1. Introduction and Safety Precautions
Thank you for selecting the ELECTESLA ES100 AC Drive. This manual provides detailed instructions for the correct installation, operation, maintenance, and troubleshooting of your Variable Frequency Drive (VFD). Please read this manual carefully before use to ensure proper function and safety. Keep this manual for future reference.
AC drives are power electronic products and should only be installed and debugged by professional electrical engineering personnel. Throughout this manual, you will find Attention and Danger symbols to highlight critical safety information.
1.1 General Safety Definitions
- Attention: Indicates potential damage to the AC drive or mechanical system if instructions are not followed.
- Danger: Indicates potential for casualties if instructions are not followed.
1.2 Before Power On
- The power input voltage must match the AC drive's specifications.
- Install the AC drive in a safe area, away from high temperatures, direct sunlight, moisture, and water droplets.
- Unauthorized use environments may lead to fire, gas explosion, or electric shock.
- If multiple AC drives are in one control cabinet, add a cooling fan to keep the temperature below 40°C.
- Avoid installing a contactor on the input side for start/stop control, as it may damage the AC drive. Control via terminal command is recommended.
- Do not install air switches, contactors, or other switch devices on the output side. If necessary, ensure the AC drive has no output when the switch activates.
- Do not install capacitance or voltage-sensitive resistance for lightning protection or power factor correction on the output side.
- Use an independent power supply; avoid sharing with strong interference equipment like welding machines.
- Do not conduct voltage withstand tests on internal components.
- Avoid touching the circuit board due to static electricity.
- Only professional electrical engineers should install, debug, and maintain the AC drive.
- When handling, carry the frequency converter by its base to prevent the cover from falling off.
1.3 Power On
- Danger: Never plug in or out any connector (except the operation panel) during power on.
- Cover the unit before power on to prevent electric shock.
1.4 Operating
- Attention: Do not check circuit board signals during operation.
- AC drive parameters are optimized at delivery. Adjust as needed.
- Consider the speed range allowed by vibration, noise, motor bearing, and mechanical devices.
- Danger: Do not connect or disconnect the motor unit during operation.
- Do not remove the cover when running.
- If fault restart is enabled, the motor will restart automatically. Keep clear of equipment.
1.5 Power Cut Off
- Attention: Even after disconnecting main power, other voltage inputs, and shared loads, residual energy may be present. Wait at least 4 minutes before contacting electronic devices to avoid electric shock.
2. Setup and Installation
2.1 Mechanical Installation
Installation Environment:
- Ambient temperature: -10°C to 40°C.
- Mount vertically on a flame-retardant surface with screws. Ensure sufficient space for heat dissipation.
- Install in low-vibration areas (vibration < 1.14g).
- Avoid direct sunlight, humidity, condensation, or water drops.
- Avoid corrosive, flammable, or explosive gases.
- Avoid oil, dust, and metal dust.
- Prevent drilling residues, thread ends, and screws from falling into the inverter.
Appearance and Installation Size:


| Product Mode | H | W | D | H1 | W1 | d |
|---|---|---|---|---|---|---|
| XXX-R40G1 to XXX-2R2G1 | 65 | 151 | 173 | 165 | 45 | 4.6 |
| XXX-003G1 to XXX-004G1 | 85 | 164 | 219 | 211 | 65 | 4.6 |
| XXX-R40G3 to XXX-2R2G3 | 65 | 151 | 173 | 165 | 45 | 4.6 |
| XXX-004G3 to XXX-7R5G3 | 85 | 164 | 219 | 211 | 65 | 4.6 |
Installation of the Whole Machine:
For single or side-by-side installation, ensure a minimum of 100mm space above and below the frequency converter for heat dissipation. For up-and-down installation of multiple inverters, use a heat insulation guide plate to prevent overheating of the upper unit.
