EARU Automatic Transfer Switch (ATS) Instruction Manual

Models: EAATS-F-CG-63, EAATS-F-CS-80

1. Introduction

The EARU Automatic Transfer Switch (ATS) is a PC class infrequent change-over switch designed for seamless power transfer between primary and backup power sources. It features a two-station design, commonly used for switching between a primary power source (e.g., City Grid) and a standby power source (e.g., Generator or PV Energy). This device is suitable for AC systems with a frequency of 50-60Hz and rated currents ranging from 10A to 80A.

The primary function of the ATS is to automatically switch to the backup power supply when the main power fails, ensuring continuous operation of connected loads. The switching speed is typically less than 50 milliseconds, minimizing power interruptions.

When both primary and backup power sources are available, the ATS prioritizes the primary power source.

EARU ATS product variants showing City Power, Generator, and Solar Energy connections

Figure 1: EARU ATS product variants illustrating different power source configurations (City Power, Generator, Solar Energy).

2. Safety Information

WARNING: Improper installation or operation can lead to serious injury or equipment damage. Always follow these safety guidelines.

  • For 220V ATS models, do not operate with a voltage lower than 185V. Operating below this threshold can cause the internal coil to overheat and burn out.
  • For 110V ATS models, do not operate with a voltage lower than 90V. Operating below this threshold can cause the internal coil to overheat and burn out.
  • The switch cannot be manually operated when it is in automatic mode. Attempting to do so may damage the internal coil.
  • For 4P ATS models, ensure correct connection of the phase sequence. Incorrect phase sequence can lead to contact burnout.
  • When performing manual operation, the mode selection switch MUST be in the "MANU" (manual) position.
  • The control circuit (TSE) is immediately energized upon power-up. After the changeover is complete, the internal switch will protect the coil in the control circuit. The coil is designed to operate normally at 85%-110% of the rated operating voltage. A consistently low input voltage can cause the coil to overheat and burn out.
  • Only pull the selector switch to the manual position after all power has been cut off for inspection and maintenance. Manual operation may result in excessive silver alloy loss if not performed correctly or too frequently.

3. Product Overview

The EARU ATS is designed for reliability and ease of use. Key components and indicators are detailed below:

Labeled diagram of EARU ATS components including manual handle, indicators, and wiring terminals

Figure 2: Labeled diagram of the Automatic Transfer Switch components.

  • Manual Operation Handle: Used for manual switching between power sources.
  • Backup Auto/Manual Switch: Selects between automatic and manual operation modes.
  • Backup Power Indicator (Red-off): Illuminates when the backup power source is active.
  • Common Power Indicator (Green-on): Illuminates when the common (primary) power source is active.
  • Backup Closing Indicator (II): Indicates the ATS is connected to the backup power.
  • Common Closing Indicator (I): Indicates the ATS is connected to the common (primary) power.
  • Load Output Live Wire (L): Terminal for connecting the live wire of the load.
  • Load Output Neutral Wire (NIL): Terminal for connecting the neutral wire of the load.
  • Backup Power Live Wire (L): Terminal for connecting the live wire of the backup power supply.
  • Backup Power Neutral Wire (NIL): Terminal for connecting the neutral wire of the backup power supply.
  • Common Power Live Wire (L): Terminal for connecting the live wire of the common power supply.
  • Common Power Neutral Wire (NIL): Terminal for connecting the neutral wire of the common power supply.

4. Specifications

Diagram showing dimensions and product parameters table for EARU ATS

Figure 3: Dimensions and key product parameters.

ParameterValue
Pole Number2P / 4P
Rated Operating Current Ie (A)63A / 80A
Rated Insulation Voltage Ui690V
Rated Impulse Withstand Voltage Uimp8kV
Rated Working Voltage UeAC110V / AC220V
Rated Frequency50/60Hz
ClassPC Class (can be switched on a loaded circuit without generating short-circuit current)
Rated Short-Circuit Current Iq50KA
Short Circuit Protection Device (Fuse)RT16-00-63A
Rated Impulse Withstand Voltage8kV
Control CircuitRated Control voltage Us: AC220V, 50Hz. Normal working conditions: 85%-110%Us
Auxiliary CircuitAC220V/110V 50Hz/60Hz Ie=5A
Contactor Change-Over Time<50ms
Operation Change-Over Time<50ms
Return Change-Over Time<50ms
Power off Time<50ms
Change-Over Operation Time<50ms
Mechanical Life≥6000 Times
Electrical Life≥1500 Times
Usage CategoryAC-31B
Width (2P)66mm
Width (4P)102mm
Height106mm
Depth80mm
Terminal Wiring Area1-25mm²
Wire Connection ScrewM5
Torque3.0N.m

5. Installation and Wiring

The EARU ATS is designed for Din Rail mounting. Ensure all power is disconnected before attempting installation or wiring.

5.1 2-Pole (2P) Wiring Diagram

Wiring diagram for a 2-pole EARU ATS, showing connections for backup power, common power, and load

Figure 4: 2-Pole ATS Wiring Diagram.

