Contents

GEYA GRT8-B1 Off Delay Time Relay User Manual

Model: GRT8-B1

1. Introduction

The GEYA GRT8-B1 is an electronic off-delay time relay designed for various industrial and domestic applications where precise timing control is required. This device is suitable for functions such as pump decay time after heating shutdown or controlling fans. It features a wide voltage range, multiple time scales, and easy DIN rail mounting.

2. Product Overview

The GRT8-B1 is a compact, 1-module device designed for standard DIN rail installation. It features two potentiometers for time setting and percentage adjustment, along with LED indicators for operational status.

Front view of GEYA GRT8-B1 Off Delay Time Relay showing terminals, potentiometers, and LED indicators.

Figure 1: Front view of the GEYA GRT8-B1 Off Delay Time Relay.

Technical parameter diagram of GRT8-B1, labeling trigger, supply terminals, LEDs, time selection, and model number.

Figure 2: Technical Parameter Diagram with labeled components.

  • A1(+) S A2(-): Trigger Terminal and Supply Terminal
  • Un: Supply LED Indicator (Green)
  • R: Output LED Indicator (Red)
  • Knob 1: 10 Time Range Selection
  • Knob 2: Time Percentage Setting %
  • GRT8-B1: Model Number
  • 15 16 18: 1SPDT Output (16A/AC1) Terminals

3. Installation

3.1 Mounting

The GRT8-B1 is designed for standard 18mm DIN rail mounting. Ensure the DIN rail is securely fastened in a suitable enclosure.

Image showing the GRT8-B1 relay being installed on a standard DIN rail.

Figure 3: DIN Rail Installation.

Diagram showing the dimensions of the GRT8-B1 relay: 90mm length, 18mm width, 64mm height.

Figure 4: Dimensions of the GRT8-B1 relay (90mm x 18mm x 64mm).

3.2 Wiring Diagram

Refer to the following wiring diagrams for proper connection of the GRT8-B1. Ensure all connections are secure and comply with local electrical codes.

Wiring diagrams for GRT8-B1 and GRT8-B2 delay off functions, showing connections for A1, S, A2, and output terminals 15, 16, 18 (and 25, 26, 28 for B2).

Figure 5: Delay Off Function & Wiring Diagram for GRT8-B1 and GRT8-B2.

Example wiring diagram for GRT8-B1 AC230V to turn off a lamp after a period of time, showing L and N connections, trigger, and lamp load.

Figure 6: Relay Wiring Example for GRT8-B1 AC230V (Turn off load after a period of time).

Wiring Steps:

  1. Connect the Live (L) and Neutral (N) wires to the appropriate power supply terminals (Un).
  2. Connect the trigger signal to terminal 'S'.
  3. Connect the load (e.g., lamp, contactor, heater, fans) to the output terminals (15, 16, 18) as per the desired normally open (NO) or normally closed (NC) configuration. For GRT8-B1, output is 1SPDT (1NO1NC).
  4. Ensure the voltage matches the selected model (AC/DC12-240V or AC230V).

4. Operating Instructions

4.1 Function: Delay Off (GRT8-B)

When the relay power is turned ON, the connected load will turn on simultaneously. The relay then starts delaying time. After reaching the set time, the load will turn off.

4.2 Time Setting

The GRT8-B1 features two potentiometers for setting the delay time:

Diagram showing two knobs for time setting: Knob 1 for time range (0.1s to 10 days) and Knob 2 for percentage (10% to 100%). Includes an example table.

Figure 7: How to Set Time using Knob 1 (Time Range) and Knob 2 (Percentage).

Time Setting Examples
Example TimeKnob 1 (Time Range)Knob 2 (Percentage)
5 minutes10m (1-10min range)50%
15 minutes1h (1-10hr range)25%

Time Ranges (Knob 1):

  • 0.1-1s
  • 1-10s
  • 6-60s
  • 1-10min
  • 6-60min
  • 1-10hr
  • 0.1-1day
  • 1-10day
  • Only ON
  • Only OFF

4.3 Indicator Light Explanation

The GRT8-B1 uses two LEDs to indicate its operational status:

Diagram explaining LED indicators: Green LED (Un) for supply power normally working, Red LED (R) for relay in delay status (flashing) and off after delay.

Figure 8: Indicator Light Explanation.

  • Green LED (Un): Indicates that the supply power is normally working (always ON).
  • Red LED (R):
    • Keep Flashing: The relay is in delay status.
    • OFF: After reaching the set delay time, the Red LED will turn off.

5. Specifications

FeatureDescription
ModelGRT8-B1
FunctionDelay Off
Voltage RangeAC/DC12-240V or AC230V
Output Contact1SPDT (1NO1NC) or 2SPDT (2NO2NC)
Rated Current16A (AC1)
Time Scale0.1s - 10 days (divided into 10 ranges)
Mounting1 MODULE 18mm, DIN rail mounting
Dimensions (L x W x H)90mm x 18mm x 64mm
MaterialPC
ColorWhite
Package Dimensions (L x W x H)10cm x 7cm x 2cm
Package Weight0.088 kg
OriginMainland China

6. Maintenance

The GEYA GRT8-B1 is designed for reliable operation with minimal maintenance. However, regular checks can ensure optimal performance and longevity:

  • Cleaning: Keep the relay free from dust and debris. Use a soft, dry cloth for cleaning. Do not use abrasive cleaners or solvents.
  • Connections: Periodically check all wiring connections to ensure they are tight and secure. Loose connections can lead to intermittent operation or overheating.
  • Environment: Ensure the operating environment is within suitable conditions to prevent damage to the electronic components.
  • Visual Inspection: Inspect the relay for any signs of physical damage, discoloration, or burning, which may indicate a fault.

Always disconnect power before performing any maintenance or inspection.

7. Troubleshooting

If you encounter issues with your GRT8-B1 relay, consider the following troubleshooting steps:

  • Relay not activating/deactivating:
    • Check if the power supply (Un) is correctly connected and within the specified voltage range. The Green LED should be ON.
    • Verify the trigger signal 'S' is correctly applied and functioning.
    • Ensure the time setting (Knob 1 and Knob 2) is configured correctly and not set to "Only ON" or "Only OFF" unintentionally.
    • Inspect wiring for loose connections or damage.
  • Incorrect timing:
    • Re-check the settings on both time potentiometers (Knob 1 for range, Knob 2 for percentage).
    • Ensure the selected time range on Knob 1 is appropriate for the desired delay.
  • Red LED (R) not flashing during delay:
    • Confirm the relay is receiving power (Green LED ON) and a trigger signal.
    • If the Red LED is constantly OFF, the delay might have already completed, or the relay is not entering the delay state.

If problems persist after following these steps, contact customer support for further assistance.

8. User Tips

  • Test Settings: Before deploying the relay in a critical application, always test your time settings with a simple load to ensure it functions as expected.
  • Voltage Compatibility: Double-check that the specific model you have (AC/DC12-240V or AC230V) matches your power supply to prevent damage.
  • Clear Labeling: For complex setups, clearly label all wires and connections to simplify future maintenance or troubleshooting.

9. Warranty and Support

For warranty information, technical support, or service inquiries, please refer to the seller's specific terms and conditions or contact the manufacturer directly. Keep your purchase receipt as proof of purchase.