1. Introduction

Thank you for selecting and using our SU600 frequency converter products. Please read this specification manual carefully before using this product correctly and safely.

It is important to read the safety notices carefully before use. Please keep this manual properly for future reference. For any questions, please contact our customer service staff for technical support.

This operating manual provides information on the SU600 frequency converter, including:

  • Safety notices of frequency converter
  • Installation and inspection of frequency converter
  • Wiring instruction of frequency converter
  • Operation instruction of frequency converter
  • All parameters instruction
  • Communication agreement instruction
  • Troubleshooting

This manual is suitable for:

  • System design and model selection staff
  • Installation or wiring staff
  • Debugging staff
  • Maintenance staff

2. Product Overview and Specifications

2.1 Naming Rules

The SU600 series frequency converter follows a specific naming convention:

SU600 Naming Rules Diagram

Diagram illustrating the SU600 model naming convention, including voltage grade and power grade.

2.2 SU600 Frequency Converter Series Index

The following table details the specifications for various SU600 models:

SU600 Frequency Converter Series Index
Frequency Converter ModePower Supply Capacity (KVA)Rated Input Current (A)Rated Output Current (A)Adapted Motor
kWHP
Single-phase 220V into three-phase 380V 50/60HZ
SU600-0R75G11.52.50.750.751
SU600-1R5G133.71.51.52
SU600-2R2G1452.22.23
SU600-3R7G15.993.73.75
SU600-5R5G18.9135.55.57.5
SU600-7R5G111177.57.510
SU600-11R0G11725111115
SU600-15R0G12132151520
Single-phase 220V into three-phase 220V 50/60HZ
SU600-0R75G21.540.750.751
SU600-1R5G2371.51.52
SU600-2R2G249.62.22.23
SU600-3R7G25.5173.73.74
SU600-5R5G28.9255.55.55
SU600-7R5G221327.57.510
SU600-11R0G22537.5111115
SU600-15R0G23240151520
Three-phase 380V into three-phase 380V 50/60HZ
SU600-0R75G31.52.50.750.751
SU600-1R5G334.11.51.52
SU600-2R2G345.82.22.23
SU600-3R7G36.19445
SU600-5R5G38.9135.55.57.5
SU600-7R5G311177.57.510
SU600-11R0G31725111115
SU600-15R0G32132151520

2.3 Technical Indicators and Specifications

The SU600 series VFD offers robust performance and features:

SU600 Technical Specifications
FeatureDescription
Rated Voltage & FrequencyThree-phase (G3 series) 380V; 50/60 HZ; Three-phase (G2 series) 220V: 50/60 HZ
Allowable Voltage RangeG3 series: 320V~460V; G2 series: 190V~250V
Output VoltageG3 series: 0~380V; G2 series: 0~220V
Output FrequencyV/F control, simple vector control: 0.0~999.9HZ; Advanced vector control, torque control: 0.5~300.0HZ
Overload Capacity110% long term; 150% for 1 min; 180% for 5s
Control MethodV/F control, simple vector control, advanced vector control, torque control
Frequency ResolutionSimulation end input: 0.1%; Digital setting: 0.1HZ
Frequency AccuracyWithin 0.2% of maximum output frequency; Set within 0.01% of output frequency
V/F CurveLinear, square, and user-defined V/F curves
Recurrent AscensionManual setting (0.0~30.0% of rated output); Automatic lifting based on output current and motor parameters
Automatic Current/Pressure LimitingStator current and voltage suppressed during acceleration, deceleration, or stable operation
Starting Torque100% Rated torque at 5.0Hz (V/F control); 150% rated torque at 1.0Hz (vector control)
Multi-section Speed Operation7-segment programmable multisegment speed control, multiple operation modes optional
PID ControlBuilt-in PID controller (pre-set frequency)
RS485 CommunicationsStandard configuration of RS485 communication function, various protocols optional
Output Signal1-way relay output (TA, TC), 1 analog signal output (0-20 mA or 0-10 V)
CertificationsCE, FCC, RoHS

3. Installation and Wiring

3.1 Safety Notes for Installation

DANGER

  1. Before wiring, confirm that the input power supply is cut off. (Risk of electric shock and fire).
  2. Ask electrical engineering professionals to conduct wiring operations. (Risk of electric shock and fire).
  3. The grounding terminal must be reliably grounded. (380V: Special 3rd earth. Risk of electric shock and fire).
  4. After the emergency stop terminal is connected, check whether the action is effective. (Risk of injury).
  5. Do not touch the output terminal directly. The output terminal of the frequency converter carries risk of electric shock and short circuit.
  6. Always install the terminal cover before power on. When removing the outer cover, always be aware of electric shock.
  7. Cut off the power supply, and wait 5 to 8 minutes to let the remaining power in the machine dissipate. (Risk of residual voltage on the electrolytic capacitor).
  8. Non-professional technical personnel should not check or conduct maintenance work. (Risk of electric shock).

