1. Introduction
The eletechsup 25IOA08, 25IOB16, and 25IOC32 series are advanced Modbus RS485 IO modules designed for industrial control and automation applications. These modules feature 8, 16, or 32 channels of photoelectrically isolated NPN/PNP inputs and corresponding DMOS PNP outputs. They are ideal for PLC IO expansion, remote control systems, smart home integration, security monitoring, and LED lamp driving.
This manual provides detailed instructions for the setup, operation, and maintenance of your eletechsup Modbus RS485 IO Expansion Board.
2. Specifications
| Feature | Description |
|---|---|
| Model Numbers | 25IOA08 (8-channel), 25IOB16 (16-channel), 25IOC32 (32-channel) |
| Brand | eletechsup |
| Theory | Solid State Relay |
| Power Source | DC 7-25V (compatible with 9V, 12V, 24V) |
| Working Current | 8-50mA |
| Input Channels | 8/16/32 photoelectrically isolated NPN/PNP (optional) |
| Output Channels | 8/16/32 DMOS PNP outputs (high level) |
| Max Output Drive Current | 300mA per channel |
| Output Modes | Open/Close/Toggle (Self-locking)/Latch(Inter-locking)/Momentary (Non-locking)/Delay |
| Modbus Command 1 Support | 03, 06, 16 function codes; Max delay 255 seconds |
| Modbus Command 2 Support | 01, 02, 03, 05, 06, 15, 16 function codes |
| Parallel Devices | Up to 64 devices in Modbus command mode |
| Baud Rate | Default 9600BPS; Settable: 1200/2400/4800/19200/38400/57600/115200BPS |
| Dimensions (Board Only) | 8CH: 61x72x18MM; 16CH: 106x72x18MM; 32CH: 196x72x18MM |
| Dimensions (With DIN Box) | 8CH: 64x80x30MM; 16CH: 109x80x30MM; 32CH: 199x80x30MM |
| Weight (Board Only) | 8CH: 46g; 16CH: 80g; 32CH: 152g |
| Weight (With DIN Box) | 8CH: 85g; 16CH: 145g; 32CH: 247g |
| Certification | CE |
| Protection Feature | Epoxy |
3. Setup and Wiring
Proper wiring is essential for the safe and correct operation of the Modbus IO module. Ensure all power is disconnected before making any connections.
3.1 General Wiring Diagram

This diagram illustrates the basic connections for driving a PLC amplifier board. Ensure correct polarity for power supply and signal lines.
3.2 Modbus RS485 Connection
The module communicates via RS485. Connect the A+ and B- terminals to your RS485 master device (PC via USB-RS485 adapter or PLC). Up to 64 devices can be connected in parallel on the same bus.

3.3 Power Supply and Inputs/Outputs
The module requires a DC 7-25V power supply connected to the VIN and GND terminals. The input channels (IN1-IN32) support NPN/PNP photoelectric isolation, and the output channels (CH1-CH32) are DMOS PNP outputs with a high-level output and 300mA drive current.


3.4 DIP Switch and M0 Port Configuration
- **DIP Switches**: Used for setting the Modbus address and baud rate. Refer to the product's detailed protocol documentation for specific switch configurations.
- **M0 Port**: This port is used for command selection.
- **RESET Port**: Short-circuit the RESET port for 5 seconds to restore the module to factory settings.
4. Operating Instructions
The module operates using Modbus RTU commands over the RS485 bus. You can control outputs, read inputs, and configure settings using a Modbus master device.
4.1 Controlling Switch Outputs (Application 1)
To control the 8/16/32 channel switch outputs via the RS485 bus, send appropriate Modbus commands to the module. The maximum drive current per channel is 300mA, and the high output level is approximately Supply Voltage - 1.2V.

4.2 Reading Switch Inputs (Application 2)
You can read the status of the 8/16/32 channel switch inputs using Modbus commands. The inputs support 3-24V NPN or PNP signals.

4.3 Input Directly Controls Output (Application 3)
In this mode, an input signal directly controls a corresponding output. This functionality requires specific Modbus register configuration. To enable this, you need to configure register 0x00FA (decimal 250).

4.4 Remote IO Control (Application 4)
Two or more modules can be linked via RS485 for remote IO control, where inputs on one board control outputs on another. Ensure all RS485 addresses are unique and configure the Remote IO Sender/Receiver Enable registers (0x00F5 and 0x00F6 respectively).

