SUSWE SU600 VFD Inverter User Manual

Model: SU600

1. Introduction

This manual provides essential information for the safe and efficient installation, operation, and maintenance of the SUSWE SU600 series Variable Frequency Drive (VFD) Inverter. The SU600 VFD is designed to control the speed of AC motors, converting single-phase 220V input to three-phase 380V output, or single-phase 220V to three-phase 220V, or three-phase 380V to three-phase 380V, depending on the specific model. Please read this manual thoroughly before using the product.

2. Safety Information

  • Ensure all wiring is performed by qualified personnel in accordance with local and national electrical codes.
  • Always disconnect power before performing any installation, wiring, or maintenance.
  • Verify correct voltage and current ratings before connecting the VFD to power and motor.
  • Ensure proper grounding to prevent electrical shock.
  • Do not operate the VFD with damaged cables or loose connections.
  • Keep the VFD away from moisture, direct sunlight, and excessive dust.

3. Product Overview

3.1. Components and Features

The SUSWE SU600 VFD Inverter is a compact and robust device designed for reliable motor speed control. Its main board features waterproof, moisture-proof, and mildew-proof characteristics for enhanced durability.

Front view of the SU600 VFD Inverter showing the display and control buttons.

Figure 1: Front View of SU600 VFD Inverter

Internal components of the SU600 VFD Inverter, highlighting the main board with waterproof, moisture-proof, and mildew-proof characteristics.

Figure 2: Internal Components and Main Board Characteristics

3.2. Control Panel Interface

The VFD features an intuitive control panel for easy operation and monitoring. It includes a digital display and various control buttons:

Detailed view of the SU600 VFD control panel, showing buttons for programming, confirmation, run, stop, and frequency adjustment, along with indicators for FWD, REV, Hz, A, V, and ALM.

Figure 3: Control Panel and Display Interface

  • Display: Shows frequency (Hz), current (A), voltage (V), and fault indicators (ALM).
  • FWD/REV Indicators: Indicate forward or reverse rotation.
  • PRG (Programming Key): Enters programming mode.
  • ENT (Confirm Key): Confirms selections and parameter changes.
  • RUN Key: Starts the motor.
  • STOP/RST Key: Stops the motor or resets alarms.
  • Incremental/Decrement Keys (Up/Down Arrows): Adjust parameters or frequency.
  • Konb (Rotary Encoder): For fine-tuning frequency or parameter values.
  • External Network Port: For external communication or control.

An optional external operation panel and cable can be connected for remote control:

Image showing the SU600 external panel and cable, with dimensions 79mm by 53mm.

Figure 4: External Panel and Cable

Diagram showing how to connect the external operation panel to the SU600 VFD Inverter.

Figure 5: External Operation Panel Connection

4. Specifications

AttributeValue
Brand NameSUSWE
Model NumberSU600
TypeDC/AC Inverters
Output TypeSINGLE (refers to single VFD unit, not output phase)
Output Power0.75-5.5KW
Output Current2.5-13A
Output Frequency50-400HZ
Size147*72*119mm / 185*87*138mm
Weight1-2Kg
OriginMainland China
CertificationCE, FCC, RoHS

4.1. SU600 Frequency Converter Series Index

Table showing SU600 frequency converter series index with power supply capacity, rated input/output current, and adapted motor KW/HP for various voltage grades.

Figure 6: SU600 Series Index Table

Frequency Converter ModePower Supply Capacity (kVA)Rated Input Current (A)Rated Output Current (A)Adapted Motor (KW)Adapted Motor (HP)
Single Phase 220V into Three Phase 380V 50/60Hz
SU600-0R75G11.53.42.50.751
SU600-1R5G135.83.71.52
SU600-2R2G1410.552.23
SU600-4R0G18.914.6945
SU600-5R5G11126135.57.5
Single Phase 220V into Three Phase 220V 50/60Hz
SU600-0R75G21.58.240.751
SU600-1R5G231471.52
SU600-2R2G24239.62.23
SU600-3R7G25.531173.74
SU600-5R5G28.935255.57.5
Three-phase 380V into Three-phase 380V 50/60Hz
SU600-0R75G31.53.62.50.751
SU600-1R5G335.14.11.52
SU600-2R2G346.15.82.23
SU600-4R0G38.910.5945
SU600-5R5G31121135.57.5

5. Installation & Setup

5.1. Wiring Diagram

Refer to the following diagrams for proper wiring connections. Ensure all connections are secure and insulated.