2.2 Product Peripheral Devices
The following diagram illustrates the standard configuration of inverter peripheral devices:

Air Switch (Circuit Breaker), Fuse, Cable, and Contactor Selection:
Refer to the table below for guidance on selecting appropriate components. Do not frequently close and open the contactor when the inverter is on or off, as this can reduce its service life.
| Inverter Model | Air switch/fuse(A) | Copper core cable (mm²) | Rated working current of contactor(A) |
|---|---|---|---|
| XXX-R40G1B | 10 | 1.5 | 9 |
| XXX-R75G1B | 16 | 2.5 | 16 |
| XXX-1R5G1B | 16 | 4 | 16 |
| XXX-2R2G1B | 25 | 6 | 25 |
| XXX-003G1B | 32 | 6 | 25 |
| XXX-004G1B | 32 | 10 | 32 |
| XXX-R40G2B | 10 | 1 | 10 |
| XXX-R75G2B | 10 | 1.5 | 10 |
| XXX-1R5G2B | 16 | 2.5 | 16 |
| XXX-2R2G2B | 16 | 4 | 16 |
| XXX-003G2B | 25 | 4 | 25 |
| XXX-004G2B | 32 | 6 | 25 |
| XXX-R40G3B | 10 | 1 | 10 |
| XXX-R75G3B | 10 | 1.5 | 10 |
| XXX-1RSG3B | 10 | 1.5 | 10 |
| XXX-2R2G3B | 16 | 2.5 | 16 |
| XXX-003G3B | 16 | 2.5 | 16 |
| XXX-004G3B | 25 | 2.5 | 16 |
| XXX-5R5G3B | 25 | 4 | 25 |
| XXX-7R5G3B | 32 | 4 | 25 |
Note: The recommended specification is for single VV cable used at 25°C. Adjust for other cables or higher ambient temperatures.
Brake Components Selection:
Users can choose different braking resistance and power based on actual situations. The resistance value should not be less than the minimum recommended value to avoid inverter damage. Higher system inertia, shorter deceleration time, and more frequent braking require greater braking resistance power and smaller resistance value.
| Inverter Model | Recommended value of braking resistance | Recommended power of brake resistor | Brake unit |
|---|---|---|---|
| XXX-R40G1B | ≥130Ω | 100W | Built-in |
| XXX-R75G1B | ≥80Ω | 150W | |
| XXX-1R5G1B | ≥50Ω | 300W | |
| XXX-2R2G1B | ≥50Ω | 300W | |
| XXX-003G1B | ≥40Ω | 500W | |
| XXX-004G1B | ≥40Ω | 500W | |
| XXX-5R5G1B | ≥30Ω | 1000W | |
| XXX-7R5G1B | ≥30Ω | 1200W | |
| XXX-R40G2B | ≥130Ω | 100W | |
| XXX-R75G2B | ≥80Ω | 150W | |
| XXX-1R5G2B | ≥50Ω | 300W | |
| XXX-2R2G2B | ≥50Ω | 300W | |
| XXX-003G2B | ≥40Ω | 500W | |
| XXX-004G2B | ≥40Ω | 500W | |
| XXX-5R5G2B | ≥30Ω | 1000W | |
| XXX-7R5G2B | ≥30Ω | 1200W | |
| XXX-011G2B | ≥20Ω | 2000W | |
| XXX-015G2B | ≥20Ω | 2500W | |
| XXX-R40G3B | ≥400Ω | 150W | |
| XXX-R75G3B | ≥300Ω | 150W | |
| XXX-1R5G3B | ≥200Ω | 300W | |
| XXX-2R2G3B | ≥100Ω | 500W | |
| XXX-003G3B | ≥100Ω | 500W | |
| XXX-004G3B | ≥100Ω | 500W | |
| XXX-5R5G3B | ≥80Ω | 700W | |
| XXX-7R5G3B | ≥65Ω | 1000W |
Input and Output Reactors:
Refer to the tables in the full PDF manual for detailed selection of AC input and output reactors based on your inverter model and power requirements. Reactors help improve power factor, suppress harmonics, and reduce interference.
Filter Selection:
Refer to the tables in the full PDF manual for input and output filter selection. Filters help reduce conduction interference and improve anti-interference ability.
Residual Current Circuit Breaker:
It is generally not recommended to install residual current circuit breakers with frequency converters. If used for leakage fault protection, select a current sensitivity rating of more than 200mA and an action time of 0.1s or more to prevent misoperation.2.3 Main Circuit Wiring
The main circuit terminals are used for power input and motor connection. Ensure correct wiring to prevent damage.

