 ERROR
51Over current or surge51 ERROR
52Bus voltage is too low52 ERROR
53Inverter soft start failed53 ERROR
55Over DC voltage in AC output55 ERROR
57Current sensor failed57 ERROR
58Output voltage is too low58 ERROR
59PV voltage is over limitation59 ERROR

Battery Fault Codes (Lithium Battery Mode):

Fault Code Fault Event Fault Condition
02The battery temperature is too highLithium battery charging battery temperature ≥65°C; The discharge temperature of the lithium battery is higher than 70°C.
03The battery voltage is too highLithium battery maximum single cell voltage >3.65V; Total voltage of lithium battery >54.6V (48V lithium battery).
04The battery voltage is too lowMinimum voltage of a lithium battery cell <2.71V; Lithium battery total voltage <40.4V (48V lithium battery).

5.10 Warning Indicator

Warning Code Warning Event Audible Alarm Icon flashing
01Fan is locked when inverter is on.Beep three times every second01
03Battery is over-chargedBeep once every second03
04Low batteryBeep once every second04
07OverloadBeep once every 0.5 second07
10Output power deratingBeep twice every 3 seconds10
15PV energy is low.Beep twice every 3 seconds15
E9Battery equalizationNoneE9
bPBattery is not connectedNonebP

Added Battery Warning Codes (Lithium Battery Mode):

Warning Code Warning Event Warning Condition
04The battery voltage is too lowMinimum voltage of a lithium battery cell <2.85V; Lithium battery total voltage <42V (48V lithium battery).
05The battery voltage is too highLithium battery maximum single cell voltage >3.55V; Total voltage of lithium battery >54V (48V lithium battery).
06The battery is low warningRemaining battery capacity ≤10%

6. Clearance and Maintenance for Anti-Dust Kit

6.1 Overview

Every inverter is already installed with an anti-dust kit from the factory. The inverter will automatically detect this kit and activate an internal thermal sensor to adjust the internal temperature. This kit also keeps dust from your inverter and increases product reliability in harsh environments.

6.2 Clearance and Maintenance Steps

  1. Loosen the screw in a counterclockwise direction on the top of the inverter.
  2. The dustproof case can then be removed, and the air filter foam taken out as shown in the diagram below.
  3. Clean the air filter foam and dustproof case. After cleaning, re-assemble the dust-kit back to the inverter.

NOTICE: The anti-dust kit should be cleaned from dust every one month.

Anti-Dust Kit Maintenance Diagram
Diagram illustrating the steps to remove and clean the anti-dust kit components.

7. Specifications

Table 1 Line Mode Specifications

INVERTER MODEL 8.2KW 10.2KW
Input Voltage WaveformSinusoidal (utility or generator)
Nominal Input Voltage230Vac
Low Loss Voltage170Vac±7V (UPS); 90Vac±7V (Appliances)
Low Loss Return Voltage180Vac±7V (UPS); 100Vac±7V (Appliances)
High Loss Voltage280Vac±7V
High Loss Return Voltage270Vac±7V
Max AC Input Voltage300Vac
Nominal Input Frequency50Hz / 60Hz (Auto detection)
Low Loss Frequency40±1Hz
Low Loss Return Frequency42±1Hz
High Loss Frequency65±1Hz
High Loss Return Frequency63±1Hz
Output Short Circuit ProtectionCircuit Breaker
Efficiency (Line Mode)>95% (Rated R load, battery full charged)
Transfer Time10ms typical (UPS); 20ms typical (Appliances)

Output power derating:

When AC input voltage drops to 170V, the output power will be derated.

Output Power Derating Graph
Graph showing output power derating based on input voltage.

Table 2 Inverter Mode Specifications

INVERTER MODEL 8.2KW 10.2KW
Rated Output Power8.2KW10.2KW
Output Voltage WaveformPure Sine Wave
Output Voltage Regulation230Vac±5%
Output Frequency50Hz
Peak Efficiency93%
Overload Protection3s@≥150% load; 5s@101%~150% load
Surge Capacity2* rated power for 5 seconds
Nominal DC Input Voltage48Vdc
Cold Start Voltage46.0Vdc
Low DC Warning Voltage @ load < 50%44.0Vdc
Low DC Warning Voltage @ load ≥ 50%42.0Vdc
Low DC Warning Return Voltage @ load < 50%45.0Vdc
Low DC Warning Return Voltage @ load ≥ 50%44.0Vdc
Low DC Cut-off Voltage @ load < 50%41.0Vdc
Low DC Cut-off Voltage @ load ≥ 50%40.0Vdc
High DC Recovery Voltage62Vdc
High DC Cut-off Voltage63Vdc
No Load Power Consumption70W75W

Table 3 Two Load Output Power

INVERTER MODEL 8.2KW 10.2KW
Full Load8200W10200W
Maximum Main Load8200W10200W
Maximum Second Load (battery model)2733W3400W
Main Load Cut Off Voltage52VDC
Main Load Return Voltage54VDC

Table 4 Charge Mode Specifications

Utility Charging Mode 8.2KW 10.2KW
Charging Algorithm3-Step
AC Charging Current (Max)140Amp140Amp
Bulk Charging Flooded Battery Voltage58.4
AGM / Gel Battery Voltage56.4
Floating Charging Voltage54Vdc

Charging Curve:

Charging Curve Diagram
Diagram showing the battery charging curve with Bulk, Absorption, and Float stages.

