SUMRY NM-ECO-LV Series Hybrid Solar Inverter (3.6KW/4.2KW/6.2KW)

Contents

SUMRY Hybrid Solar Inverter User Manual

Model: NM-ECO-LV Series (3.6KW/4.2KW/6.2KW)

Brand: SUMRY

1. Introduction

1.1 About This Manual

This manual describes the assembly, installation, operation, and troubleshooting of the SUMRY Hybrid Solar Inverter. Please read this manual carefully before installations and operations. Keep this manual for future reference.

This manual provides safety and installation guidelines as well as information on tools and wiring.

1.2 Features

  • Pure sine wave inverter
  • Configurable input voltage range for home appliances and personal computers via LCD setting
  • Configurable battery charging current based on applications via LCD setting
  • Configurable AC/Solar Charger priority via LCD setting
  • Compatible with mains voltage or generator power
  • Auto restart while AC is recovering
  • Overload, over temperature, and short circuit protection
  • Smart battery charger design for optimized battery performance
  • Cold start function
  • Built-in 120A MPPT Solar charge (max 4200W for 3.6KW, max 6000W for 6.2KW)
  • High PV input voltage range (60-500VDC)
  • AC output Voltage 120VC (for some models)
  • WIFI & GPRS available for iOS and Android (optional)
  • Dual output

1.3 Basic System Architecture

The following illustration shows the basic application for this inverter/charger. It includes connections for solar panels, utility grid, generator, lithium battery, and home appliances. The inverter can power various appliances in home or office environments, including motor-type appliances like tube lights, fans, refrigerators, and air conditioners.

Basic System Architecture Diagram
Diagram illustrating the basic system architecture of the hybrid solar inverter, showing connections to solar panels, utility grid, generator, battery, and home appliances.
On/Off Grid Solar Inverter Wiring Diagram
Detailed wiring diagram for an On/Off Grid Solar Inverter system, including solar panels, AC input (generator or utility), battery, and AC output to home appliances.

2. Safety Instructions

WARNING: This chapter contains important safety and operating instructions. Read and keep this manual for future reference.

  1. Before using the unit, read all instructions and cautionary markings on the unit, the batteries, and all appropriate sections of this manual.
  2. Do not disassemble the unit. Take it to a qualified service center when service or repair is required. Incorrect re-assembly may result in a risk of electric shock or fire.
  3. To reduce risk of electric shock, disconnect all wirings before attempting any maintenance or cleaning. Turning off the unit will not reduce this risk.
  4. CAUTION – Only qualified personnel can install this device with battery. NEVER charge a frozen battery.
  5. For optimum operation of this inverter/charger, please follow required specifications to select appropriate cable size. It's very important to correctly operate this inverter/charger.
  6. Be very cautious when working with metal tools on or around batteries. A potential risk exists to drop a tool to spark or short circuit batteries or other electrical parts and could cause an explosion.
  7. Please strictly follow installation procedure when you want to disconnect AC or DC terminals. Please refer to INSTALLATION section of this manual for the details.
  8. One piece of 150A fuse is provided as over-current protection for the battery supply.
  9. GROUNDING INSTRUCTIONS - This inverter/charger should be connected to a permanent grounded wiring system. Be sure to comply with local requirements and regulation to install this inverter.
  10. NEVER cause AC output and DC input short circuited. Do NOT connect to the mains when DC input short circuits.
  11. Warning!! Only qualified service persons are able to service this device. If errors still persist after following troubleshooting table, please send this inverter/charger back to local dealer or service center for maintenance.

3. Product Overview

The inverter features a clear LCD display and various ports for connectivity and power management.

Product Overview
Various views of the SUMRY Hybrid Solar Inverter, showing its front, back, side, and perspective.
Inverter Ports and Controls
Detailed view of the inverter's rear panel, labeling AC input, Main output, Second output, Battery communication (RS-485), WIFI communication (RS-232), PV input, and Battery input ports.

