1. Introduction
The Aramox TL-136 Liquid Level Transmitter is a high-precision device designed for accurate and stable monitoring of liquid levels. Featuring robust construction and advanced digital circuitry, it provides reliable 4-20mA signal output for various industrial and domestic applications. This manual provides essential information for the safe and effective installation, operation, and maintenance of your liquid level transmitter.

2. Features
- Input level transmitter with high-precision diffused silicon for accurate water level monitoring.
- All-digital conditioning circuit ensures a stable 4-20mA signal output.
- IP68 multilayer waterproof protection for enhanced safety and durability.
- 45-degree oblique angle anti-shock design.
- Detachable anti-blocking design for easy maintenance.
- Suitable for measuring water and other liquids that do not corrode stainless steel.
3. Specifications
| Parameter | Value |
|---|---|
| Model Number | Liquid Level Sensor (TL-136) |
| Brand Name | Aramox |
| DIY Supplies | Electrical |
| Certification | CE |
| Tested Medium | Water (liquid that does not corrode stainless steel) |
| Guide Cable Length | 5 meters |
| Measuring Range | 0-1m / 0-2m / 0-3m / 0-4m / 0-5m (optional) |
| Measurement Accuracy | 0.2% FS-0.5% FS (conventional) |
| Output Signal | 4-20mA |
| Supply Voltage | 24VDC |
| Medium Temperature | -40-70 ℃ |
| Ambient Temperature | -40-80 ℃ |
| Temperature Compensation | -10-70 ℃ |
| Overload Capacity | Protection Level: IP68 |
| Temperature Source Shift | ± 0.01% FS / ℃ |
| Long-term Stability | ± 0.2% FS / year |
| Machine Impact | 20g (20-5000HZ) |
| Product Material | 304 stainless steel |
| Battery Included | No |
| High-concerned chemical | None |

4. Package Contents
- 1 x Liquid Level Transmitter (TL-136)
5. Setup
Follow these steps to set up your TL-136 Liquid Level Transmitter:
- Placement: Submerge the probe body of the liquid level transmitter into the liquid you wish to measure. Ensure the probe is positioned vertically and securely at the desired measurement depth.
- Wiring: Connect the red and black wires of the sensor to your 24VDC power supply and the receiving device (e.g., a display unit, PLC, or control system) that accepts a 4-20mA input signal. The red wire is typically for positive power, and the black wire for negative/signal return.
- Air Guide Cable: Ensure the air guide cable is properly routed and not obstructed, as it is crucial for accurate pressure readings.
- Control Unit (Optional): If you intend to use the sensor for automated control (e.g., pump activation/deactivation), connect the 4-20mA output to a compatible control unit. This unit will interpret the analog signal and trigger actions based on predefined thresholds.


6. Operating Instructions
The TL-136 Liquid Level Transmitter continuously measures the liquid level and outputs a corresponding 4-20mA signal. This signal can be read by a compatible display or control system.
6.1 Basic Operation
- Ensure the sensor is correctly installed and powered with 24VDC.
- The sensor will immediately begin transmitting the liquid level as a 4-20mA current signal.
- A 4mA output typically corresponds to the minimum measured level (e.g., 0m), and a 20mA output corresponds to the maximum measured level (e.g., 1m, 2m, 3m, 4m, or 5m, depending on the sensor model).
- Monitor the output signal using your connected display or control system.
6.2 Automated Control Example
For automated control, such as maintaining a specific water level range, you will need an external control unit. The video below demonstrates a typical setup:
In the demonstration:
- The sensor is placed at the bottom of the water tank.
- A control unit is set with a lower limit alarm at 20 cm and an upper limit alarm at 30 cm.
- When the water level drops to 20 cm, the control unit triggers a pump to start replenishing water.
- When the water level rises to 30 cm, the control unit stops the pump.
- The control unit's display shows the actual water level and its percentage.
- The control unit can also be connected to other devices like alarms, solenoid valves, or AC contactors for integrated systems.
7. Maintenance
To ensure the longevity and accurate performance of your TL-136 Liquid Level Transmitter, consider the following maintenance tips:
- Regular Cleaning: Periodically inspect the sensor probe for any buildup of debris, algae, or other contaminants. Clean the probe gently with a soft cloth and appropriate cleaning solution if necessary, ensuring not to damage the sensor surface.
- Cable Inspection: Check the sensor cable for any signs of wear, cuts, or damage. Ensure all connections are secure and free from corrosion.
- Environmental Considerations: While the sensor has IP68 protection, avoid exposing it to harsh chemicals or extreme physical impacts that could compromise its integrity.
- Anti-blocking Design: The detachable anti-blocking design allows for easier cleaning and removal of obstructions from the sensor tip. Utilize this feature for thorough maintenance.
8. Troubleshooting
If you encounter issues with your liquid level transmitter, consider these common troubleshooting steps:
- No Output/Incorrect Reading:
- Verify the 24VDC power supply is correctly connected and providing the specified voltage.
- Check all wiring connections for looseness or damage.
- Ensure the sensor probe is fully submerged and not obstructed by debris.
- Confirm that the receiving device (display, PLC) is correctly configured to read a 4-20mA signal.
- Unstable Output:
- Check for electrical interference from nearby equipment.
- Ensure the sensor cable is not damaged or kinked.
- Verify the liquid medium is stable and not experiencing excessive turbulence.
- Sensor Corrosion:
- The sensor is made of 304 stainless steel. Ensure the measured liquid does not contain substances that corrode this material. If corrosion is observed, the sensor may be incompatible with the liquid.
9. User Tips
- Continuous Measurement: The TL-136 is a continuous liquid level transmitter, providing an analog 4-20mA output proportional to the liquid level. It is not a simple on/off float switch. For on/off control, an external control unit capable of interpreting the 4-20mA signal and triggering relays is required.
- Liquid Compatibility: The sensor is designed for use with water and other liquids that do not corrode 304 stainless steel. If using in specialized environments like marine tanks with black water or liquids containing debris, ensure the debris is finely chopped or filtered to prevent clogging the sensor's anti-blocking connector. Always verify liquid compatibility with stainless steel to prevent damage and ensure accurate readings.
- Calibration: While the sensor is factory calibrated, for critical applications, it is advisable to periodically verify its readings against a known standard.
10. Warranty and Support
For warranty information, technical support, or service inquiries, please refer to the documentation provided with your purchase or contact your retailer. Keep your purchase receipt as proof of purchase.