4.5 Modbus Command Functions
- **Modbus Command 1**: Supports function codes 03 (Read Holding Registers), 06 (Write Single Register), and 16 (Write Multiple Registers).
- **Modbus Command 2**: Supports function codes 01 (Read Coils), 02 (Read Discrete Inputs), 03 (Read Holding Registers), 05 (Write Single Coil), 06 (Write Single Register), 15 (Write Multiple Coils), and 16 (Write Multiple Registers).
- **Output Modes**: The default command supports various output modes including Open, Close, Toggle (Self-locking), Latch (Inter-locking), Momentary (Non-locking), and Delay.
4.6 Modbus Poll Software Demonstration
The following video demonstrates the use of Modbus Poll software to interact with the module, showing how to establish a connection and send commands.
5. Maintenance
The eletechsup Modbus IO module is designed for reliable operation with minimal maintenance. Follow these guidelines to ensure longevity:
- **Keep Clean**: Regularly clean the module and its surroundings to prevent dust and debris accumulation, which can affect performance and heat dissipation. Use a soft, dry cloth.
- **Environmental Conditions**: Operate the module within its specified temperature and humidity ranges. Avoid exposure to extreme temperatures, direct sunlight, or corrosive environments.
- **Secure Connections**: Periodically check all wiring connections to ensure they are secure and free from corrosion. Loose connections can lead to intermittent operation or damage.
- **Power Supply Stability**: Ensure a stable and clean power supply within the specified voltage range (DC 7-25V). Voltage fluctuations can impact the module's performance.
- **Firmware Updates**: Check the manufacturer's website for any available firmware updates. Follow the provided instructions carefully if performing an update.
6. Troubleshooting
If you encounter issues with your Modbus IO module, refer to the following troubleshooting tips:
- **No Power/Indicators Off**:
- Verify the power supply voltage is within DC 7-25V.
- Check power connections for proper polarity and secure contact.
- Ensure the power supply is functional.
- **No RS485 Communication**:
- Check RS485 A+ and B- wiring for correct polarity and secure connections.
- Verify the Modbus address of the module matches the address configured in your master device.
- Confirm the baud rate and parity settings on the module (via DIP switches) match your master device.
- Ensure the RS485 bus is properly terminated if necessary (for long distances or multiple devices).
- Check for bus conflicts if multiple devices are on the same RS485 line.
- **Inputs Not Responding**:
- Verify the input signal voltage is within the 3-24V range.
- Check if the input type (NPN/PNP) of the module matches the sensor/switch connected.
- Ensure input wiring is correct and secure.
- Confirm that the Modbus master is reading the correct input registers.
- **Outputs Not Activating**:
- Verify the load connected to the output does not exceed 300mA.
- Check output wiring for secure connections and correct polarity.
- Confirm that the Modbus master is writing to the correct output registers/coils.
- If using direct input-to-output control (Application 3), ensure register 0x00FA (250) is configured correctly.
- If using remote IO control (Application 4), verify sender/receiver enable registers (0x00F5, 0x00F6) and RS485 addresses are correctly set.
- **Module Overheating**:
- Ensure adequate ventilation around the module.
- Verify that the output loads do not exceed the maximum current rating.
- Check the ambient temperature to ensure it's within the operating range.
If the problem persists after checking these points, consider restoring factory settings using the RESET port or contacting technical support.
7. User Tips
To maximize the performance and reliability of your eletechsup Modbus IO module, consider these user tips:
- **Documentation**: Always refer to the detailed Modbus protocol documentation provided by eletechsup for specific register addresses, command structures, and DIP switch settings.
- **Testing**: Before deploying in a critical application, thoroughly test all inputs, outputs, and communication functions in a controlled environment.
- **Grounding**: Ensure proper grounding practices are followed in your installation to minimize electrical noise and improve signal integrity.
- **Cable Quality**: Use high-quality shielded twisted-pair cables for RS485 communication, especially over longer distances, to prevent interference.
- **Software Tools**: Utilize Modbus master software (like Modbus Poll) during development and troubleshooting to easily monitor and control the module.
- **NPN vs. PNP**: Double-check the input type (NPN or PNP) of your sensors and configure the module accordingly to avoid damage or incorrect readings.
8. Warranty and Support
For warranty information, technical support, or further assistance, please contact the seller or manufacturer directly. Keep your purchase records handy for any support inquiries.