Connect the Live (L) and Neutral (N) wires from your Backup Power Supply, Common Power Supply, and Load to the corresponding terminals as indicated in Figure 4. Ensure secure connections with the specified torque.

5.2 4-Pole (4P) Wiring Diagram

Wiring diagram for a 4-pole EARU ATS, showing connections for backup power, common power, and load with L1, L2, L3, N

Figure 5: 4-Pole ATS Wiring Diagram.

For 4-Pole models, connect the L1, L2, L3, and Neutral (N) wires from your Backup Power Supply, Common Power Supply, and Load to the corresponding terminals as shown in Figure 5. It is critical to ensure the correct phase sequence for all connections to prevent damage to the contacts.

Important: Use appropriate wire gauges (1-25mm²) and tighten M5 screws to a torque of 3.0N.m.

6. Operation

The ATS offers both automatic and manual operation modes.

6.1 Automatic Mode

In automatic mode, the ATS will manage power transfer without manual intervention. The operational logic is as follows:

Flowchart illustrating the automatic transfer logic of the ATS between primary and backup power

Figure 6: Automatic Transfer Logic.

  1. When the normal (primary) power supply is available and stable, the ATS will use the normal power supply.
  2. If the normal power supply is cut off, the ATS will automatically switch to the backup power supply to maintain power to the load.
  3. If the switch was manually set to the "backup position" and the normal power supply is restored, the ATS will still switch back to the normal power supply automatically.
  4. If both the normal power supply and the backup power supply are cut off, the ATS will not switch to a photovoltaic (solar) power supply, even if it has power. This applies to mains-generator and mains-mains scenarios. Note: For mains-photovoltaic scenarios, DC or low-voltage power needs to be converted to 220V AC through an inverter.

To engage automatic mode, ensure the manual operation handle is in the "AUTO" position.

6.2 Manual Mode

Manual mode allows for direct control over the power source selection. This mode is primarily for inspection, maintenance, or specific operational needs.

  1. Before engaging manual mode, ensure all power to the ATS is cut off.
  2. Pull the selector switch to the "MANU" (manual) position.
  3. Use the manual operation handle to switch between power sources I (Common Power) and II (Backup Power) as needed.
  4. After completing manual operations, return the selector switch from the "MANU" position to the "AUTO" position to re-enable automatic power transfer.

Caution: Do not switch the grey button handle manually while the ATS is in "AUTO" mode. This can cause damage.

Video 1: Demonstration of the Automatic Transfer Switch operation, including manual override.

7. Maintenance

Regular maintenance ensures the longevity and reliable operation of your ATS.

  • Periodically inspect the ATS for any signs of physical damage, loose connections, or discoloration.
  • Ensure all power is disconnected before performing any inspection or maintenance.
  • Only use manual mode for inspection and maintenance after power has been completely cut off. This prevents excessive wear on the contacts.
  • Keep the ATS clean and free from dust and debris.

8. Troubleshooting

If you encounter issues with your ATS, refer to the following common problems and solutions:

  • ATS coil burnout:
    • Cause: Operating the 220V ATS below 185V or the 110V ATS below 90V. Also, attempting manual switching while in automatic mode.
    • Solution: Ensure the input voltage is within the specified operating range (85%-110% of rated voltage). Always switch to "MANU" mode before manual operation.
  • Contact burnout (4P ATS):
    • Cause: Incorrect phase sequence connection.
    • Solution: Verify and correct the phase sequence wiring according to the installation diagrams.
  • Excessive silver alloy loss during manual operation:
    • Cause: Frequent or improper manual switching, especially when power is still connected.
    • Solution: Use manual mode sparingly and only after all power has been disconnected for inspection or maintenance. Always return to "AUTO" mode for normal operation.
  • ATS not switching to PV Energy when both main and backup are off:
    • Cause: The ATS logic for mains-generator and mains-mains scenarios does not automatically switch to PV energy if both primary and backup are unavailable.
    • Solution: Ensure PV energy is properly integrated with an inverter to provide AC power at the correct voltage (e.g., 220V AC) and connected as a designated backup source if this functionality is desired and supported by your specific model.

9. User Tips

  • Compatibility Check: Before installation, ensure the ATS is compatible with your existing power generation systems, such as solar inverters. Verify voltage and current ratings match your setup.
  • Professional Installation: For electrical devices like the ATS, it is highly recommended to have installation and wiring performed by a qualified electrician to ensure safety and proper functionality.
  • Regular Testing: Periodically test the automatic transfer function by temporarily cutting off the primary power to ensure the ATS switches to the backup source as expected.

10. Warranty and Support

For warranty information, technical support, or service inquiries regarding your EARU Automatic Transfer Switch, please contact the manufacturer or your authorized dealer. Ensure you have your product model number (EAATS-F-CG-63 or EAATS-F-CS-80) and purchase details available when seeking assistance.