3.1 Components and Indicators

No.Component/Indicator
1LCD display
2Status indicator
3Charging indicator
4Fault indicator
5Function buttons
6Power on/off switch
7AC input
8Main output
9Second output
10Battery input
11PV input
12Anti dust kit
13WIFI communication/RS-232 port
14Battery communication/RS-485 port

3.2 Product Demonstration

Video demonstrating the physical overview and basic wiring connections of the SUMRY Hybrid Solar Inverter.

4. Installation

4.1 Unpacking and Inspection

Before installation, inspect the unit. Be sure that nothing inside the package is damaged. You should have received the unit and a user manual.

4.2 Preparation

Before connecting any lines, remove the screws under the machine and remove the bottom cover plate.

4.3 Mounting the Unit

Consider the following points before selecting where to install:

  • Do not mount the inverter on flammable construction materials.
  • Mount on a solid surface.
  • Install this inverter at eye level in order to allow the LCD display to be read at all times.
  • For proper air circulation to dissipate heat, allow a clearance of approximately 20 cm to the side and approximately 50 cm above and below the unit.
  • The ambient temperature should be between 0°C and 55°C to ensure optimal operation.
  • The recommended installation position is to be adhered to the wall vertically.
  • Make sure that other objects and surfaces are left with enough space from the machine to ensure adequate heat dissipation and that there is enough room to remove the wires.

WARNING: SUITABLE FOR MOUNTING ON CONCRETE OR OTHER NON-COMBUSTIBLE SURFACE ONLY.

Install the unit by screwing two M6 screws.

4.4 Battery Connection

CAUTION: For safety operation and regulation compliance, it's requested to install a separate DC over-current protector or disconnect device between battery and inverter. It may not be requested to have a disconnect device in some applications, however, it's still requested to have over-current protection installed. Please refer to typical amperage in below table as required fuse or breaker size.

WARNING! All wiring must be performed by a qualified personnel.

WARNING! It's very important for system safety and efficient operation to use appropriate cable for battery connection. To reduce risk of injury, please use the proper recommended cable as below.

ModelWire SizeCable (mm²)Torque value (max)
3.6KW/4.2KW/6.2KW1 x 2AWG252 Nm

Please follow below steps to implement battery connection:

  1. Remove insulation sleeve 18 mm for positive and negative conductors.
  2. Suggest to put bootlace ferrules on the end of positive and negative wires with a proper crimping tool.
  3. Connect all battery packs as shown in the chart below.
Battery Pack Connection Diagram
Diagram showing how to connect multiple 12V battery packs in series for 3.6KW/4.2KW and 6.2KW inverters.
  1. Insert the battery wires flatly into battery connectors of inverter and make sure the bolts are tightened with torque of 2 Nm in clockwise direction. Make sure polarity at both the battery and the inverter/charger is correctly connected and conductors are tightly screwed into the battery terminals. Recommended tool: #2 Pozi Screwdriver.

WARNING: Shock Hazard. Installation must be performed with care due to high battery voltage in series.

CAUTION!! Before making the final DC connection or closing DC breaker/disconnector, be sure positive (+) must be connected to positive (+) and negative (-) must be connected to negative (-).

4.4.1 Lithium Battery Communication and Setting

The communication between the battery and the inverter can be realized through the battery communication interface, so that the inverter and the lithium battery can exchange information (Baud rate: 9600).

If choosing a lithium battery for the inverter, only lithium batteries that have been matched with BMS communication protocol are allowed.

  1. Connect the battery according to the recommended battery cable specifications.
  2. Insert the ring terminal of the battery cable into the battery connector of the inverter flatly, and ensure that the bolts are tightened with a torque of 2-3 Nm. Make sure that the polarities of the battery and inverter are connected correctly, and that the ring terminal is tightened with the battery terminal.
  3. Connect one side of RJ45 cable to the BMS communication port of inverter.
  4. Insert the other side of RJ45 cable into RS485 communication port on lithium battery.

