1. Introduction
This manual provides detailed instructions for the installation, operation, and maintenance of the GEYA GPS8-03 Din Rail 3 Phase Voltage and Current Protector. This device is designed to monitor and protect household and industrial equipment from overvoltage, undervoltage, and overcurrent conditions in 3-phase + Neutral electrical systems. It features true RMS measurement, adjustable protection parameters, and automatic reset capabilities.
2. Safety Information
WARNING: Electrical shock hazard. Installation and maintenance should only be performed by qualified personnel.
- Always disconnect power before installing or servicing the device.
- Ensure all wiring connections are secure and comply with local electrical codes.
- This product does not have an isolation function. Always disconnect the superior Main Circuit Breaker (MCB) during maintenance to prevent electrical shock.
- Do not operate the device if it appears damaged.
3. Product Overview
3.1 Panel Diagram and Indicators
The front panel features digital displays for voltage (V) and current (A) for each phase (L1, L2, L3), along with LED indicators and control buttons:
- >U Indicator: Overvoltage status.
- <U Indicator: Undervoltage status.
- >I Indicator: Overcurrent status.
- Asy Indicator: Voltage unbalance status.
- Power Open/Close Indicator (---): Indicates load status.
- Power Button (circle with line): Manually turn on/off the load. If automatic fault reset is off, use for manual reset.
- M Button: Press and hold for 3 seconds to enter setting mode. Press and hold for 3 seconds to save settings.
- Up Arrow Button: Increase value when setting parameters.
- Down Arrow Button: Reduce value when setting parameters.
4. Specifications
| Parameter | Value |
|---|---|
| Function | Over voltage, under voltage and over current |
| Rated supply voltage | AC220V (L1,L2,L3,N) |
| Rated Frequency | 45-65Hz |
| Operation voltage range | 80V~400V (L1,L2,L3-N) |
| Rated operational current | 63A (AC1) |
| Burden | AC max.3VA |
| Over voltage operation value | OFF, 230V-300V (Factory default: 275V) |
| Under voltage operation value | 140V-210V, OFF (Factory default: 175V) |
| Over/under voltage action delay | 0.1s-10s (Factory default: 0.5s) |
| Over current value | OFF, 1A-63A (Factory default: 60A) |
| Over current action delay | 2s-600s (Factory default: 5s) |
| Voltage unbalance value | OFF, 20V-99V (Factory default: 40V) |
| Power up delay | 2s-600s (Factory default: 5s) |
| Reset time | 2s-900s (Factory default: 30s) |
| Measurement error | less than 1% |
| Mechanical life (AC1) | 1 x 106 |
| Electrical life (AC1) | 1 x 104 |
| Operating temperature | -20°C ~ +60°C |
| Storage temperature | -35°C ~ +75°C |
| Mounting/DIN rail | Din Rail EN/IEC 60715 |
| Protection degree | IP40 for front panel / IP20 terminals |
| Operating position | Any |
| Overvoltage category | III |
| Pollution degree | 2 |
| Dimensions | 82 x 72 x 68mm |
| Weight | 376g |
5. Setup and Installation
5.1 Mounting
The GEYA GPS8-03 is designed for Din Rail mounting (EN/IEC 60715). Ensure the Din Rail is securely installed in a suitable enclosure.
5.2 Wiring Diagram
IMPORTANT: This product does not have an isolation function. Please disconnect the superior Main Circuit Breaker (MCB) during maintenance to prevent electrical shock.
Connect the device according to the diagram above. Ensure proper connection of Neutral (N), Line 1 (L1), Line 2 (L2), and Line 3 (L3) for both input and output. The device should be installed after the main circuit breaker and before the loads it is intended to protect.
5.3 Terminal Sectional Area
Based on common industrial standards for devices with 63A rated current, it is recommended to use wires with an appropriate sectional area to handle the current safely and prevent overheating. Consult local electrical codes for specific requirements. For 63A, typically 10-16mm² wire is used, but this can vary.
