NOYAFA NF-826 Intelligent Underground Cable Locator User Manual

Model: NF-826

Brand: NOYAFA

1. Safety Precautions

Please read and understand the safety precautions before using or repairing the equipment.

  1. Only professionals can calibrate and repair the detector.
  2. Before each use, the detector and the test lead wire to be used should be inspected for damage. Please ensure that the detector and the test lead wire to be used are in good condition.
  3. When using the detector, the rated voltage of the line under test cannot be greater than 400V.
  4. When the transmitter is connected to a live grid, if the "ground" jack on the transmitter is connected to the protective ground and when there is leakage current in the power supply line, such leakage current and the loop current of the transmitter are combined, which may cause the leakage protection switch to trip, that is, cause the FI/RCD disconnection.

2. Product Overview

2.1 Components and Function Description

The NF-826 Underground & Wall Cable Detector consists of a transmitter, receiver and accessories. The new integrated devices and digital circuit technology are used, so the electrical performance is stable and reliable. According to the change of the signal, the specific location and fault point of the buried cable or pipeline can be detected.

It is suitable for the construction, maintenance and overhaul of power cables, communication cables, electric heating lines and building pipelines.

Diagram showing the key descriptions of the NF-826 Transmitter and Receiver
Figure 2.1: Key Description of Transmitter and Receiver

Transmitter Features:

  • Power on-off button
  • Up/Down buttons for navigation
  • Flashlight switch
  • Set signal code button
  • HD screen
  • Negative electrode interface
  • Positive electrode interface

Receiver Features:

  • Power on-off button
  • Up/Down buttons for navigation
  • Mute/Backlight button
  • Flashlight switch
  • Electrical test pen (NCV) button
  • Menu/Mode switch button
  • HD screen
  • Probe head

2.2 Display Interface

The LCD screens on both the transmitter and receiver provide essential information:

Transmitter Display:

  • Transmission status indication
  • Battery indication
  • Mute indication
  • External voltage indication (DC voltage, AC voltage, value of external voltage)
  • Signal code setting (CODE A/C/E/F/H/L)
  • Transmission signal level indication (LEVEL I/II/III)
  • Code of signal being transmitted
  • Transmitted signal strength

Receiver Display:

  • Receiver Sensitivity (MANUAL/AUTO)
  • Mute function
  • NCV Non-contact test electric pen indicator
  • Auto mode / Manual mode indicator
  • Wire detection signal value
  • Code of signal received
  • Received signal level
  • Received signal strength

2.3 Accessories

The NF-826 package includes the following items:

Image showing all included accessories: Transmitter, Receiver, test clips, test pen, test lead wire, user manual, ground rod, toolkit, graphic carton.
Figure 2.2: Packaging Accessories
Item Quantity Item Quantity
Transmitter 1 set User Manual 1 pcs
Receiver 1 set Ground rod 1 pcs
Test clips (red and black) Each 1 pcs Toolkit 1 pcs
Test pen (red and black) Each 1 pcs Graphic carton 1 pcs
Test lead wire (red and black) Each 1 pcs

Note: The list is for reference only. The accessories actually delivered shall control.

3. Setup and Operation

3.1 General Functions

  • Power-on and Power-off: Press and hold the power key for two seconds to turn on/off the instrument.
  • Setting the Transmitted Signal Level (Transmitter): Press the signal level setup key, then use the up/down keys to select one of three signal levels (I, II, and III). Press the setup key again to confirm.
  • Setting the Transmitted Signal Code (Transmitter): Press the signal code setup key, then use the up/down keys to select one of six signal codes (A/C/E/F/H/L). Press the setup key again to confirm.
  • Start/Pause of Signal Transmission (Transmitter): Press the Start/Pause key to start or suspend signal transmission.
  • Sensitivity Mode Setting (Receiver): After power-on, the receiver defaults to automatic detection mode. Press the mode switch key to toggle between Auto Mode and Manual Mode. In Auto Mode, sensitivity is maximum for quick searches. In Manual Mode, sensitivity can be adjusted (8 levels) for accurate positioning.
  • Voltage Test Function (Transmitter): If connected to a live line with voltage >12V, the transmitter displays the current AC/DC voltage (12-400V) and a lightning symbol.
  • NCV Test Pen Function (Receiver): Press the NCV key on the receiver. Use the probe head near a strong current cable; the receiver will emit a "whoo" sound, stronger with closer proximity.
  • Auto Power-off Function: Both transmitter and receiver will automatically power off after 15 minutes of inactivity.