Additional precautions:

  • Confirm that the power supply voltage of the incoming line is consistent with the device's requirements.
  • Connect the brake resistance or the brake unit correctly.
  • Use a screwdriver and wrench with specified torque to tighten terminals.
  • Do not connect the input power cord to the output U, V, and W terminals.
  • Do not remove the front panel cover. Only remove the terminal cover when wiring.

3.2 Shape Diagram

The following diagrams illustrate the dimensions of the external lead keyboard base and the overall machine:

SU600 External Panel Set Dimensions

Dimensions of the SU600 external panel set (panel and cable).

Hole Size of Keyboard Base
WW1HH1DD1
53mm49.4mm79mm75.4mm15.9mm14.5mm
Form Size of the Whole Machine (Peripheral Dimensions)
ModelInstallation Size (mm)Peripheral Dimensions (mm)Mounting Hole (mm)
H2W1HH1WD
0.4KW-2.2KW136.56314714272118.44
3.7KW-5.5KW172.578185182871384

3.3 Basic Operation Wiring

The frequency converter wiring is divided into the main circuit and the control circuit. Users should open the lid of the output/input terminal to see the main loop terminal and the control loop terminal, and connect correctly according to the wiring circuit below.

SU600 Wiring Diagram

Detailed wiring diagram for the SU600 VFD, showing input, output, and brake resistor connections.

3.4 Control Loop Terminal

The control loop terminals are used for external control signals and communication. The terminals are: 10V GND AI AO 485+ 485- X1 X2 X3 X4 COM TA TC.

3.5 Main Loop Terminal (0.4KW-2.2KW)

For 0.4KW-2.2KW models, the main loop terminals are: R S/L1 T/L2 U V W.

3.6 Main Loop Terminal (3.7KW-5.5KW)

For 3.7KW-5.5KW models, the main loop terminals are: R S T P+ PB U V W.

3.7 Main Control Board Jumper Description

Jumpers on the main control board configure various functions:

Main Control Board Jumper Settings
JumperFunction
J1 (File)Master control panel ground
J1 (OFF keep off)Master panel ground off (default off)
J2 (AVO file)Analog volume AO output voltage signal, 0-10V
J2 (ACO keep off)Analog AO output current signal, 0-20 mA
J4 (P-I file)Built-in keyboard potentiometer selection (default valid)
J4 (P-E keep off)External keyboard potentiometer selection
J5 (AVI keep off)Analog AI input voltage signal, 0-10V
J5 (ACI keep off)Analog AI input current signal, 0-20 mA

3.8 Wiring Precautions

  • When replacing the motor, the input power supply of the frequency converter must be switched off.
  • Switch the motor or the power frequency power supply only when the frequency converter stops output.
  • To minimize electromagnetic interference, consider additional surge absorption devices for electromagnetic contactors and relays used near the frequency converter.
  • Do not connect the AC input power supply to the frequency converter output terminals U, V, W.
  • The external control line of the frequency converter should be equipped with an isolation device or a shielding line.
  • The input command signal line should be wired separately, preferably away from the main circuit line.
  • When the carrier frequency is less than 4 KHz, the maximum distance between the frequency converter and the motor should be within 50 meters. For carrier frequencies greater than 4 KHz, reduce this distance and lay wiring in metal pipe.
  • When the frequency converter is equipped with peripheral equipment (filters, reactors, etc.), measure insulation resistance to ground with a 1000V megohm meter (should be above 4 megohm).
  • Phase capacitors or resistance absorbers cannot be installed at the output ends of the frequency converter U, V and W.
  • If frequent starting is required, use the COM/RUN of the control terminal for start/stop operation to avoid damage to the rectification bridge.
  • Grounding terminal G must be reliably grounded (impedance below 100 Ω) to prevent accidents.
  • Main circuit wiring should conform to national electrical regulations.

4. Operation

4.1 Panel Operation Demonstration

Watch this video for a demonstration of the SU600 inverter's panel operation, showing how to adjust frequency and control the motor.

Video demonstrating the adjustment of frequency and motor speed using the SU600 inverter's control panel.