MPPT Solar Charging Mode

INVERTER MODEL 8.2KW 10.2KW
Max. PV Array PowerPV1 Channel:5400W, PV2 Channel:5400WPV1 Channel:5400W, PV2 Channel:5400W
IMax.PVPV1 Channel:18A, PV2 Channel:18APV1 Channel:18A, PV2 Channel:18A
Nominal PV Voltage360Vdc
PV Array MPPT Voltage Range90Vdc-450Vdc
Max. PV Array Open Circuit Voltage500Vdc
Max Charging Current (AC charger plus solar charger)160Amp

Table 5 Grid-Tie Operation

INVERTER MODEL 8.2KW 10.2KW
Nominal Output Voltage220/230/240 VAC
Feed-in Grid Voltage Range195~253VAC
Feed-in Grid Frequency Range49~51 ±1Hz/59~61±1Hz
Nominal Output Current35.6A44.3A
Power Factor Range>0.99
Maximum Conversion Efficiency (DC/AC)98%

Table 6 General Specifications

INVERTER MODEL 8.2KW 10.2KW
Safety CertificationCE
Operating Temperature Range-10°C to 50°C
Storage temperature-15°C~60°C
Humidity5% to 95% Relative Humidity (Non-condensing)
Dimension (D*W*H), mm530*390*130mm
Net Weight, kg14.214.5

9. Appendix: Approximate Back-up Time Table

Model Load (W) Backup Time @ 48Vdc 100Ah (min) Backup Time @ 48Vdc 200Ah (min)
8.2KW
10.2KW
5006131288
1000268613
1500158402
2000111271
250090215
320076182
350065141
400050112
450044100
50004090
62003680
72003270
82002860
92002450
102002040

Note:

  1. Backup time depends on the quality of the battery, age of battery, and type of battery. Specifications of batteries may vary depending on different manufacturers.
  2. The final interpretation right of this product belongs to the company.

8. Troubleshooting

Problem LCD/LED/Buzzer Explanation / Possible cause What to do
Unit shuts down automatically during startup process. LCD/LEDs and buzzer will be active for 3 seconds and then complete off. The battery voltage is too low (<1.91V/Cell) 1. Re-charge battery.
2. Replace battery.
No response after power on. No indication. 1. The battery voltage is far too low. (<1.4V/Cell)
2. Internal fuse tripped.
1. Contact repair center for replacing the fuse.
2. Re-charge battery.
3. Replace battery.
Mains exist but the unit works in battery mode. Input voltage is displayed as 0 on the LCD and green LED is flashing. Input protector is tripped Check if AC breaker is tripped and AC wiring is connected well.
Green LED is flashing. Insufficient quality of AC power. (Shore or Generator) 1. Check if AC wires are too thin and/or too long.
2. Check if generator (if applied) is working well or if input voltage range setting is correct. (UPS/Appliance)
Green LED is flashing. Set "Solar First" as the priority of output source. Change output source priority to Utility first.
When the unit is turned on, internal relay is switched on and off repeatedly. LCD display and LEDs are flashing Battery is disconnected. Check if battery wires are connected well.
Buzzer beeps continuously and red LED is on. Fault code 07 Overload error. The inverter is overload 110% and time is up. Reduce the connected load by switching off some equipment.
Fault code 05 Output short circuited. Check if wiring is connected well and remove abnormal load.
Fault code 02 Temperature of internal converter component is over 120°C. Internal temperature of inverter component is over 100°C. Check whether the air flow of the unit is blocked or whether the ambient temperature is too high.
Fault code 03 Battery is over-charged. The battery voltage is too high. Return to repair center. Check if spec and quantity of batteries are meet requirements.
Fault code 01 Fan fault Replace the fan.
Fault code 06/58 Output abnormal (Inverter voltage below than 190Vac or is higher than 260Vac) 1. Reduce the connected load.
2. Return to repair center
Fault code 08/09/53/57 Internal components failed. Return to repair center.
Fault code 51 Over current or surge. Restart the unit, if the error happens again, please return to repair center.
Fault code 52 Bus voltage is too low.
Fault code 55 Output voltage is unbalanced.

9. User Tips

  • Wi-Fi Connectivity: If the inverter's own Wi-Fi app has connection issues, try using a third-party app for monitoring.
  • Noise Levels: The inverter's coolers are designed to activate under load, which may produce some noise. This is normal operation.
  • Inductive Load Power: Ensure that the starting power of inductive loads is at least three times the inverter's rated power to prevent damage.
  • Connection Order: Always connect circuits correctly and install circuit breakers for each circuit. The power-on order should be: Battery ON, Inverter ON, then Photovoltaic, Mains, and Load circuit breakers ON. Switch off in reverse order.

10. Frequently Asked Questions

Q: Can the inverter be installed outdoors?
A: The inverter is suitable for mounting on concrete or other non-combustible surfaces only. The recommended installation position is to be adhered to the wall vertically. While not explicitly stated as outdoor-rated, the manual emphasizes non-combustible surfaces and proper air circulation, suggesting a protected environment if installed outside.

11. Warranty and Support

For warranty information, technical support, or service inquiries, please contact your local dealer or the authorized service center. Only qualified service personnel should attempt repairs. If issues persist after following the troubleshooting guide, return the inverter/charger to your dealer or service center for maintenance.

Product Video

Video showcasing the Anern Hybrid Solar Inverter, including unboxing and a 360-degree view of the unit and its connection ports.

Ask a question about this manual

Ask about setup, troubleshooting, compatibility, parts, safety, or missing instructions. Manuals+ will review the question and use this page’s manual context to help answer it.

After a successful submission, we securely hash the supplied account or form email before sending it to Microsoft Advertising for conversion attribution. Privacy details.