3.2 Wiring Methods and Operation Steps (Line must be de-energized)

3.2.1 Finding the Direction of Cabling

  1. Connect the positive electrode (red clip) to the target wire and the negative electrode (black clip) to ground. If other cables are near, ground them together.
  2. Power on the transmitter and transmit signal.
  3. Use the receiver's probe head to approach the wall or ground where the target wire is located and move it slowly. The signal bar on the screen will jump, and the receiver will display the signal value and emit a "whoo" sound. The path with the strongest signal indicates the target wire's route.
Diagram showing how to detect the line direction of in-wall, underground, and wall pipe wiring.
Figure 3.1: Detecting Line Direction

Important Note:

The negative electrode of the instrument must be connected to an effective ground wire or the ground, otherwise the detection distance will become very short.

3.2.2 Locating the Breakpoint of the Cable

  1. Connect the positive electrode (red clip) to the broken core of the cable and the negative electrode (black clip) to ground. If other cores are near, ground them together.
  2. Power on the transmitter and transmit signal.
  3. Use the receiver's probe head to approach the target wire and move it slowly. When the signal suddenly attenuates or disappears, that point is the breakpoint of the cable.
Diagram showing how to find breakpoints and shorts in various wiring scenarios.
Figure 3.2: Finding Breakpoints and Shorts

Important Note:

The negative electrode of the instrument must be connected to an effective ground wire or the ground, otherwise the detection distance will become very short.

3.2.3 Locating the Short Circuit Point of the Cable

  1. Use the red and black clips to clamp the short-circuited core of the cable respectively. If there are other excess cores, connect them into the black clip.
  2. Power on the transmitter and transmit signal.
  3. Use the receiver's probe head to approach the target wire and move it slowly. When the signal suddenly attenuates or disappears, that point is the short circuit point of the cable.

Important Notes:

  • In the short circuit point test, the short-circuited core of cable must be known, otherwise the test is impossible.
  • The short-circuit point can be found only when the resistance of the short-circuited line is less than 200Ω, and the short-circuit resistance can be measured by a multimeter.

3.3 Application Examples

3.3.1 Detecting the Direction of Buried Cabling

Perform the operations described in section 3.2.1 above.

Image showing the NF-826 detecting underground cables.
Figure 3.3: Detecting Underground Cables

Caution:

  1. The distance between the grounding terminal and the line under test should be as large as possible; otherwise, the detection depth may be affected.
  2. The depth of detection is greatly affected by the ground conditions (e.g. wet ground, existence of rebars, wire with metal shielding layer or metal pipe sleeve).
  3. The farther away from the transmitter, the weaker the signal strength and the smaller the depth of detection.

3.3.2 Detecting Buried Metal Water Pipe and Metal Heating Pipe

  • The pipes must be made of metal (e.g. steel pipe/iron pipe).
  • The pipes must not be connected to the ground wire, and there should be a large resistance between the pipe and the soil (if the resistance is too small, the detection distance will be small).
  • Connect the target pipe with the positive electrode, and connect the negative electrode to the ground.
  • Perform the operations described in section 3.2.1 above.