6. Operation
6.1 Manual On/Off
Under normal operation, the load can be switched on or off manually by pressing the power key (circle with line) for approximately 0.5 seconds.
6.2 Power-on and Reset Delay
During power-on or after a fault reset, the product will display a countdown according to the set delay time. Once the countdown finishes, it will enter the running state.
6.3 Parameter Setting
To adjust protection parameters:
- Press and hold the 'M' button for 3 seconds to enter the setting mode.
- Use the 'Up' and 'Down' arrow buttons to navigate through parameters and adjust their values.
- Press and hold the 'M' button for 3 seconds again to save the settings and exit the setting mode.
The following parameters can be set:
| Parameter | Range | Step Value | Factory Default |
|---|---|---|---|
| Over voltage value | OFF, 230V-300V | 1V | 275V |
| Over voltage recovery value | 225V-295V | 1V | 265V |
| Under voltage value | 145V-210V, OFF | 1V | 175V |
| Under voltage recovery value | 145V-215V | 1V | 180V |
| Voltage fault action time | 0.1s-10s | 0.1s | 0.5s |
| Over current value | OFF, 1A-63A | 0.1A | 60A |
| Over current action delay | 2s-600s | 1s | 5s |
| Voltage unbalance value | OFF, 20V-99V | 1V | 40V |
| Power on delay time | 2s-600s | 1s | 5s |
| Reset time | 2s-900s | 1s | 30s |
| Phase sequence | ON-OFF | --- | OFF |
| Fault reset | ON-OFF | --- | ON |
6.4 Phase Sequence Fault
If the phase sequence protection function is turned ON, an error in phase sequence access will be indicated on the display (e.g., L1, L3, L2 instead of L1, L2, L3).
6.5 Product Demonstration Video
7. Maintenance
- Regularly inspect the device for any signs of physical damage or loose connections.
- Keep the device clean and free from dust and moisture. Use a dry, soft cloth for cleaning.
- Ensure proper ventilation around the device to prevent overheating.
- Periodically verify the protection settings to ensure they meet current system requirements.
8. Troubleshooting
The device provides visual indicators for various fault conditions. Refer to the "Functions Diagram" for understanding fault behavior and recovery times.
- Overvoltage/Undervoltage Fault: The corresponding LED (>U or <U) will illuminate. The device will trip and automatically reset after the set 'Reset Time' (Tr) if 'Fault reset' is ON.
- Overcurrent Fault: The >I LED will illuminate. The device will trip and automatically reset after the set 'Reset Time' (Tr) if 'Fault reset' is ON.
- Voltage Unbalance Fault: The Asy LED will illuminate. The device will trip and automatically reset after the set 'Reset Time' (Tr) if 'Fault reset' is ON.
- No Power/Display Off: Check the power supply connections and the main circuit breaker.
- Device Not Resetting: If the 'Fault reset' parameter is set to OFF, manual reset is required by pressing the power button.
- Incorrect Readings: Ensure all wiring is correct and terminals are tight. Measurement error is less than 1%.
Timing Parameters:
- Tp (Power-up delay): 2-600s
- Tr (Reset delay time): 2-900s
- Tu (Over/under voltage fault action time): 0.1-10s
- Tc (Overcurrent fault action time): 2-600s
9. User Tips
- Terminal Sectional Area: For optimal performance and safety, ensure the wire sectional area matches the 63A rated current. Consult an electrician or local codes for precise recommendations.
- Operating Modes: The device primarily offers protection based on set voltage and current thresholds with automatic or manual reset. The provided information does not explicitly mention synchronous/asynchronous operating modes for the relay itself, but rather protection functions.
10. Warranty and Support
For warranty information, technical support, or service inquiries, please contact your authorized GEYA distributor or refer to the official GEYA website. Keep your purchase receipt for warranty claims.