DIANQI DDS665

Contents

DIANQI DDS665 Multifunction Bi-Directional Energy Meter User Manual

Model: DDS665

1. Introduction

The DIANQI DDS665 is a single-phase, two-wire multifunction energy meter designed for accurate measurement of electrical parameters. It supports bi-directional measurement, allowing it to monitor both city power consumption and negative power generation, such as from solar PV systems or generators. This meter provides real-time display of various electrical values and features an RS485 (Modbus-RTU) communication interface for advanced data acquisition.

This manual provides essential information for the safe and efficient installation, operation, and maintenance of your DDS665 energy meter. Please read it thoroughly before use.

2. Safety Instructions

  • Installation and maintenance should only be performed by qualified personnel.
  • Ensure all power is disconnected before attempting any installation, wiring, or maintenance.
  • Always follow local electrical codes and regulations.
  • Do not operate the meter in environments exceeding its specified operating temperature or humidity ranges.
  • Avoid exposing the meter to direct sunlight, rain, or excessive dust.
  • Do not disassemble or modify the meter. Doing so will void the warranty and may pose a safety risk.

3. Key Features

  • Bi-directional Measurement: Measures both consumed (city power) and generated (solar PV, generator) energy.
  • Real-time Display: Shows Total Active Energy (KWh), Positive Active Energy (KWH), Negative Active Energy (KWH), Temporary Active Energy (KWH), Voltage (V), Current (A), Active Power (W), Power Factor (PF), and Frequency (Hz).
  • LCD Display with Backlight: Clear and easy-to-read display, even in low light conditions.
  • RS485 (Modbus-RTU) Communication: Enables remote monitoring and integration with energy management systems.
  • High Accuracy: Accuracy Level 1.0 for reliable measurements.
  • DIN Rail Mounting: Compact design for easy installation in electrical cabinets.

4. Specifications

ParameterValue
Model NumberDDS665
Brand NameDIANQI
Rated VoltageAC 220/230V
Reference Current5(100)A
Accuracy Level1.0
Rated Frequency50Hz
Constant Pulse1600imp / kWh
Power Consumption≤2W, 10VA
Starting Current0.004Ib
Operating Temperature-20°C to +55°C
Storage Temperature-25°C to +70°C
Display TypeLCD with Backlight
Dimensions (L*W*H)90mm * 45mm * 70mm
PhaseSingle Phase
Power SupplyAC
CommunicationRS485 (Modbus-RTU)
CertificationCE
Battery IncludedNo

5. Installation

5.1 Mounting

The DDS665 energy meter is designed for DIN rail mounting. Ensure the DIN rail is securely installed in a suitable electrical enclosure. The meter clips onto the DIN rail for easy and secure placement.

Image showing the DDS665 energy meter's mounting clips, designed for DIN rail installation (DIN rail not included).
Figure 1: DIN Rail Mounting Clips (DIN rail not included)

5.2 Wiring Diagram

WARNING: Electrical shock hazard. Ensure all power is OFF before wiring. Wiring must be performed by a qualified electrician.

Connect the meter according to the following diagram. Pay close attention to the Live (L) and Neutral (N) input and output terminals, as well as the RS485 communication terminals.

Wiring diagram for the DDS665 energy meter, showing Live (L) and Neutral (N) input and output connections.
Figure 2: Main Power Wiring Diagram

Terminal Connections:

  • IN (Input): Connect the incoming Live (L) and Neutral (N) wires from the power source.
  • OUT (Output): Connect the outgoing Live (L) and Neutral (N) wires to the load.
  • RS485 (Modbus-RTU): For models with RS485, connect the communication wires to terminals +21, -20, and 22 as indicated on the meter. Refer to the detailed image below for clarity.
Side view of the DDS665 energy meter, detailing the MODBUS-RTU (RS485) communication interface with terminals +21, -20, and 22.
Figure 3: RS485 Communication Port Details

6. Operation

6.1 Power On

Once correctly wired and mounted, restore power to the circuit. The LCD display will illuminate, showing the current electrical parameters.

Close-up view of the DDS665 energy meter's LCD display and front panel, highlighting the 230VAC 5(100)A 50Hz IEC62053-21 1600imp specifications.
Figure 4: Meter Display and Front Panel

6.2 Display Modes

The meter cycles through various parameters on its LCD display. These include:

  • Total Active Energy (KWh)
  • Positive Active Energy (KWh)
  • Negative Active Energy (KWh)
  • Temporary Active Energy (KWh)
  • Voltage (V)
  • Current (A)
  • Active Power (W)
  • Power Factor (PF)
  • Frequency (Hz)
DIANQI DDS665 energy meter displaying various electrical parameters, including KWh, Voltage, Current, and Frequency.
Figure 5: Example Display Readings

6.3 Resetting Temporary KWh

To reset the Temporary Active Energy (KWh) to zero, press and hold the button on the front panel for approximately 6 seconds. This action will only affect the temporary reading.

Note: The Total Active Energy (KWh), Positive Active Energy (KWh), and Negative Active Energy (KWh) cannot be reset.

6.4 RS485 Communication (Optional)

For models equipped with RS485, the meter can be integrated into a Modbus-RTU network for remote data acquisition and control. Refer to the Modbus communication protocol documentation for detailed register maps and communication settings. Ensure proper termination and addressing for the RS485 bus.

7. Maintenance

  • Cleaning: Use a soft, dry cloth to clean the meter's exterior. Do not use abrasive cleaners or solvents.
  • Connection Check: Periodically inspect all wiring connections to ensure they are tight and free from corrosion.
  • Environmental Conditions: Ensure the operating environment remains within the specified temperature and humidity ranges to prolong the meter's lifespan.

8. Troubleshooting

  • No Display: Check the power supply connections. Ensure the meter is receiving the correct voltage.
  • Incorrect Readings: Verify that the wiring is correct according to the diagram. Ensure the meter is installed in the correct phase.
  • Communication Issues (RS485): Check RS485 wiring, baud rate, parity, and slave ID settings. Ensure proper termination resistors are used if necessary.
  • Temporary KWh Not Resetting: Ensure you are holding the button for the full 6 seconds. Remember that total KWh values cannot be reset.

If problems persist, contact customer support for assistance.

9. User Tips

  • Monitoring Solar PV: When using the meter for solar PV systems, the 'Negative Active Energy KWh' will indicate the energy generated and fed back into the grid, while 'Positive Active Energy KWh' will show energy consumed from the grid.
  • Temporary vs. Total KWh: Utilize the 'Temporary Active Energy KWh' for short-term monitoring or testing specific loads, as it can be reset. The 'Total Active Energy KWh' provides a cumulative, non-resettable record of energy flow.
  • RS485 Integration: For advanced users, integrating the RS485 interface with a home automation system or data logger can provide detailed historical data and remote monitoring capabilities.

10. Warranty and Support

This product is covered by a manufacturer's warranty against defects in materials and workmanship. For specific warranty terms and conditions, please refer to the product packaging or contact your point of purchase. For technical support or inquiries, please reach out to DIANQI customer service.

© 2023 DIANQI. All rights reserved.