Caution:

  1. For safety reasons, power off the electrical equipment.
  2. Select the manual mode of the receiver and set the appropriate sensitivity for accurate positioning of the pipe.
Image showing the NF-826 detecting pipes in walls.
Figure 3.4: Detecting Pipes in Walls

3.3.3 Locating the User Assignment of the Three-phase Power Supply Line on the Same Floor

  • Disconnect the main switch in the distribution box on this floor.
  • Disconnect the neutral line in the distribution box on this floor from the neutral line on other floors.
  • Connect the positive electrode of the transmitter to the three-phase line under test, and ground the negative electrode.
  • Perform the operations described in section 3.2.1 above.
  • After setting up the transmitter, take the receiver to the air switch of the household for detection. If there is a signal, the corresponding line is found; otherwise, the corresponding line is not found.

Warning:

For safety reasons, please be sure to switch off electrical power!

Caution:

The grounding terminal should be fully grounded, and the grounding terminal of the transmitter should have a certain distance from the line under test, otherwise the detection effect may be affected.

3.3.4 Locating the Air Switch or Electric Leakage Switch Corresponding to the Socket

  • Turn off all air switches or electric leakage switches in the distribution box.
  • Connect the positive electrode of the transmitter to the live line of the socket, and the negative electrode to the neutral line.
  • Adjust the transmitter to the appropriate signal level, and adjust the receiver sensitivity to the appropriate level. Use the receiver for detection near the air switch or the electric leakage switch. The switch with the strongest signal is the switch corresponding to the socket.

Warning:

When conducting live line connection with the transmitter, always follow the safety instructions!

Caution:

  • Because of the crosstalk effect of the signal on other lines, there may be signals on other lines, but the signals are relatively weak.
  • During detection, it's better to place the probe head of the receiver at the incoming wire of the switch for a better effect.

3.3.5 Locating the Breakpoint of the Cable Using Two Transmitters (More Accurate)

  • The circuit must be uncharged.
  • Connect the positive electrode of transmitter 1 to one end of the cable under test, and ground the negative electrode.
  • Connect the positive electrode of transmitter 2 to the other end of the cable under test, and ground the negative electrode. Other excess cables must also be grounded (if any).
  • Set the signal code of transmitter 1 to F and the signal code of transmitter 2 to C. (The signal codes should not be consistent).
  • Set the sensitivity of the receiver and detect signals along the path of the target cable. Observe the signal code received by the receiver. When the code changes from F to C, or from C to F, the point is the breakpoint. The sensitivity of the receiver can be reduced for accurate positioning.

Caution:

  • Adjust the transmitter's transmitting power level to accommodate different detection radii.
  • The receiver sensitivity can be adjusted to determine the location of the detection site.

Caution:

  • Ensure that the grounding terminal is well grounded.
  • The contact resistance of line interruption must be greater than 100 kilohm.

3.3.6 Locating the Breakpoint of the Underfloor Heating Cable

  • The circuit must be uncharged.
  • Connect the positive electrode of the transmitter to the underfloor heating cable and ground the negative electrode.
  • Follow the method in section 3.2.2 above to locate the breakpoint.

Caution:

  • If the outside of the heating wire is wrapped with a shielding net, the shielding net cannot be connected with the ground wire. If necessary, disconnect the ground wire of the shielding net.
  • During the process of searching along the line, if the signal of the receiver suddenly attenuates at a certain location, it is the fault location of the line.

3.3.7 Locating the Blockage Point in Buried Non-metallic Pipes

  • The pipe must be made of non-metal material (such as PVC pipe).
  • Pull a cable or metal hose through the pipe until it can no longer stretch.
  • Perform the operations described in section 3.2.1 above. The receiver is used for detection along the laid path. If the signal received by the receiver suddenly attenuates in a certain area, the area is the blockage point.

Caution:

  • If there are other cables in the pipe, disconnect the power supply and ground them together with the negative electrode of the instrument.
  • Ensure that the grounding is good, otherwise, the detection effect may be affected.

3.3.8 Distinguishing Multiple Lines with Multiple Hosts

  • The circuit must be uncharged.
  • The ends of the core wires must be twisted to each other for conduction.
  • Connect the transmitter as shown in the manual.
  • Different hosts transmit signals with different codes, and the receiver receives and recognizes the signals to distinguish different lines.