NOTE: If you choose a lithium battery, please make sure to connect the battery and inverter with BMS communication cable, and select the battery type as "LIB-485" mode.

RJ45 Pin Definition
Pin numberPort definitions
1RS485B
2RS485A
3NG
4NG
5NG
6NG
7RS485A
8RS485B
LCD Settings for Lithium Battery

In order to communicate with the lithium battery BMS, you should press the "ENTER" button for a long time, and set the battery type as "LIB-485" in program 05. Then select the matching battery protocol in Program 43.

CAUTION: When the battery type is set to "LIB-485", the setting items 12, 13 and 29 are displayed in percentage. When the battery type is set to "LIB-485", the user cannot modify the maximum charging current. When communication fails, the inverter will cut off the output.

4.5 AC Input/Output Connection

CAUTION!! Before connecting to AC input power source, please install a separate AC breaker between inverter and AC input power source. This will ensure the inverter can be securely disconnected during maintenance and fully protected from over current of AC input. The recommended spec of AC breaker is 32A for 3.6KW/4.2KW and 50A for 6.2KW.

CAUTION!! There are two terminal blocks with “IN” and “OUT” markings. Please do NOT mis-connect input and output connectors.

WARNING! All wiring must be performed by a qualified personnel.

WARNING! It's very important for system safety and efficient operation to use appropriate cable for AC input connection. To reduce risk of injury, please use the proper recommended cable size as below.

Suggested cable requirement for AC wires

ModelGaugeCable (mm²)Torque Value
3.6KW/4.2KW12 AWG41.2 Nm
6.2KW10 AWG61.2 Nm

Please follow below steps to implement AC input/output connection:

  1. Before making AC input/output connection, be sure to open DC protector or disconnector first.
  2. Remove insulation sleeve 10mm for six conductors. And shorten phase L and neutral conductor N 3 mm.
  3. Insert AC input wires according to polarities indicated on terminal block and tighten the terminal screws. L→LINE (brown or black), N→Neutral (blue).

WARNING: Be sure that AC power source is disconnected before attempting to hardwire it to the unit.

  1. Then, insert AC output wires according to polarities indicated on terminal block and tighten terminal screws. L→LINE (brown or black), N→Neutral (blue).
  2. Make sure the wires are securely connected.

CAUTION: Appliances such as air conditioner are required at least 2~3 minutes to restart because it's required to have enough time to balance refrigerant gas inside of circuits. If a power shortage occurs and recovers in a short time, it will cause damage to your connected appliances. To prevent this kind of damage, please check manufacturer of air conditioner if it's equipped with time-delay function before installation. Otherwise, this inverter/charger will trig overload fault and cut off output to protect your appliance but sometimes it still causes internal damage to the air conditioner.

4.6 PV Connection

CAUTION: Before connecting to PV modules, please install separately a DC circuit breaker between inverter and PV modules.

WARNING! It's very important for system safety and efficient operation to use appropriate cable for PV module connection. To reduce risk of injury, please use the proper recommended cable size as below.

Suggested cable requirement for PV wires

ModelWire SizeCable (mm²)Torque value (max)
3.6KW/4.2KW/6.2KW1 x 12AWG41.2 Nm

PV Module Selection

When selecting proper PV modules, please be sure to consider below parameters:

