1. Introduction
The GEYA GPS6 series is a range of adjustable voltage and current protection devices designed for single-phase electrical systems. These devices provide essential protection against overvoltage, undervoltage, and overcurrent conditions, safeguarding connected equipment from potential damage. The GPS6-VAK model further includes Kilowatt-hour (KWH) measuring capabilities for energy monitoring.
This manual provides detailed instructions for the safe installation, configuration, and operation of your GEYA GPS6 protector.
2. Safety Information
WARNING: Electrical shock hazard. Installation and maintenance should only be performed by qualified personnel.
- Always disconnect power before installing or servicing the device.
- Ensure all wiring connections are secure and comply with local electrical codes.
- Do not operate the device if it appears damaged.
- This device is designed for 220V AC systems. Using it with incompatible voltage may cause damage or malfunction.
3. Product Overview
The GEYA GPS6 series protectors are compact, DIN rail-mountable devices featuring a digital display and intuitive button controls for setting protection parameters.

Figure 3.1: GEYA GPS6-VA5 (left) and GPS6-VAK (right) models
3.1. Models
- GPS6-VA5: Adjustable Voltage/Current Protector
Provides overvoltage, undervoltage, and overcurrent protection. The display shows real-time voltage and current. - GPS6-VAK: Adjustable Voltage/Current Protector with KWH Measuring
In addition to the protection features of the GPS6-VA5, this model also measures and displays Kilowatt-hours (KWH) for energy consumption monitoring.

Figure 3.2: GPS6-VA5 Voltage & Current Protection

Figure 3.3: GPS6-VAK KWH Measuring, Voltage & Current Protection
3.2. Display and Controls
Both models feature a digital display and four control buttons:
- SET: Enters/exits setting mode and confirms selections.
- ▲ (Up Arrow): Increases parameter values or navigates menus.
- ▼ (Down Arrow): Decreases parameter values or navigates menus.
- O (Power/Reset): Turns the device ON/OFF or manually resets after a trip.
The display shows real-time voltage (V) and current (A). The GPS6-VAK model also shows KWH readings.
A working indicator LED (POWER) shows the device status:
- Green: Normal operation.
- Red: Fault condition (overvoltage, undervoltage, or overcurrent).
4. Specifications

Figure 4.1: GPS6-VA5 Specifications Overview

Figure 4.2: GPS6-VAK Specifications Overview
| Parameter | GPS6-VA5 | GPS6-VAK |
|---|---|---|
| Supply Terminals (UP) | N, L | |
| Rated Supply Voltage | AC220V; DC85~300V | AC220V |
| Rated Frequency | 40~70Hz | 50~60Hz |
| Overvoltage (>V) Setting Range | AC130~300V; DC130~300V | AC130~300V |
| Undervoltage (<V) Setting Range | AC80~210V; DC85~210V | AC80~210V |
| Max Operating Current (>A) | 40A, 63A, 80A (model dependent) | |
| Voltage Hysteresis | 5V | |
| Voltage Accuracy | <1% | |
| Overvoltage Trip Delay | 5s | |
| Reset Time | 1~900s (factory default: 30s) | |
| Certification | CE | |
4.1. Dimensions

Figure 4.3: Device Dimensions
- Overall Height: 86mm
- Overall Width: 38mm
- Overall Depth: 46mm
- Height from DIN Rail: 67.5mm
- Width on DIN Rail: 35mm
5. Installation
The GEYA GPS6 protector is designed for DIN rail mounting within an electrical enclosure.
5.1. Mounting
- Ensure the main power supply is OFF at the circuit breaker.
- Snap the device onto a standard 35mm DIN rail.
- Ensure it is securely fastened.
5.2. Wiring Diagram
Connect the device according to the following diagram. Ensure correct polarity for Neutral (N) and Live (L) connections.

