1. Introduction
The eletechsup 25IOA08, 25IOB16, 25IOC32 series are advanced Modbus RS485 IO modules designed for industrial control and automation applications. These modules feature 8, 16, or 32 channels of photoelectrically isolated NPN/PNP inputs and corresponding 300mA DMOS PNP outputs. They support standard Modbus RTU commands, allowing for flexible integration into various systems, including PLC IO expansion, remote control, smart home automation, and security monitoring.
2. Features
- Working Voltage: DC 7-25V (compatible with 9V, 12V, 24V systems)
- Working Current: 8-50mA
- Input Ports: 8/16/32 photoelectrically isolated NPN/PNP inputs (optional)
- Output Ports: 8/16/32 DMOS PNP outputs (high level output, 300mA drive current per channel)
- Output Modes: Supports Open, Close, Toggle (Self-locking), Latch (Inter-locking), Momentary (Non-locking), and Delay modes.
- Remote Control: Input ports can remotely control output ports of other modules via the RS485 bus.
- MODBUS Command Support: Command 1 supports function codes 03, 06, 16. Command 2 supports function codes 01, 02, 03, 05, 06, 15, 16.
- Maximum Delay (Command 1): 255 seconds
- Parallel Devices: Up to 64 devices can be supported in parallel in MODBUS command mode.
- Baud Rate: Default 9600BPS, configurable to 1200/2400/4800/19200/38400/57600/115200BPS.
- Protection Feature: Epoxy encapsulation.
3. Setup
3.1 Product Overview
The modules are available in 8, 16, and 32 channel configurations, supporting both NPN and PNP input types. The M0 port is used for command selection, and the RESET port allows restoring factory settings by short-circuiting it for 5 seconds.

Figure 3.1: Module variants and key ports (M0 for command selection, RESET for factory settings).
3.2 Wiring Diagrams
Proper wiring is crucial for the module's functionality. Refer to the diagrams below for common application scenarios.
3.2.1 Modbus Communication Setup
The module communicates via RS485. It can be connected to a PC using a USB-RS485 converter or directly to a PLC. Up to 64 devices can be connected in parallel on the Modbus bus.

Figure 3.2: Modbus connection examples for PC and PLC, illustrating multi-device setup.
3.2.2 Driving PLC Amplifier Board
This diagram illustrates how to wire the module to drive a PLC amplifier board.

Figure 3.3: Wiring for driving a PLC amplifier board.
3.2.3 Reading Switch Input via RS485 Bus (Application 2)
This application demonstrates reading switch inputs (NPN or PNP) from the module via the RS485 bus. Ensure the power supply is DC 7-25V.

Figure 3.4: Wiring for reading NPN/PNP switch inputs via RS485.
3.2.4 Input and Output Amplifier (Application 3)
In this configuration, the input directly controls the output. The module acts as an amplifier. Note that for this function, you may need to configure register 0x00FA(250) via the RS485 bus.