  1. Open circuit Voltage (Voc) of PV modules not exceeds max. PV array open circuit voltage of inverter.
  2. Open circuit Voltage (Voc) of PV modules should be higher than min. battery voltage.
INVERTER MODEL3.6KW/4.2KW6.2KW
Max. PV Array Open Circuit Voltage500Vdc
PV Array MPPT Voltage Range60Vdc~450Vdc
Solar Panel Spec. (reference)SOLAR INPUT (Min in serial: 6 pcs, max. in serial: 13 pcs)Q'ty of panelsTotal input power
250Wp
Vmp: 30.1Vdc
Imp: 8.3A
Voc: 37.7Vdc
Isc: 8.4A
Cells: 60
6 pcs in serial6 pcs1500W
8 pcs in serial8 pcs2000W
12 pcs in serial12 pcs3000W
13 pcs in serial13 pcs3250W
8 pieces in serial and 2 sets in parallel16 pcs4000W
10 pieces in serial and 2 sets in parallel20 pcs5000W
12 pieces in serial and 2 sets in parallel24 pcs6500W
10 pieces in serial and 3 sets in parallel30 pcs7500W

PV Module Wire Connection

Please follow below steps to implement PV module connection:

  1. Remove insulation sleeve 10 mm for positive and negative conductors.
  2. Suggest to put bootlace ferrules on the end of positive and negative wires with a proper crimping tool.
  3. Check correct polarity of wire connection from PV modules and PV input connectors. Then, connect positive pole (+) of connection wire to positive pole (+) of PV input connector. Connect negative pole (-) of connection wire to negative pole (-) of PV input connector. Recommended tool: 4mm blade screwdriver.

4.7 Final Assembly

After connecting all wirings, please put the bottom cover back by screwing two screws.

4.8 Communication Connection

4.8.1 Wi-Fi Cloud Communication (option)

Please use the supplied communication cable to connect to the inverter and Wi-Fi module. Download the APP and install it from the APP store, and refer to the "Wi-Fi Plug Quick Installation Guideline" to set up the network and register. The inverter status will be shown by mobile phone APP or webpage of a computer.

4.8.2 GPRS Cloud Communication (option)

Please use the supplied communication cable to connect to the inverter and GPRS module, and then apply external power to the GPRS module. Download the APP and install it from the APP store, and refer to the "GPRS RTU Quick Installation Guideline" to set up the network and register. The inverter status will be shown by mobile phone APP or webpage of a computer.

Monitor and Control via Smartess App
Image showing the inverter connected to a mobile phone via an optional WiFi/GPRS module for monitoring and control through the Smartess App.

5. Operation

5.1 Power ON/OFF

Once the unit has been properly installed and the batteries are connected, simply press the On/Off switch (located on the bottom of the case) to turn on the unit.

5.2 Operation and Display Panel

The operation and display panel is on the front panel of the inverter. It includes three indicators, four function keys, and an LCD display, indicating the operating status and input/output power information.

LED Indicator

LED IndicatorColorStatusMessages
INV/ACGreenSolid OnOutput is powered by utility in Line mode.
FlashingOutput is powered by battery or PV in battery mode.
CHGGreenSolid OnBattery is fully charged.
FlashingBattery is charging.
FAULTRedSolid OnFault occurs in the inverter.
FlashingWarning condition occurs in the inverter.

Function Keys

Function KeyDescription
ESCTo exit setting mode
UPTo go to previous selection
DOWNTo go to next selection
ENTERTo confirm the selection in setting mode or enter setting mode

5.3 LCD Display Icons

The LCD display provides various information about the inverter's status and operation.

Input Source Information

  • Indicates the AC input.
  • Indicates the PV input.
  • Indicates input voltage, input frequency, PV voltage, charger current (if PV in charging for 3.6KW models), charger power, battery voltage.

Configuration Program and Fault Information

  • Indicates the setting programs.
  • Indicates the warning and fault codes.
  • Warning: Flashing with warning code.
  • Fault: Lighting with fault code.

Output Information

  • Indicates output voltage, output frequency, load percent, load in VA, load in Watt, and discharging current.

Battery Information

  • Battery icon with charge level.

Load Information

  • Indicates overload.

Mode Operation Information

  • Indicates unit connects to the mains.
  • Indicates unit connects to the PV panel.
  • Indicates load is supplied by utility power.
  • Indicates the utility charger circuit is working.
  • Indicates the DC/AC inverter circuit is working.