SU600 Control Panel Layout

Detailed view of the SU600 control panel, highlighting programming, run, stop, and incremental/decremental keys.

4.2 Communication Protocol

The SU600 inverter supports Modbus RTU mode for communication. Information is transmitted in 8-bit bytes, with each 8-bit byte divided into two 4-bit 16-decimal characters.

RTU Mode and Format

The format for each byte in RTU mode includes: 1 start bit, 8 data bits (low send first), 1 stop bit, and selectable parity bit. Error checking is performed using Cyclic Redundancy Check (CRC).

Function Code Description

Function Codes
FCFunction Declaration
03Read the register
06Write register

Register Address

Register Addresses
Register FunctionAddress
Control command input2000H
Monitoring parameter reading (d-00-d-31)1000H~001FH
Communication frequency setting2001H
User parameter setting (F0.00 to F8.06)0000H~0806H
Parameter setting of the manufacturer (F9.00~F9.10)0900H~090AH

Parameter and Address Description of Communication Protocol

Communication Protocol Parameters
Function DeclarationAddress DefinitionData Meaning DescriptionR/W
Communication control command2000H0001H: StopW
0012H: Forward turn operationW
0013H: Forward point operationW
0022H: Reverse operationW
0023H: Reverse point operationW
Communication to set frequency address2001HSet frequency range of communication is -10000 to 10000. Note: The communication set frequency is the percentage relative to the maximum frequency, ranging from -100.00% to 100.00%.W
Communication control command2002H0001H: External fault inputW
0002H: Fault resetW
Read the description of the operation/shutdown parameters2102HSet frequency (two decimal places)R
2103HOutput frequency (two decimal places)R
2104HOutput current (to one decimal place)R
2105HBus voltage (one decimal place)R
2106HOutput voltage (one decimal place)R
2107HAnalog input AI (two decimal places)R
2108HContinue to haveR
2109HCurrent gauge valuesR
210AHMotor speedR
210BHAnalog output AO (two decimal places)R
210CHContinue to haveR
210DHFrequter temperature (one decimal place)R
210EHPID feedback value (two decimal places)R
210FHPID Setpoint (two decimal places)R
2110HContinue to haveR
2111HPulse input frequencyR
2112HThe current failureR
2113HThe current timingR
2114HEnter terminal statusR
2115HOutput terminal statusR
2116HOperation/Downtime, Forward/Reverse, DC Brake, Overvoltage limit, etc.R
2101HRun, Shutdown, Forward, Reverse, Communication given, Analog input, etc.R
2100HFault code description (e.g., No abnormality, Module failure, Overvoltage)R

4.3 Parameter Settings

The SU600 inverter features extensive parameter settings for fine-tuning its operation. Parameters are categorized into several groups:

  • F0 Group: Basic Running Parameters (e.g., Motor control mode, Maximum output frequency, Acceleration time)
  • F1 Group: Auxiliary Running Parameters (e.g., Start way, Frequency of starting, Downtime method)
  • F2 Group: Analog and Numerical Input and Output Parameters (e.g., AI input lower/upper limit voltage, Filtering time constant, AO analog quantity output terminal function selection)
  • F3 Group: PID Parameters (e.g., PID function setting, Feedback channel gain, Proportional gain P)
  • F4 Group: Advanced Functional Parameters (e.g., Motor rated power, Energy consumption brake start voltage, Speed loop proportional gain)
  • F5 Group: Protective Function Parameters (e.g., Motor overload protection factor, Under-pressure protection level, Reduced-down voltage limit factor)
  • F6 Group: Communication Parameters (e.g., This machine address, MODBUS Communication configuration, Communication timeout check-out time)
  • F7 Group: Supplementary Functional Parameters (e.g., Counting and timing mode, Counter reset value setting, Pop frequency control)
  • F8 Group: Management and Display Parameters (e.g., Run to monitor the primary parameter project selection, Parameter initialization)
  • F9 Group: Manufacturer's Parameters (e.g., Manufacturer password)
  • Group d: Monitoring the Parameter Group (e.g., Output Frequency, Set Frequency, Output voltage)

For detailed tables and descriptions of each parameter, please refer to the full user manual PDF: SU600 Series Vector Frequency Inverter User Manual (PDF).

5. Troubleshooting

This section provides common anomalies and their corresponding countermeasures.