| Terminals | Terminal function |
|---|---|
| R, S, T (L, N) | Power input terminals |
| U, V, W | Power output terminals, connect to motor |
| P, PR | Brake resistor connection terminal |
| Ground terminal |
Recommended Specifications for Main Loop Terminal Screws and Wiring:
Refer to the full PDF manual for a table detailing recommended screw sizes, terminal widths, torque, and wire ear models for each inverter model.
2.4 Control Loop Wiring
The control loop terminals are used for various control signals. Ensure proper connections for reliable operation.

| Terminals | Description | Specifications |
|---|---|---|
| X1-X4 | Digital input terminal | Logic: >DC19V (0), <DC14V (1); Input Voltage: 0-30V; Input impedance: 3.6KΩ; X3 configurable as pulse input (0.00-100.00kHz). |
| COM | Digital signal ground | Common port linking digital signal inputs. |
| +24V | 24V power supply | Provides 24V power supply for digital input/output terminals and external sensors; Max output current: 100mA. |
| +10V | 10V power supply | Max load 10mA. |
| VI | Analog input terminals | Select 0-10V or 0-20mA via DIP switch; Voltage input impedance 10KΩ; Current input impedance ≤500Ω. |
| GND | Signal ground | Two signals ground internal connectivity. |
| AMO | Analog output terminals | AMO: 0-10V voltage output; Voltage output load > 500Ω. |
| RS+, RS- | RS485 Communication | Max baud rate: 38400bit/s. |
| KA-KB-KC | Relay output | Resistive load: 250VAC 3A/30VDC 3A; Inductive load: 250VAC 0.2A/24VDC 0.1A; KA and KB are normally open, KA and KC are normally closed. |
| J2 | Used for external keyboard | For external keyboard. |
| J3 | Dial switch | Switch between VI (0-10V) and AI (0-20mA) (Pull off the cable interface cover to see the dial switch). |
Control Loop Terminal Specifications:
The control terminal uses shrapnel-type terminal blocks. Tube-type terminals are recommended for control lines. The recommended cable size is 0.3mm². The relay terminal uses screw-type terminal blocks. Wiring with a flat blade screwdriver (3.5mm² wide, 0.6mm² thick) is recommended. Ideal stripping diameter for wiring end is 6-7mm². Wire diameter specification: 0.4-1.0mm², Torque: 0.4Nm.
Digital Input Terminal Instruction:
Only open collector NPN connection mode is supported. Multi-function terminal input X1-X4 corresponding common terminal is GND.
Analog Output Terminal Instruction:
The analog output terminal provides a signal for external devices.
2.5 EMC Guidance in Electrical Wiring
The inverter complies with IEC/EN61800-3:2004 standards for electromagnetic compatibility. Proper wiring is crucial for noise suppression.
Noise Control Measures:
- Add input noise filters to the frequency converter and power filters to affected equipment if sharing power supply.
- Use an isolation transformer to separate noise transmission paths.
- Install easily affected equipment and signal lines as far away from the frequency converter as possible.
- Use shielded cable for signal lines, with the shielding layer reliably grounded.
- Keep signal lines orthogonal to power cables if they must cross.
- Place motor cables in thick barriers or metal pipes, grounded with a shielded cable.
- Use 4-core motor cable, with one core grounded at the converter and the other at the motor housing.
- Equip input and output with radio noise filters and line radiation noise filters (e.g., ferrite mold choke).
Grounding Treatment:

- Use maximum standard size grounding cable to reduce impedance.
- Keep ground wire as short as possible.
- Grounding point should be close to the frequency converter.
- One of the four-core motor cables should be grounded on the inverter side, and the other side connected to the motor grounding terminal.
- Separate grounding terminals of the inverter and other interference-vulnerable equipment.
- Arrange grounding cable away from noise-sensitive input/output wiring.
Leakage Current Suppression:
- Reduce carrier frequency and select the shortest possible motor cable to suppress leakage current to ground.
- Increasing the output reactor can also effectively suppress leakage current between lines.
3. Operation
3.1 Operator Panel
The operator panel allows you to modify parameters, monitor the working status, and control the inverter (start/stop).