Mute Operation

  • Indicates unit alarm is disabled.

5.4 LCD Setting

After pressing and holding the ENTER button for 3 seconds, the unit will enter setting mode. Press “UP” or “DOWN" button to select setting programs. And then, press "ENTER" button to confirm the selection or ESC button to exit.

The manual provides detailed tables for various LCD settings, including output source priority, maximum charging current, AC input voltage range, battery type, auto restart settings, output frequency, output voltage, maximum utility charging current, setting voltage point back to utility source, power point of dual output function, bulk charging voltage, floating charging voltage, low DC cut-off voltage, battery equalization, equalization interval, equalization activated immediately, GRID-tie operation, GRID-tie current, LED pattern light, dual output, dual output functional voltage point, lithium battery protocol, and delayed grid access.

5.5 Operating Mode Description

The inverter supports various operating modes:

  • Standby Mode: The inverter is not turned on yet, but it can charge batteries without AC output.
  • Line Mode: The unit will provide output power from the mains and will also charge the battery.
  • Grid-Tie Operation: When working in Grid-Tie mode, the unit will flash.
  • Battery Mode: The unit will provide output power from the battery and PV.

5.6 RGB Light (option)

  • Battery Mode: Red Light
  • Utility Mode: Blue Light
  • PV Mode: Purple Light

5.7 Battery Equalization

Battery equalization reverses the buildup of negative chemical effects like stratification and removes sulfate crystals, which can reduce battery capacity. It is recommended to equalize the battery periodically.

How to Apply Equalization Function

You must enable the battery equalization function in monitoring LCD setting program 30 first. Then, you may apply this function in the device by either one of the following methods:

  1. Setting equalization interval in program 35.
  2. Active equalization immediately in program 36.

When to Equalize

In the float stage, when the setting equalization interval (battery equalization cycle) is arrived, or equalization is active immediately, the controller will start to enter the Equalize stage.

Equalize Charging Time and Timeout

In the Equalize stage, the controller supplies power to charge the battery until the battery voltage reaches the equalization voltage. Constant-voltage regulation is applied to maintain the battery voltage at the equalization voltage. The battery remains in the Equalize stage until the set battery equalized time is reached.

If the battery equalized time expires and the battery voltage does not reach the equalization voltage point, the charge controller will extend the battery equalized time until the battery voltage achieves the equalization voltage. If the battery voltage is still lower than the battery equalization voltage when the battery equalized timeout setting is over, the charge controller will stop equalization and return to the float stage.

5.8 Mains and Lithium Battery Activation Function

  1. After 90s of mains power connection to the inverter, the machine is connected to the mains and starts to work.
  2. If the inverter is in lithium battery mode (item 05 is Llb or Llb-485), and the mains is connected but the battery is not connected, the mains activation function is automatically enabled.

6. Maintenance

6.1 Clearance and Maintenance for Anti-Dust Kit

6.1.1 Overview

Every inverter is already installed with an anti-dust kit from the factory. The inverter will automatically detect this kit and activate an internal thermal sensor to adjust the internal temperature. This kit also keeps dust out of your inverter and increases product reliability in harsh environments.

6.1.2 Clearance and Maintenance Steps

  1. Loosen the screw in a counterclockwise direction on the top of the inverter.
  2. Remove the dustproof case and take out the air filter foam.
  3. Clean the air filter foam and dustproof case. After cleaning, re-assemble the dust-kit back to the inverter.

NOTICE: The anti-dust kit should be cleaned from dust every one month.

7. Troubleshooting

7.1 Fault Reference Code

The following table lists common fault codes, their explanations, and recommended actions.