5.1 Common Anomalies and Countermeasures

Common Anomalies and Countermeasures
Abnormal PhenomenaPossible Causes and Countermeasures
The keyboard is not displayedCheck power failure, input power supply short of phase, or wrongly connected input power cord.
The keyboard is not displayed, but the in-machine charging indicator light is onCheck wiring and socket related to the keyboard; measure control power supply voltage.
The motor has a buzzing soundMotor load is too heavy; try to reduce the load.
No abnormalities were foundConfirm if in trip state or not reset; check keyboard reset; try restoring factory values.
The motor cannot increase and slow down smoothlyAcceleration/deceleration time setting is inappropriate; current limit set too small; overvoltage protection during deceleration.
The motor can rotate but cannot adjust the speedUpper/lower frequency limits are not appropriate; frequency setting is low or frequency gain setting is too small.
The motor rotates in the opposite directionAdjust the phase sequence of the output terminals U, V, and W; set running direction (F0.12=1) to reverse.

5.2 Fault Codes

The following table lists common fault codes and their possible causes and troubleshooting steps.

Group E - Fault Codes
Fault CodeNamePossible Cause of FailureTroubleshooting
E0C1Overflow in the accelerated operationAcceleration time too short; frequency converter power too small; improper V/F curve or torque lift setting.Extend acceleration time; choose higher power converter; adjust V/F curve or torque lift amount.
E0C2Overcurrent during deceleration operationDeceleration time too short; frequency converter power too small; low grid voltage.Extend deceleration time; choose higher power converter; check input power.
E0C3Overflow during running at a constant speedMutations or abnormalities occurred in the load; frequency converter power too small.Check or reduce load for mutations; choose higher power converter.
EHU1Overvoltage in the deceleration operationInput voltage exception; start motor in rotation.Check input power; set to start after DC braking.
EHU2Overvoltage in the deceleration operationDeceleration time too short; input voltage exception.Extend deceleration time; check input power.
EHU3Overpressure in running at uniform speedInput voltage exception.Check input power.
EHU4Overpressure during shutdownInput voltage exception.Check the power voltage.
ELUOUnder pressure in operationInput voltage abnormal or relay not engaged; Frequter output short circuit or grounding.Check power supply voltage or seek service from manufacturer; check motor wiring.
ESC1Under pressure in operationFrequency converter instantaneous overcurrent; control board abnormal or seriously disturbed; power device damage.See Overflow Countermeasures; seek service from manufacturer.
E-OHRadiator overheatingAmbient temperature too high; fan damage; air duct blocked.Reduce ambient temperature; change fan; unclog air duct.
EOL1Frequency converter overloadPower grid voltage too low; acceleration time too short; motor load heavy; improper V/F curve or torque lift setting.Check power grid voltage; extend acceleration time; choose larger power converter; adjust V/F curve or torque lift amount.
EOL2Motor overloadMotor blocking rotation or load mutation too large; motor overload protection factor not set correctly.Check the load; set motor overload protection factor correctly.
E-EFExternal equipment failureExternal equipment fault input terminal is closed.Disconnect external equipment fault input terminal and clear fault.
EPOFDual CPU communication failureA CPU communication failure.Seek service from the manufacturer.
EPIDPID feedback disconnectionPID feedback line loose; feedback amount less than disconnection detection value.Check feedback connection; adjust test input threshold value.
E485A RS485 communication failureUpper machine port rate mismatch; RS485 channel interference.Adjust the Porter rate; check communication line shielding and wiring.
ETUNMotor tuning faultMotor parameter set wrong.Reset motor parameters.
ECCFCurrent detection failureCurrent sampling circuit fault; auxiliary power failure.Seek service from the manufacturer.
EEEPEEPROM Read and write errorEEPROM hitch.Seek service from the manufacturer.
EPLIOutput phase-deficiency protectionOutputs U, V, and W have a missing phase.Check the output wiring.
EPAOFault of explosive pipeFeedback pressure less than low pressure detection threshold or equal to high pressure detection threshold.Test the feedback line or adjust the high and low pressure valves.

6. User Tips

  • Ensure all wiring connections are secure and correctly terminated to prevent intermittent operation or faults.
  • For optimal performance, regularly check the motor parameters and adjust them as needed for your specific application.
  • If you encounter any issues, always refer to the troubleshooting section first before contacting support.

7. Warranty and Support

7.1 Certificate of Qualification

This product has been inspected to meet quality standards and is allowed to leave the factory. A printing certificate is included with the product.

7.2 Technical Support

For any questions or technical assistance not covered in this manual, please contact our customer service staff. Our professionals are dedicated to providing the best possible service.