Figure 3.5: Wiring for input and output amplification. Register 0x00FA(250) configuration may be required.
4. Operating Instructions
4.1 Modbus Communication
The module operates using the Modbus RTU protocol over RS485. You can use Modbus master software (e.g., Modbus Poll) or a PLC to send commands and read statuses.
4.1.1 Function Codes
- MODBUS Command 1: Supports function codes 03 (Read Holding Registers), 06 (Write Single Register), and 16 (Write Multiple Registers).
- MODBUS Command 2: Supports function codes 01 (Read Coils), 02 (Read Discrete Inputs), 03 (Read Holding Registers), 05 (Write Single Coil), 06 (Write Single Register), 15 (Write Multiple Coils), and 16 (Write Multiple Registers).
4.1.2 Baud Rate Configuration
The default baud rate is 9600BPS. This can be configured to 1200, 2400, 4800, 19200, 38400, 57600, or 115200BPS through Modbus commands.
4.2 Output Control Modes
The module supports various output control modes:
- Open/Close: Directly turn outputs ON or OFF.
- Toggle (Self-locking): Each command toggles the output state (ON to OFF, OFF to ON).
- Latch (Inter-locking): Activating one output deactivates all others in the group.
- Momentary (Non-locking): Output turns ON for a brief period and then automatically turns OFF.
- Delay: Output remains ON for a specified duration (up to 255 seconds with Command 1) before turning OFF.
4.3 Operation Demonstration Video
Watch this video for a practical demonstration of connecting the module to a PC and controlling its outputs using Modbus Poll software.
Video: Demonstrating Modbus communication and output control via PC software.
5. Maintenance
To ensure optimal performance and longevity of your eletechsup Modbus RS485 IO module, follow these maintenance guidelines:
- Keep Clean: Regularly clean the module and its connections to prevent dust and debris accumulation, which can affect performance.
- Check Connections: Periodically inspect all wiring connections to ensure they are secure and free from corrosion or damage.
- Environmental Conditions: Operate the module within its specified temperature and humidity ranges. Avoid exposure to extreme conditions or corrosive environments.
- Power Supply: Ensure a stable DC 7-25V power supply is used to prevent damage to the module.
6. Troubleshooting
6.1 Common Issues and Solutions
| Problem | Possible Cause | Solution |
|---|---|---|
| No communication with Modbus master (e.g., "No Connection" in software) | Incorrect serial port selection, incorrect baud rate, wiring error (A/B lines reversed or disconnected), incorrect slave ID. | Verify the correct COM port is selected in your software. Ensure the baud rate, data bits, parity, and stop bits match the module's settings. Check RS485 A+ and B- wiring for correct polarity and secure connection. Confirm the slave ID configured in the software matches the module's ID. |
| Outputs not responding | Incorrect Modbus command, insufficient power supply, output overload, module in NPN output mode (if expecting PNP). | Check the Modbus function code and register address used. Ensure the power supply is within DC 7-25V and stable. Verify the load current does not exceed 300mA per channel. Confirm you have the PNP output version (25IO series) if high-level output is required. |
| Module not functioning as expected after configuration changes | Incorrect configuration saved, corrupted settings. | Use the RESET port: Short-circuit the RESET port for 5 seconds to restore the module to factory default settings. Then reconfigure as needed. |
7. Specifications
| Parameter | Value |
|---|---|
| Power Source | DC 7-25V |
| Working Current | 8-50mA |
| Input Channels | 8/16/32 photoelectrically isolated NPN/PNP (optional) |
| Output Channels | 8/16/32 DMOS PNP (high level, 300mA max per channel) |
| Communication Interface | RS485 Modbus RTU |
| Baud Rate | Default 9600BPS (Configurable: 1200-115200BPS) |
| Max Parallel Devices | 64 |
| Theory | Solid State Relay |
| Contact Load | Low Power |
| Protect Feature | Epoxy |
| Dimensions (Only Board) | 8CH: 61x72x18MM 16CH: 106x72x18MM 32CH: 196x72x18MM |
| Dimensions (With DIN Box) | 8CH: 64x80x30MM 16CH: 109x80x30MM 32CH: 199x80x30MM |
| Weight (Only Board) | 8CH: 46g 16CH: 80g 32CH: 152g |
| Weight (With DIN Box) | 8CH: 85g 16CH: 145g 32CH: 247g |
8. User Tips
- ESPHome Compatibility: For users integrating with ESPHome devices that have RS485 output, the module's adherence to standard Modbus RTU protocol generally ensures compatibility. Consult ESPHome's Modbus documentation for specific integration guidelines and coding examples.
- NPN Output Modules: If your application requires NPN (low-level) outputs instead of PNP (high-level) outputs, please ensure you select the appropriate 23IOA08, 23IOB16, 23IOC24, 23IOD32, or 23IOE48 series modules.
9. Warranty and Support
For any technical assistance, troubleshooting beyond this manual, or warranty inquiries, please contact the seller directly. Provide your product model and a detailed description of the issue for efficient support.