Indicator Light Description:
| FOR | REV | State |
|---|---|---|
| On | Off | Running FOR |
| Off | On | Running REV |
| Off | Off | Stop |
Indicator lights HZ, A, RPM signify the monitoring display data of the frequency converter.
3.2 Display Screen
The 5-digit LED display shows set frequency, output frequency, various monitoring data, and alarm codes.
3.3 Keyboard Keys
| Button | Name | Function |
|---|---|---|
| RUN | Operate Button | Starts the inverter directly. |
| STOP | Stop / Reset key | Stops or resets the inverter in case of failure. |
| Displacement key | Displays data circularly in the main interface; selects modification bit when modifying a parameter. | |
| FOR/REV | FOR and REV switch key | Switches forward or reverse rotation directly on the panel. |
| PROG | Menu key | Enters or returns the menu. |
| Encoder | Adjusts frequency converter speed; enters menu or confirms data. Clockwise rotation increases, counter-clockwise decreases. |
3.4 Parameter Setting
To set parameters, power on and set P00.02 = 1 or =2/3. The command source is given by external terminal or communication. After parameter modification, short circuit digital input terminal X1 and GND (COM) to start the inverter. Otherwise, the frequency converter will stop when disconnected.
Refer to Chapter 5 and 6 of the full PDF manual for a comprehensive list and description of functional parameters (P00-P11 groups).
3.5 Monitor Running Status
The operator panel can display various running statuses. Refer to the full PDF manual, page 31, for a table detailing specifications, buttons, display on screen, and introduction for monitoring running status like output frequency, set value, motor current, motor voltage, motor RPM, DC voltage, inverter temperature, feedback value, and analog VI input.
4. Specifications
4.1 Product Model Specifications
The ES100 series VFDs are available in various power ratings and input/output voltage configurations. The model number indicates the power and voltage type.
| Model | Input Voltage | Input Current (A) | Output Current (A) | Rated Power (kW) |
|---|---|---|---|---|
| XXX-R40G1 | 1×200-240V | 6.5 | 2.3 | 0.40 |
| XXX-R75G1 | 1×200-240V | 11.3 | 4.0 | 0.75 |
| XXX-1R5G1 | 1×200-240V | 18.5 | 7.0 | 1.5 |
| XXX-2R2G1 | 1×200-240V | 23.9 | 11 | 2.2 |
| XXX-003G1 | 1×200-240V | 28.1 | 13 | 3.0 |
| XXX-004G1 | 1×200-240V | 36.4 | 17 | 4.0 |
| XXX-R40G3 | 3×380-440V | 2.4 | 1.2 | 0.4 |
| XXX-R75G3 | 3×380-440V | 3.7 | 2.1 | 0.75 |
| XXX-1R5G3 | 3×380-440V | 6.4 | 4 | 1.5 |
| XXX-2R2G3 | 3×380-440V | 8.9 | 5.6 | 2.2 |
| XXX-003G3 | 3×380-440V | 13.4 | 7.3 | 3.0 |
| XXX-004G3 | 3×380-440V | 15.8 | 9.8 | 4.0 |
| XXX-5R5G3 | 3×380-440V | 21.3 | 13.3 | 5.5 |
| XXX-7R5G3 | 3×380-440V | 28.3 | 17.7 | 7.5 |
Note: This table shows a partial list. Refer to the full PDF manual for complete model specifications.