Figure 5.1: Wiring Diagram
- Input (UP): Connect the incoming Neutral (N) and Live (L) wires from your power source (e.g., main circuit breaker) to the corresponding 'N' and 'L' terminals at the top of the device.
- Output (OUT): Connect the Neutral (N) and Live (L) wires leading to your load (protected equipment) to the 'OUT N' and 'OUT L' terminals at the bottom of the device.
- It is recommended to install a circuit breaker upstream of the protector for additional safety and isolation.
6. Operation
6.1. Initial Power-Up
- After wiring, turn on the main power supply.
- The device display will light up, showing real-time voltage and current. The 'POWER' indicator should be green.
6.2. Setting Parameters
To configure the protection parameters:
- Press the SET button to enter the setting mode. The first parameter will start flashing.
- Use the ▲ and ▼ buttons to adjust the value of the flashing parameter.
- Press SET again to confirm the value and move to the next parameter.
- Repeat steps 2 and 3 for all desired parameters.
- After setting all parameters, press and hold the SET button for a few seconds to save the settings and exit the setting mode.
Adjustable parameters typically include:
- Overvoltage Threshold (>V): The voltage level above which the device will trip.
- Undervoltage Threshold (<V): The voltage level below which the device will trip.
- Overcurrent Threshold (>A): The current level above which the device will trip.
- Recovery Time (Reset Time): The delay (1-900 seconds, factory default 30s) before the device automatically resets after a fault condition clears.
- Voltage Trip Delay (P-7): This setting applies to both overvoltage and undervoltage conditions, defining how long the voltage must be outside the set limits before a trip occurs.
6.3. KWH Measuring (GPS6-VAK only)
The GPS6-VAK model continuously measures and displays the accumulated Kilowatt-hours (KWH). This reading can be viewed on the display. Consult the specific model's detailed instructions for KWH reset procedures if available.
7. Maintenance
- Keep the device clean and free from dust. Use a dry, soft cloth for cleaning.
- Regularly check wiring connections for tightness and signs of wear or corrosion.
- Ensure proper ventilation around the device to prevent overheating.
- No user-serviceable parts inside. Do not attempt to open or repair the device.
8. Troubleshooting
| Problem | Possible Cause | Solution |
|---|---|---|
| Device does not power on | No input power; incorrect wiring | Check main power supply and wiring connections. |
| Device trips frequently | Voltage/current outside set limits; incorrect settings | Verify input voltage/current. Adjust over/undervoltage or overcurrent thresholds. Check recovery time setting. |
| Display shows 'Red' POWER indicator | Fault condition (over/undervoltage, overcurrent) | Identify the cause of the fault (e.g., high voltage, low voltage, excessive load). Once the fault clears, the device should reset automatically after the set recovery time, or can be manually reset using the 'O' button. |
| Cannot change settings | Not in setting mode; buttons unresponsive | Press 'SET' to enter setting mode. If buttons are unresponsive, power cycle the device. |
9. User Tips
- Voltage Compatibility: This device is primarily designed for 220V AC installations. While it has a wide DC operating range, ensure your AC system voltage matches the specified 220V for optimal performance and protection.
- Hysteresis for Stable Operation: The device features a 5V voltage hysteresis. This means if you set an undervoltage trip at 200V, it will not immediately reconnect at 200V but will wait until the voltage recovers to 205V (200V + 5V) to prevent rapid on/off cycling near the threshold.
- Recovery Time: The adjustable recovery time (1-900s) is crucial. A longer recovery time can prevent damage from intermittent power fluctuations, allowing the system to stabilize before reconnection. The factory default is 30 seconds.
- Voltage Trip Delay (P-7): This setting helps prevent nuisance tripping from very short voltage spikes or dips. Configure it to a suitable delay to ensure the voltage condition persists for a set duration before the device acts.
10. Warranty and Support
GEYA products are manufactured to high-quality standards. For warranty information, technical support, or service inquiries, please refer to the official GEYA website or contact your authorized dealer. Keep your purchase receipt as proof of purchase.