1. Introduction
The EARU 3-Phase Automatic Transfer Switch (ATS) is a microcontroller-based device designed to provide uninterrupted power by automatically switching between different power sources. It incorporates advanced protection features including overvoltage, undervoltage, and overcurrent protection, ensuring the safety and stability of your electrical system. This manual provides essential information for the safe installation, operation, and maintenance of your ATS device.
2. Safety Information
WARNING: Electrical shock hazard. Installation and servicing should only be performed by qualified personnel.
- Always disconnect power before installing or servicing the device.
- Ensure all wiring connections are secure and comply with local electrical codes.
- Do not operate the device if it appears damaged.
- Verify voltage and current ratings match your application requirements.
- Keep the device away from moisture and extreme temperatures.
3. Product Overview
3.1 Key Features
- Automatic Changeover Switch with "Priority" phase selection.
- Microcontroller-based for precise control.
- Parameter setting via front panel buttons.
- Overvoltage and Undervoltage protection.
- Overcurrent protection.
- LED indication for operating voltage and fault status.
- Din-rail mounting for easy installation.
- Adjustable time delays for reclosing and return to priority phase.
3.2 Components and Dimensions
The ATS features a compact design suitable for Din-rail mounting. The front panel includes digital displays for voltage and current, along with control buttons and status indicators.




4. Specifications
| Parameter | Value |
|---|---|
| Supply Terminals | N, L1, L2, L3 |
| Rated Supply Voltage | AC 3*220V (N-L1/L2/L3) |
| Rated Frequency | 40/50/60/70Hz |
| Umax Setting Range (Overvoltage) | 230-300V |
| Umin Setting Range (Undervoltage) | 140-210V |
| Auto-Reclosing Delay (Ton) | 1-600s |
| Return Delay to Priority Phase | 1-600s |
| Switch Delay to Reserve Phases | <0.2s |
| Voltage Hysteresis | 5V |
| Overvoltage Trip Delay | 0.1s; >350V: 0.02s |
| Undervoltage Trip Delay | 0.1s; >350V: 0.02s |
| Voltage Accuracy | <1% |
| Max. Operating Phase Voltage | 350V |
| Rated Operating Current | 63A / 80A / 100A |
| Storage Temperature | -25°C ~ +55°C |
5. Installation and Wiring
The ATS is designed for Din-rail mounting. Ensure adequate space for ventilation and wiring connections.
5.1 Mounting
Snap the device onto a standard 35mm DIN rail. Ensure it is securely fastened.

5.2 Wiring Diagram
Connect the power sources and load according to the diagram below. Pay close attention to the Neutral (N) and Live (L1, L2, L3) connections for both input and output.

6. Operation
6.1 Display and Indicators
The ATS features multiple digital displays for real-time monitoring of input voltages (L1-IN, L2-IN, L3-IN) and output current (Output A). Status indicators (L1, L2, L3, Fault) provide visual feedback on the operational state.

6.2 Button Functions
- M (Menu/Selection): Press to enter the menu for parameter settings or to confirm a selection.
- Up Arrow (Digit+/Up): Used to increase values or navigate up in menu options.
- Down Arrow (Digit-/Down): Used to decrease values or navigate down in menu options.
- Power Button (Manual ON/OFF): Press to manually switch the device ON or OFF.
6.3 Parameter Setting (Priority Phase)
The ATS allows you to set a priority phase. When the priority phase recovers to normal voltage, the switch will automatically transfer back to that power resource.

Steps to Set Parameters:
- Press the M button to enter the menu.
- Use the Up/Down arrows to navigate through parameters (e.g., Power-on delay, Protection recovery delay, Overvoltage/Undervoltage values, Overcurrent values).
- Press M again to select a parameter for editing.
- Use the Up/Down arrows to adjust the value.
- Press M to confirm the new value and move to the next parameter or exit the menu.
6.4 Overcurrent Protection
The ATS is built with a magnetic interlocking relay (63A/100A models) designed to prevent burnout under high current conditions. In the event of overvoltage, undervoltage, or a power supply interruption, the switch will automatically transfer to an alternative power supply to protect connected loads.

6.5 Product Demonstration Video
7. Maintenance
- Regular Inspection: Periodically check all wiring connections for tightness and signs of wear or damage.
- Cleaning: Keep the device clean and free from dust and debris. Use a dry, soft cloth for cleaning. Do not use liquid cleaners.
- Environmental Conditions: Ensure the operating environment remains within the specified temperature and humidity ranges.
8. Troubleshooting
| Problem | Possible Cause | Solution |
|---|---|---|
| Device not powering on | No input power; Loose connections | Check power supply; Verify all wiring connections are secure. |
| No automatic transfer | Priority phase settings incorrect; Fault in power source | Review and adjust priority phase settings; Check health of power sources. |
| Overvoltage/Undervoltage fault | Input voltage outside set limits | Check input voltage; Adjust Umax/Umin settings if necessary. |
| Overcurrent fault | Load current exceeds set limit | Reduce load; Check for short circuits; Adjust overcurrent setting if appropriate for the load. |
| Inaccurate voltage/current display | Calibration needed | Manually calibrate voltage and current as per instructions (refer to Figure 7). |
9. User Tips
- Optimal Settings: Take time to properly set the Umax, Umin, and overcurrent protection values to match your specific electrical system and connected loads. Incorrect settings can lead to nuisance tripping or insufficient protection.
- Delay Adjustments: Utilize the adjustable auto-reclosing and return delays to prevent rapid switching during momentary power fluctuations, which can stress connected equipment.
- Regular Monitoring: Periodically observe the real-time voltage and current displays to ensure stable operation and identify any potential issues early.