Simplified wiring diagram for the SU600 VFD, showing connections for input power (R, S/L1, T/L2), output power to motor (U, V, W), ground wire, and brake resistor (P+, PB).

Figure 7: Basic Wiring Diagram

Detailed terminal wiring diagram for the SU600 VFD, including connections for circuit breaker, power input, motor output, braking resistor, multifunctional input terminals (X1-X4, COM), external keyboard interface (J11), analog input/output, RS485 communication, and relay output.

Figure 8: Detailed Terminal Wiring Diagram

  • Input Power Connection: Connect the main power supply to terminals R, S/L1, T/L2.
  • Output Power Connection: Connect the motor to terminals U, V, W.
  • Ground Wire: Connect the ground wire to the designated ground terminal.
  • Brake Resistor: For applications requiring rapid deceleration, connect a brake resistor to terminals P+ and PB (CNC machine tool selection).
  • Multifunctional Input Terminals (X1-X4, COM): These terminals can be configured for various control functions (e.g., external start/stop, multi-speed selection).
  • Analog Input (AI): Connect DC 0-10V or DC 0-20mA signals for external frequency control.
  • Analog Output (AO): Provides DC 0-10V or 0-20mA output for monitoring.
  • RS485 Communication: Terminals 485+ and 485- for serial communication.
  • Relay Output (TA, TC): Programmable relay contacts for external control.

5.2. Mounting

Mount the VFD in a well-ventilated area, ensuring adequate clearance for heat dissipation. Avoid mounting in direct sunlight or areas with excessive vibration.

6. Operation

6.1. Basic Panel Operation

The VFD can be operated directly from its control panel. The video below demonstrates basic panel operation, including adjusting frequency and starting/stopping the motor.

Video 1: SU600 Inverter Panel Operation Demonstration

  1. Power On: Ensure all wiring is correct and power on the VFD.
  2. Set Frequency: Use the Incremental/Decrement keys or the rotary Konb to set the desired output frequency (motor speed). The display will show the current frequency in Hz.
  3. Start Motor: Press the RUN button to start the motor.
  4. Stop Motor: Press the STOP/RST button to stop the motor.
  5. Programming: Press the PRG button to enter parameter programming mode. Use the arrow keys and ENT button to navigate and modify parameters.

6.2. External Control

The SU600 VFD supports external control via its multifunctional input terminals, analog inputs, and RS485 communication port. Refer to the detailed wiring diagram (Figure 8) and the full programming manual for specific configurations and parameter settings for external control methods.

7. Maintenance

  • Regular Cleaning: Keep the VFD clean and free from dust and debris. Use a soft, dry cloth for cleaning.
  • Check Connections: Periodically inspect all wiring connections for tightness and signs of wear or damage.
  • Ventilation: Ensure that the cooling fan and ventilation openings are not obstructed to prevent overheating.
  • Environmental Conditions: Operate the VFD within its specified environmental conditions (temperature, humidity) to prolong its lifespan.

8. Troubleshooting

If the VFD is not operating as expected, perform the following basic checks:

  • No Power: Check the main power supply and circuit breaker.
  • Motor Not Running: Verify that the RUN command is active and the frequency setting is not zero. Check motor wiring.
  • Alarm Display (ALM): If an alarm code is displayed, consult the full product manual for specific error code meanings and corrective actions. Press STOP/RST to clear minor alarms after addressing the issue.
  • Incorrect Speed: Check the frequency setting and any external speed control inputs.
  • Overload: If the VFD trips due to overload, reduce the motor load or check for mechanical issues with the motor/driven equipment.

For complex issues or persistent problems, contact technical support.

9. User Tips

  • Factory Reset: If you encounter unexpected behavior or need to revert to default settings, a factory reset might be necessary. Specific instructions for performing a factory reset are typically found in the detailed programming manual or can be obtained from technical support. Proceed with caution as this will erase all custom settings.
  • Parameter Backup: Before making significant changes to parameters, it is advisable to record your current settings. This allows for easy restoration if needed.

10. Warranty & Support

For warranty information, technical support, or service inquiries regarding your SUSWE SU600 VFD Inverter, please refer to the documentation provided at the time of purchase or contact the manufacturer/seller directly. Ensure you have your product model (SU600) and any relevant purchase details available when seeking support.