Fault CodeFault EventExplanation / Possible causeWhat to do
01Fan is locked when inverter is off.Replace the fan.
02Over temperatureTemperature of internal converter component is over 120°C. Internal temperature of inverter component is over 100°C.Check whether the air flow of the unit is blocked or whether the ambient temperature is too high.
03Battery voltage is too highBattery is over-charged.Return to repair center. Check if spec and quantity of batteries are meet requirements.
04Battery voltage is too lowThe battery voltage is too low (<1.91V/Cell)1. Re-charge battery. 2. Replace battery.
05Output short circuited or over temperature is detected by internal converter components.Output short circuited.Check if wiring is connected well and remove abnormal load.
06/58Output voltage is too high / Output voltage is too lowOutput abnormal (Inverter voltage below than 190Vac or is higher than 260Vac)1. Reduce the connected load. 2. Return to repair center.
07Overload time outOverload error. The inverter is overload 110% and time is up.Reduce the connected load by switching off some equipment.
08/09/53/57Bus voltage is too high / Bus soft start failed / Inverter soft start failed / Current sensor failedInternal components failed.Return to repair center.
51Over current or surge.Over current or surge.Restart the unit, if the error happens again, please return to repair center.
52Bus voltage is too low.Bus voltage is too low.Restart the unit, if the error happens again, please return to repair center.
55Over DC voltage in AC outputOutput voltage is unbalanced.Restart the unit, if the error happens again, please return to repair center.
59PV voltage is over limitation

7.2 Warning Indicator

The following table lists warning events, their audible alarms, and corresponding icon flashing.

Warning CodeWarning EventAudible AlarmIcon flashing
01Fan is locked when inverter is on.Beep three times every second01
03Battery is over-chargedBeep once every second03
04Low batteryBeep once every second04
07OverloadBeep once every 0.5 second07
10Output power deratingBeep twice every 3 seconds10
15PV energy is low.Beep twice every 3 seconds15
E9Battery equalizationNoneE9
6PBattery is not connectedNone6P

8. Specifications

8.1 Line Mode Specifications

INVERTER MODEL3.6KW4.2KW6.2KW
Input Voltage WaveformSinusoidal (utility or generator)
Nominal Input Voltage230Vac
Low Loss Voltage170Vac±7V (UPS); 90Vac±7V (Appliances)
Low Loss Return Voltage180Vac±7V (UPS); 100Vac±7V (Appliances)
High Loss Voltage280Vac±7V
High Loss Return Voltage270Vac±7V
Max AC Input Voltage300Vac
Nominal Input Frequency50Hz / 60Hz (Auto detection)
Low Loss Frequency40±1Hz
Low Loss Return Frequency42±1Hz
High Loss Frequency65±1Hz
High Loss Return Frequency63±1Hz
Output Short Circuit ProtectionCircuit Breaker
Efficiency (Line Mode)>95% (Rated R load, battery full charged)
Transfer Time10ms typical (UPS); 20ms typical (Appliances)

8.2 Inverter Mode Specifications

INVERTER MODEL3.6KW4.2KW6.2KW
Rated Output Power3.6KW4.2KW6.2KW
Output Voltage WaveformPure Sine Wave
Output Voltage Regulation230Vac±5%
Output Frequency50Hz
Peak Efficiency93%
Overload Protection3s@≥150% load; 5s@101%~150% load
Surge Capacity2* rated power for 5 seconds
Nominal DC Input Voltage24Vdc48Vdc
Cold Start Voltage23.0Vdc46.0Vdc
Low DC Warning Voltage @load < 50%22.0Vdc44.0Vdc
Low DC Warning Voltage @load ≥ 50%21.0Vdc42.0Vdc
Low DC Warning Return Voltage @load < 50%22.5Vdc45.0Vdc
Low DC Warning Return Voltage @load ≥ 50%22.0Vdc44.0Vdc
Low DC Cut-off Voltage @load < 50%20.5Vdc41.0Vdc
Low DC Cut-off Voltage @load ≥ 50%20.0Vdc40.0Vdc
High DC Recovery Voltage32Vdc62Vdc
High DC Cut-off Voltage33Vdc63Vdc
No Load Power Consumption30W35W50W

