KONLEN KL-72DTT-Tuya

Contents

KONLEN WIFI Dual Temperature Controller Instruction Manual

Model: KL-72DTT-Tuya

Brand: KONLEN

1. Introduction

The KONLEN WIFI Dual Temperature Controller (Model: KL-72DTT-Tuya) is a versatile smart device designed for precise temperature management. It features two independent relay outputs and is compatible with the Tuya Smart or Smart Life mobile applications, allowing for remote monitoring and control. This controller can operate in various modes, including dual temperature control (heating or cooling), temperature difference control, or alarm output, making it suitable for a wide range of applications such as HVAC systems, hot water engineering, boilers, breeding, hatching, and other intelligent electromechanical equipment.

This manual provides detailed instructions for the safe and efficient use of your KONLEN Dual Temperature Controller. Please read it thoroughly before installation and operation.

2. Product Overview

2.1. Product Versions

The controller is available in two versions:

  • Version 1: Powered by AC220V (compatible with 210V to 240V).
  • Version 2: Powered by DC12V. Note: The DC12V power adapter is not included and must be supplied by the user (≥1A recommended).

Important: To prevent damage to the device, always select the correct version and ensure the power voltage matches the device's requirements.

2.2. Front Panel Display and Buttons

Front view of KONLEN Dual Temperature Controller with labeled display and buttons

Image: Front view of the controller showing the digital display and control buttons.

  • A: Displays the real-time temperature of Channel 1 sensor.
  • B: Displays the real-time temperature of Channel 2 sensor.
  • C: Status indicator for CH1 relay output. It flashes when the relay is closed.
  • D: Status indicator for CH2 relay output. It flashes when the relay is closed.

Buttons:

  1. Left Button (▼): Relay CH1 manual switch or for parameter setting. Short press to decrease temperature by 0.1; long-press to decrease temperature quickly.
  2. Right Button (▲): Relay CH2 manual switch or for parameter setting. Short press to increase temperature by 0.1; long-press to increase temperature quickly.
  3. Menu Button: Short-press to enter the menu settings.
  4. Exit Button (↩): Short-press to exit settings and return to working mode.

Tip: The CH1 and CH2 manual switches are only effective when the current temperature or temperature difference is within the set start and stop values. They will not function if the temperature is outside this range.

2.3. Wiring Terminals

Back view of KONLEN Dual Temperature Controller with labeled wiring terminals

Image: Rear view of the controller showing the wiring terminals for power, relays, and sensors.

  • Terminal 1: Relay output CH1 normal open (N.O.)
  • Terminal 2: Common (COM) for relay CH1
  • Terminal 3: Relay output CH1 normal closed (N.C.)
  • Terminal 4 & 5: Power input (AC220V or DC12V, depending on version)
  • Terminal 6: Relay output CH2 normal open (N.O.)
  • Terminal 7: Relay output CH2 normal closed (N.C.)
  • Terminal 8: Common (COM) for relay CH2
  • Terminal 9 & 10: Connect with Sensor CH1
  • Terminal 10 & 11: Connect with Sensor CH2

3. Setup and Installation

3.1. Physical Installation

The controller is designed for embedded installation. Ensure adequate space and ventilation around the device.

3.2. Wiring Instructions

Carefully follow the wiring diagrams below based on your intended application. Ensure all connections are secure and correct to prevent damage or malfunction.

3.2.1. Dual Temperature Control (Heating/Cooling)

Wiring diagram for CH1 and CH2 temperature control with heaters/freezers

Image: Wiring diagram for connecting heaters or freezers to Relay CH1 and CH2 for independent temperature control.

3.2.2. Solar Hot Water Circulation System (Temperature Difference Control)

Wiring diagram for solar hot water circulation system using temperature difference control

Image: Wiring diagram illustrating the connection for a solar hot water circulation system, utilizing temperature difference control between a high temperature sensor (boiler) and a low temperature sensor (water pipe) to activate a circulating pump via an AC contactor.

3.2.3. CH2 Alarm Output Wiring

Wiring diagram for CH2 alarm output with a siren

Image: Wiring diagram for connecting a siren to Relay CH2 for alarm output.

3.3. App Installation and WIFI Configuration

The controller uses the Tuya Smart App or Smart Life App. Download and install either app from your device's app store.

3.3.1. Connecting to WIFI

Ensure your WIFI network is 2.4GHz (5GHz networks are not supported).