4.2 Product Technical Specifications
| Name | Specification |
|---|---|
| Input Power Voltage | 1PH/3PH200~240V -20%~+10%; 3PH380~480V -20%~+10% |
| Input Power Frequency | 48-62HZ |
| Input Power Max Unbalance | 3% |
| Output Power Output Voltage | 3PH0~100 full voltage input |
| Output Power Output Frequency | Vector control; V/F:0-600Hz |
| Control Mode | V/F, Vector control |
| Start Torque | 0.5Hz 150% |
| Overload Capacity | 150% Rated output current (60s), 200% Rated output current (1s) |
| Carrier Frequency | VF:2K~16kHz, Vector: 2K~10KHz |
| Speed Setting Resolution (Digital) | 0.001Hz |
| Speed Setting Resolution (Analog) | 0.5% of Max Operation Frequency |
| Open Loop Speed Control Accuracy | 30~4000rpm: Error±8rpm |
| Control Command Source | Operate Panel, Digital Terminal; Communication |
| Set Frequency Source | Panel; Analog; Pulse; Communication |
| Acceleration and Deceleration time | 4 Groups Acceleration and Deceleration time is 0.05-3600.00S |
| Protection Level | IP20 |
| Operation Temperature | -10°C~40°C (Over 40°C need bigger capacity inverter) |
| Operation Humidity | 5%-85% (95% No drops of water) |
| Vibration | < 5.9m/S2 (0.6g) |
| Highest altitude | 1000m (Over 1000m need bigger power inverter) |
| Length of Motor Wire line | Shielding wire: 50m; Unshielding wire: 10m |
| DC reactor | NO |
| Braking Unit | Built-in |
IO Panel Control Terminal Specifications:
Refer to the full PDF manual, page 11, for a detailed table of IO Panel Control Terminal specifications, including input/output terminals, power supply terminals, communication terminals, LED display, monitoring functions, and indicator lights.
Description of Volume Reduction:
- Temperature Derating: If ambient temperature exceeds 40°C, the inverter must be used with reduced capacity.
- Altitude Capacity Reduction: Cooling capacity decreases at low pressure. No reduction needed below 1000m. Above 1000m, reduce output by 1% every 100 meters, or reduce max ambient temperature by 1°C every 200 meters.
5. Troubleshooting
The inverter provides fault alarms and warnings to indicate operational issues. These are displayed as codes on the inverter panel.
5.1 Fault Alarm and Treatment
Warnings: Indicate the inverter is operating near its design limit but can continue. The warning disappears if the cause is resolved. If persistent, it may lead to a fault. Displayed as "A.XX".
Faults: Indicate the inverter has exceeded its design limit, causing it to trip and require a reset. Displayed as "E.XX". Some faults are "tripping locking faults" and require power cycling to reset.
Refer to the full PDF manual, pages 117-118, for a comprehensive list of fault codes, their names, and recommended treatments. Below are some common examples:
| Warning | Fault | Fault name | Treatment |
|---|---|---|---|
| - | E.01 | Output short circuit | Check the wiring and insulation of the motor. |
| A.02 | E.02 | Acceleration over current | Increase acceleration time; Manual torque lifting; Remove peripheral faults; Carry out self-learning of motor parameters; Select speed tracking start or start after motor stop; Cancel sudden loading; Choose a converter with higher power level. |
| A.03 | E.03 | Deceleration over current | Remove peripheral faults; Carry out self-learning of motor parameters; Increase deceleration time; Cancel sudden loading; Add brake unit and resistor. |
| A.12 | E.12 | Input phase loss | Check the connection of the input power line. |
| A.14 | E.14 | IGBT temperature too high | Clean fan duct; Replace the cooling fan. |
| A.24 | E.24 | Torque limit | Set motor parameters correctly or adjust P09.04 parameters. |
| A.45 | E.45 | Motor overload | Choose higher power model; Correctly set parameter based on motor parameter. |
| - | E.98 | Restore factory settings | Press "STOP" button to reset. |
If the above operations do not resolve the issue, please contact technical support.
6. Maintenance
Regular maintenance is crucial for extending the service life of your inverter and preventing potential failures caused by environmental factors like temperature, humidity, dust, and vibration.
6.1 Daily Inspection and Maintenance
Perform the following checks daily:
- Check for abnormal sound changes during motor operation.
- Observe if the motor vibrates.
- Verify if the installation environment of the frequency converter has changed.
- Ensure the cooling fan operates normally.
- Check if the frequency converter is overheated.
- Monitor inverter output voltage, current, and frequency.
- Inspect for dust, scrap iron, or corrosive liquid inside the inverter.
6.2 Regular Maintenance
Depending on environmental conditions, check the inverter every 3-6 months to prevent hidden issues.
Note:
- Always ensure the inverter is powered off and fully discharged before maintenance.
- Do not leave metal objects, screws, gaskets, wires, or tools inside the inverter.