Tips:

  1. If necessary, multiple transmitters can be purchased to transmit signals with different codes.
  2. If there is only one transmitter, conduct multiple measurements.

4. Improving Detection Depth

4.1 How to Improve the Detection Depth of Uncharged Lines

If the core wire of a multi-core cable is used as the loop, the detection depth is quite limited due to magnetic field distortion. To improve this, specific wiring methods can be used.

Caution:

The distance between the feeder line and the loop should be at least 2 meters.

4.2 How to Improve the Detection Depth of Live Lines

When the transmitter is directly connected to the phase line and neutral line, the signal is conducted on two parallel lines, causing signals to cancel out and limiting detection depth to 0.5 meters. To eliminate this, a cable tray can be used to provide a longer loop, increasing detection depth to 2.5 meters or more.

Warning:

When conducting live line connection with the transmitter, always follow the safety instructions!

Video: Demonstration of the NF-826 in use, including detecting breakpoints and connecting cables.

5. Maintenance and Repair

If the detector is not working properly, please check it according to the following table:

Fault Check Item Measures
Cannot be started Is the battery low? Charge with the USB cable
Whether the contact is good? Reconnect the cable
The transmitter cannot recognize the external voltage Is the test pen broken? Replace the test pen
Is the test pen inserted in place? Insert the test pen in place
Is the test lead wire disconnected? Replace the test lead wire
Is the test lead wire inserted in place? Insert the test lead wire in place
Power off during measurement Is the battery low? Charge with the USB cable
Does the instrument shut down automatically? Restart it
The transmitter cannot receive the signal transmitted by itself Has the transmit key been pressed? Retransmit the signal
Detect if the fuse of the transmitter is disconnected? Send it to a nearby service center

6. Technical Specifications

6.1 Transmitter Parameters

Parameter Value
Output Signal 125kHz
Range of External Voltage Identified DC12-400V±2.5%, AC12-400V(50-60Hz)±2.5%
Screen LCD, with function display and bar charts
Dielectric Strength of External Voltage Max. 400VAC/DC
Overvoltage Level CAT III 300V
Power Supply 3.7V 1400mAh lithium battery
Min. Current 80mA
Max. Current 300mA
Fuse F0.5A500V, 6.3x32mm
Operating Temperature 0°C to 40°C, max. 80% RH (Noncondensing)
Storage Temperature -20°C to +60°C, max. 80% RH (Noncondensing)
Dimension (H x W x D) 156x80x32mm
Weight (Containing battery) 235g

6.2 Receiver Parameters

Parameter Value
Maximum Detection Depth (Single-pole Application) About 0~1m
Maximum Detection Depth (Dual-pole Application) About 0-0.5m
Maximum Detection Depth (Single Loop Line) Up to 2.5m
Maximum Detection Depth (Induction electrical test pen) About 0-5cm
Screen LCD, with function display and bar charts
Power Supply 3.7V 1400mAh lithium battery
Min. Current 100mA
Max. Current 300mA
Operating Temperature 0°C to 40°C, max. 80% RH (Noncondensing)
Storage Temperature -20°C to +60°C, max. 80% RH (Noncondensing)
Dimension (H x W x D) 226x73x29mm
Weight (Containing battery) 235g

7. User Tips

  • For optimal detection depth, ensure the negative electrode of the instrument is always connected to an effective ground wire or the ground. Failure to do so will significantly reduce the detection range.
  • The maximum detection distance varies by application and environmental conditions, ranging from 0.5 meters to 2.5 meters. Adjust sensitivity settings and ensure proper grounding for the best results.
  • Ground conditions, such as wet soil, the presence of rebars, or metal shielding layers, can significantly affect detection depth. Be aware of these factors when performing tests.
  • When locating air switches or electric leakage switches, placing the receiver's probe head at the incoming wire of the switch can yield better results.

8. Warranty and Support

This product is covered by the manufacturer's standard warranty. For any technical support, troubleshooting assistance beyond this manual, or warranty claims, please contact your retailer or the manufacturer's customer service department.

Please retain your proof of purchase for warranty purposes.