Screenshot of app asking for Wi-Fi password

Image: App screenshot showing the prompt to enter your Wi-Fi password.

Screenshots of app connecting and device added

Image: App screenshots showing the device connecting to Wi-Fi and successfully being added to the app.

  1. Open the Tuya Smart or Smart Life app.
  2. Follow the in-app instructions to add a new device.
  3. Select the temperature controller from the device list.
  4. Enter your 2.4GHz Wi-Fi network password when prompted.
  5. Place your router, mobile phone, and device as close as possible during the connection process.
  6. Once connected, the device will appear in your app.

4. Operating Instructions

4.1. App Interface Overview

App interface screenshot with numbered features

Image: Detailed view of the KONLEN Dual Temperature Controller app interface with numbered features.

  1. Product Name: Can be edited.
  2. Sensor 1: Displays real-time temperature of sensor CH1.
  3. Sensor 2: Displays real-time temperature of sensor CH2.
  4. CH1 Control Mode: Set to Heating or Cooling.
  5. CH2 Control Mode: Set to Heating, Cooling, Temperature Difference, or Alarm Output.
  6. Relay CH1 Switch: Manual ON/OFF for Relay CH1.
  7. Relay CH2 Switch: Manual ON/OFF for Relay CH2.
  8. CH2 Mode Options: Allows setting CH2 working mode (Heating, Cooling, Alarm Output, Temperature Difference).
  9. Alarm On/Off: Enable/disable alarm message push notifications.
  10. Log: Access history records.
  11. CH1 CH2 Sensor Status: Displays sensor status (Normal, Error, Temperature Up Limit, Temperature Lower Limit Alarm, etc.).
  12. Temp_diff: Displays temperature difference between Sensor 1 and Sensor 2.
  13. CH1 Start/Stop Temperature: Set upper and lower temperature limits for Relay CH1.
  14. CH2 Lower/Upper Limit: Set upper and lower temperature limits for Relay CH2.
  15. Alarm Lower Limit: Set the lower limit for temperature alarm.
  16. Alarm Upper Limit: Set the upper limit for temperature alarm.
  17. CH1/CH2 Calibration: Calibrate temperature for Sensor 1 and Sensor 2.

4.2. Control Modes

4.2.1. Dual Temperature Control (Heating or Cooling)

Diagram showing heating and cooling modes based on temperature thresholds

Image: Visual representation of heating and cooling modes. When temperature is above 30°C, start exhaust fan (cooling). When temperature is below -10°C, start heater (heating).

Sensor CH1 controls the equipment connected to Relay CH1 for heating or cooling. If the start temperature is greater than the stop temperature, it operates in cooling mode. If the start temperature is less than the stop temperature, it operates in heating mode.

Sensor CH2 controls the equipment connected to Relay CH2 for heating or cooling:

  • Heating Mode: If the current temperature ≤ CH2 lower limit, Relay CH2 turns ON. If the current temperature ≥ CH2 upper limit, Relay CH2 turns OFF.
  • Cooling Mode: If the current temperature ≥ CH2 upper limit, Relay CH2 turns ON. If the current temperature ≤ CH2 lower limit, Relay CH2 turns OFF.

4.2.2. CH1 Temperature Control, CH2 Temperature Difference Control

Diagram for solar hot water circulation system using temperature difference control

Image: Wiring diagram for a solar hot water circulation system, demonstrating temperature difference control.

Sensor CH1 controls the equipment connected to Relay CH1 for heating or cooling (as described in 4.2.1).

The temperature difference between Sensor CH1 and CH2 controls Relay CH2. The temperature difference is calculated as: High Temperature Probe Value - Low Temperature Probe Value.

  • If the current temperature difference ≥ temperature upper limit, Relay CH2 turns ON.
  • If the current temperature difference ≤ temperature lower limit, Relay CH2 turns OFF.

4.2.3. CH1 Temperature Control, CH2 Alarm Output Control

Wiring diagram for CH2 alarm output with a siren

Image: Wiring diagram for connecting a siren to Relay CH2 for alarm output.

Sensor CH1 controls the equipment connected to Relay CH1 for heating or cooling (as described in 4.2.1).

If CH2 working mode is set to 'Alarm Output', you can connect a siren to Relay CH2. The siren will activate (sound and flash) when the current temperature of Sensor CH2 exceeds the preset upper limit or falls below the preset lower limit.

4.3. Upper/Lower Temperature Limit Alarm

App screenshot showing alarm limit settings

Image: App interface for setting temperature alarm limits.