- Do not perform any internal transformations, as this may affect normal operation or damage the equipment.
| Inspection item | Measures |
|---|---|
| Control terminal screw loose | Tighten with a screwdriver |
| Main circuit terminal screw loose | Tighten with a screwdriver or sleeve |
| Ground terminal screw loose | Tighten with a screwdriver or sleeve |
| Mounting screw of frequency converter loose | Tighten with a screwdriver or sleeve |
| Power cable and control cable damaged | Replace the damaged cable |
| Circuit board dusty | Clean up |
| Air duct blocked | Clean up |
6.3 Replacement of Vulnerable Parts
Key wearing parts include the cooling fan, electrolytic capacitor, relay, or contactor. Their service life depends on the operating environment and maintenance. Inspect these parts regularly and replace them if abnormalities are found.
| Part | Service life (good environment) | Cause of damage | Situation requiring replacement |
|---|---|---|---|
| Cooling fan | 4~5 years | Bearing wear; Leaf aging | Cracks in fan blades; Abnormal vibration sound. |
| Electrolytic capacitor | 4~5 years | Poor input power; High ambient temperature; Frequent load jump; Electrolyte aging | Liquid leakage; Safety valve protruded; Change in electrostatic capacitance; Low insulation resistance. |
| Relay or contactor | 5-10 million times | Corrosion and dust affect contact; Too frequent contact action | Opening and closing failure. |
6.4 Storage and Transportation
If the product is not used immediately, store it in its original packing box under the following conditions:
- Dust-free, dry environment.
- Storage ambient temperature: -25°C to 60°C.
- Relative humidity: 5% to 95%, no condensation.
- No corrosive gas or liquid.
- Store on a shelf and pack properly.
- Transportation environment temperature: -25°C to 70°C.
- Transportation relative humidity: less than 95% (at 40°C).
If stored for a long time, the electrolytic capacitor may deteriorate. Power on the inverter once a year for at least 5 hours, slowly increasing the input voltage to the rated value with a voltage regulator.
6.5 Frequency Converter Scrapping
The raw materials of the drive unit are recyclable. Packaging materials are degradable. Metal parts (steel, aluminum, copper) can be recycled. Plastic, rubber, and cardboard can also be recycled. Printed circuit boards and DC capacitors should be treated selectively according to EC62635 standards. Consult local regulations for proper disposal.
7. User Tips
- For optimal performance, ensure all motor parameters are accurately set in the VFD. Incorrect settings can lead to inefficient operation or faults.
- When experiencing over-current faults, first check motor wiring and insulation before adjusting acceleration/deceleration times.
- If using an external control panel, ensure the cable is securely connected and within the recommended length (generally within 15m).
- Regularly clean the cooling fan and air ducts to prevent overheating, especially in dusty environments.
- If you encounter communication issues, verify the RS485 wiring, baud rate, and data format settings.
8. Warranty and Support
ELECTESLA Official Store offers an 18-month warranty on this product. For any technical assistance, troubleshooting not covered in this manual, or warranty claims, please contact ELECTESLA Official Store directly.
Contact Information:
- Online Service: Available through the seller's platform.
- WhatsApp: +8618656102087
- Email: alex@jinqu-electric.com
You can also refer to the official user manual (PDF) for more detailed information: ELECTESLA ES100 User Manual (PDF)
9. Frequently Asked Questions
- Q: What should I do if the inverter displays an 'E.XX' fault code?
- A: 'E.XX' fault codes indicate a critical error. Refer to the 'Troubleshooting' section (Section 5) and the full PDF manual's fault list for specific fault descriptions and recommended treatments. Often, these require a reset after addressing the underlying cause.
- Q: Can I use this VFD with both synchronous and asynchronous motors?
- A: Yes, the ELECTESLA ES100 VFD is designed to drive both synchronous and asynchronous motors. Ensure you select the correct motor type in the parameter settings (P01.00 Motor Type) for optimal performance.
- Q: How do I connect an external control panel?
- A: An external control panel can be connected via a network cable. Refer to Figure 2.5 in the 'Setup and Installation' section for the control loop wiring diagram. The panel can be used to modify parameters, monitor status, and control the inverter from a distance.
- Q: What is the maximum output frequency?
- A: The maximum output frequency is 600Hz, as specified in the technical specifications (Table 4.2).