8.3 Two Load Output Power

INVERTER MODEL3.6KW4.2KW6.2KW
Full Load3600W4200W6200W
Maximum Main Load3600W4200W6200W
Second Load Range720W~2520W840W~2940W1240W~4340W
Main Load Cut Off Voltage22VDC44VDC
Main Load Return Voltage26VDC52VDC

8.4 Charge Mode Specifications

Utility Charging Mode

INVERTER MODEL3.6KW4.2KW6.2KW
Charging Algorithm3-Step
AC Charging Current (Max)100Amp (@VI/P=230Vac)
Bulk Charging Voltage (Flooded Battery)29.258.4
Bulk Charging Voltage (AGM / Gel Battery)28.256.4
Floating Charging Voltage27Vdc54Vdc

MPPT Solar Charging Mode

INVERTER MODEL3.6KW4.2KW6.2KW
Max. PV Array Power6200W6500W
Nominal PV Voltage240Vdc360Vdc
PV Array MPPT Voltage Range60Vdc~500Vdc
Max. PV Array Open Circuit Voltage500Vdc
Max Charging Current (AC charger plus solar charger)120Amp120Amp120Amp

8.5 Grid-Tie Operation

INVERTER MODEL3.6KW4.2KW6.2KW
Nominal Output Voltage220/230/240 VAC
Feed-in Grid Voltage Range195~253VAC
Feed-in Grid Frequency Range50±1Hz/60±1Hz
Nominal Output Current15.7A18.2A26.9A
Power Factor Range>0.99
Maximum Conversion Efficiency (DC/AC)97%

8.6 General Specifications

INVERTER MODEL3.6KW4.2KW6.2KW
Safety CertificationCE
Operating Temperature Range-10°C to 50°C
Storage temperature-15°C~60°C
Humidity5% to 95% Relative Humidity (Non-condensing)
Dimension (D*W*H), mm358×442×116
Net Weight, kg8.08.08.9

9. User Tips

  • Battery-Free Operation: This inverter can operate without batteries, utilizing solar and/or utility power directly.
  • Utility Grid Connection: The inverter is designed to connect to the electric utility grid, allowing for flexible power management.
  • Battery Compatibility: The inverter is compatible with various battery types, including Flooded, Gel, Lithium-iron phosphate, Lithium-ion, AGM/Sealed, and user-customized batteries. Ensure the correct battery type is selected in the LCD settings (Program 05) for optimal performance, especially for lithium batteries (LIB-485 mode).
  • AC Output Voltage: The AC output voltage is configurable, with options for 110V and 120V, depending on the model and settings.
  • Appliance Compatibility: This inverter is capable of powering a wide range of home and office appliances, including motor-type loads such as air conditioners, refrigerators, fans, and tube lights.
  • Air Conditioner Restart Delay: For appliances like air conditioners, a 2-3 minute restart delay is often required to balance refrigerant gas. If your air conditioner does not have a built-in time-delay function, a power shortage and quick recovery could cause damage. The inverter may trigger an overload fault to protect the appliance, but internal damage can still occur.

10. Warranty & Support

All SUMRY products come with a 1-year warranty from the store. For technical support or service, please contact your local dealer or service center.

For additional item guides and documents, you may refer to the official user manual PDF: User manual (PDF).

11. Appendix

11.1 Approximate Back-up Time Table

ModelLoad (W)Backup Time @ 24Vdc 100Ah (min)Backup Time @ 24Vdc 200Ah (min)
3.6KW/4.2KW3004491100
600222525
900124303
120095227
150068164
180056126
210048108
24003594
27003174
32002867
36002560
42002253
6.2KW5006131288
1000268613
1500158402
2000111271
250090215
320076182
350065141
400050112
450044100
50004090
62003680

Note:

  1. Backup time depends on the quality of the battery, age of battery, and type of battery. Specifications of batteries may vary depending on different manufacturers.
  2. The final interpretation right of this product belongs to the company.