You can set upper and lower limit values for temperature alarms. For example, if the temperature range is set to 12.5°C to 37.9°C, the controller will operate normally within this range. If the temperature falls below 12.5°C or rises above 37.9°C, an alarm notification will be pushed to your smartphone via the app.

Note: Notification authority and the Alarm function must be enabled in the app settings for alarms to function correctly.

4.4. Demo Test Video

Play video
Watch video online

Video: A demonstration of the KONLEN WIFI Dual Temperature Controller in action, showing how it responds to temperature changes in hot and cold water, and how the app controls heating and cooling relays.

5. Maintenance

  • Sensor Cable Extension: The standard temperature sensor cable length is 2 meters. Users can extend the cable length up to a maximum of 20 meters. Ensure proper connections when extending cables to maintain accuracy.
  • Relay Lifespan: The relays have a lifespan of 100,000 cycles. Regular checks of connected equipment are recommended.
  • Load Capacity: The contact current capacity is 10A. It can control a 2000W resistive load or a 500W motor/water pump. For larger loads, it is essential to add AC contactors to prevent overheating and potential fire hazards.
  • Cleaning: Keep the device clean and free from dust. Use a dry, soft cloth for cleaning. Do not use abrasive cleaners or solvents.

6. Troubleshooting

  • Device not powering on: Ensure the correct power voltage (AC220V or DC12V) is supplied according to your device version. Check all power connections.
  • Temperature readings are inaccurate: The measurement error is ±1°C. You can calibrate the sensors via the app (refer to App Interface Overview, point 17). Ensure sensors are properly immersed and not damaged.
  • Relays not activating: Check the set start and stop temperatures/limits in the app. Verify that the manual switches are not overriding automatic control. Ensure the current temperature is within the active range for the set mode.
  • No app notifications for alarms: Confirm that 'Notification authority' and 'Alarm function' are enabled in your phone's settings and within the app (refer to App Interface Overview, point 9).
  • Cannot connect to WIFI: Ensure your router is broadcasting a 2.4GHz Wi-Fi signal. The device does not support 5GHz Wi-Fi. Place the device close to the router during initial setup.
  • Device burning/overheating: This is a critical safety concern. Immediately disconnect power. Ensure that the connected load does not exceed the device's capacity (2000W resistive, 500W motor). For larger loads, an external AC contactor is mandatory.

7. Specifications

FeatureSpecification
Product Dimension83mm (L) × 72mm (W) × 72mm (H)
InstallationEmbedded Installation
Power Voltage OptionsAC220V (210V-240V) or DC12V (adapter not included)
Sensor InterfaceTwo temperature sensor interfaces
Temperature Detection Range-35℃ to +140℃
Measurement Error±1℃ (calibratable)
Sensor Cable Length2 meters (extendable up to 20 meters Max)
Relay OutputsTwo (Normal Open or Normal Closed)
Relay Lifespan100,000 times
Contact Current Capacity10A (inductive load 2A)
Max Load Capacity2000W resistive load or 500W motor/water pump
Working Environment-10℃ to 50℃
WIFI ConnectivityWi-Fi 2.4GHZ B/G/N (5G not supported)

8. User Tips

  • Always double-check your wiring against the provided diagrams before applying power. Incorrect wiring can damage the device or connected equipment.
  • For optimal performance and safety, ensure that the power supply voltage matches the specific version of your controller.
  • If you need to control high-power devices (e.g., resistive loads over 2000W or motors/pumps over 500W), always use an external AC contactor. This prevents overloading the internal relays and ensures safe operation.
  • When setting up temperature alarms, remember to enable both the 'Notification authority' in your phone's system settings and the 'Alarm function' within the Tuya Smart/Smart Life app to receive alerts.
  • If experiencing connectivity issues, confirm your Wi-Fi network is 2.4GHz. This controller does not support 5GHz Wi-Fi. Try moving the device closer to your router during setup.
  • The temperature sensors can be extended up to 20 meters. Use appropriate gauge wiring for extensions to avoid signal degradation.

9. Warranty and Support

For any technical assistance, troubleshooting beyond this manual, or warranty inquiries, please contact the seller or manufacturer directly. Provide your product model number (KL-72DTT-Tuya) and a detailed description of the issue for efficient support.

Documents and downloads

Ask a question about this manual

Ask about setup, troubleshooting, compatibility, parts, safety, or missing instructions. Manuals+ will review the question and use this page’s manual context to help answer it.