1. Overview
The PowMr HHJ-60A MPPT Solar Charge Controller is an advanced maximum power point tracking (MPPT) technology-based device designed for solar systems. It offers a charge controller conversion efficiency of up to 97%.
Key features include:
- 100% MPPT technology for optimal power harvesting.
- Built-in DSP controller with high performance.
- Automatic battery voltage detection for 12V, 24V, 36V, and 48V battery banks.
- Three-stage charging process to optimize battery performance.
- Multi-function LCD display for monitoring system data and statuses.
- Comprehensive protection features including reverse polarity protection for solar panels, overcharge protection, and over-temperature protection.
- Suitable for various battery types: sealed lead acid, vented Gel, and Lithium batteries.
- Easy to mount and install.
Note: The output terminal is designed for low-power loads (lamps only: 12V system less than 60W, 24V/36V/48V system less than 100W). Connecting to other loads may cause damage. The output for the battery does not have reverse polarity protection.
Video: Unboxing and initial overview of the PowMr HHJ-60A MPPT Solar Charge Controller, demonstrating its components and basic setup.
2. Important Safety Instructions
Please read all instructions and cautions carefully before installation and operation. This manual uses the following symbols to indicate potentially dangerous conditions or important safety information:
⚠ WARNING: Indicates a potentially dangerous condition. User extreme caution when performing this task.
CAUTION: Indicates a critical procedure for safe and proper operation of the controller.
NOTE: Indicates a procedure or function that is important to the safe and proper operation of the controller.
2.1. General Safety Information
- Read all instructions and cautions in the manual before beginning installation.
- There are no serviceable parts inside this controller. DO NOT disassemble or attempt to repair it.
- DO NOT allow water to enter the controller.
- Ensure all connections going into and from the controller are tight.
2.2. Charge Controller Safety
- NEVER connect the solar panel array to the controller without a battery. The battery MUST be connected first.
- Ensure input voltage does not exceed 190 VDC to prevent permanent damage. Use the Open Circuit Voltage (Voc) to ensure the voltage does not exceed this value when connecting panels together.
2.3. Battery Safety
- Use only sealed lead-acid, flooded, gel, or lithium batteries which must be deep cycle.
- Explosive battery gases may be present while charging. Ensure adequate ventilation to release gases.
- Be careful when working with large lead-acid batteries. Wear eye protection and have fresh water available in case of contact with battery acid.
- Carefully read battery manuals before operation.
- DO NOT let the positive (+) and negative (-) terminals of the battery touch each other. Recycle batteries when replaced.
- Over-charging and excessive gas precipitation can damage battery plates and activate material shedding. Too high or too long an equalizing charge may cause damage. Review specific requirements for the battery used.
- Equalization is only for non-sealed/vented/flooded/wet cell lead-acid batteries.
- DO NOT equalize VRLA type AGM/Gel/Lithium cell batteries UNLESS permitted by the battery manufacturer.
⚠ WARNING:
• Connect battery terminals to the charge controller BEFORE connecting the solar panel(s) to the charge controller. NEVER connect solar panels to the charge controller until the battery is connected.
• DO NOT connect any inverters or battery charger into the load terminal of the charge controller.
• Once equalization is active in battery charging, it will not exit this stage unless there is adequate charging current from the solar panel. There should be NO load on the batteries when in the equalization charging stage.
3. Setup & Installation
Follow these steps for proper installation:
3.1. Instruction Notes
- 1st step: Connect the batteries
Connect the battery connection cable with the correct polarity to the middle pair of terminals on the solar charge controller (marked with the battery symbol). If the system is 12V, ensure your battery voltage is more than 12V for the controller to boot up. - 2nd step: Connect the solar panel
Ensure that the PV modules are protected from incident light. Ensure the solar panel input does not exceed the maximum permissible input current. Connect the PV modules connection cable to the correct polarity of the left pair of terminals on the solar charge controller (marked with the PV modules symbol). - 3rd step: Connect loads
Connect the load cable to the correct polarity of the right pair of terminals on the solar charge controller (marked with the lamp symbol). To avoid any voltage on the wires, connect the wire to the load before connecting to the controller. - 4th step: Final work
Tighten all cables connected to the controller and remove all debris around the controller, leaving a space of approximately 5.91 inches (15 cm) for ventilation.
Note: If the reading data of PV or battery is constantly changing, do not worry. The controller is finding the MPP point, which can be caused by insufficient PV input power or voltage. Contact our technical team for assistance if needed.
3.2. Air Circuit Breaker Installation
We strongly recommend connecting a fuse directly to the battery to protect against any short circuit at the battery wiring. Solar PV modules generate current when exposed to light. This current varies with light intensity, but even low light levels can produce full voltage. Protect solar modules from incident light during installation. Never touch uninsulated cable ends, use only insulated tools, and ensure the wire diameter is appropriate for the expected currents of the solar charge controller. Connections must always be made in the sequence described below.

Reminder: It's better to connect two wires to two PV+ and another two wires to two PV-. For BAT+ and BAT-, it's the same way to connect wires.
- Install an air circuit breaker between the controller and batteries. Turn off the circuit breaker, then connect batteries to the controller with correct polarity.
- Install an air circuit breaker between the controller and PV modules. Turn off the circuit breaker, and ensure the PV polarity is correct, then connect wires between PV modules and the controller.
- Turn on the air circuit breaker between the controller and batteries.
- Turn on the air circuit breaker between the controller and PV modules.
- The controller will enter self-test mode. Its LCD will display parameters if all connections are correct. The RUN lamp (under the fan inside the casing) will flash every one second. If the controller does not respond, please re-read the manual or contact support.
3.3. Air Circuit Breaker and Wires Requirement
| Models | Copper wires | Air circuit breakers |
|---|---|---|
| HHJ-60A | 6mm²x2PCS | 100A |
4. Operation
4.1. LCD Display
The LCD provides real-time information about the system's status. The main interface shows PV voltage/output power, battery voltage/charging current, working mode/temperature, and fault codes. A sub-interface provides more detailed settings and readings.

| Item | Description |
|---|---|
| 1 | PV voltage / Output power |
| 2 | Battery voltage / Charging current |
| 3 | Working mode / Temperature |
| 4 | Fault code |
4.2. Working Mode
| Mode | Description |
|---|---|
| 3.0 | Night mode, no charging |
| 4.0 | MPPT mode |
| 7.0 | Absorption mode |
| 8.0 | Floating mode |
4.3. Manual Setting
Reminder: The controller will work fine under default settings except for lithium batteries.
CAUTION: All steps must be carried out when the PV modules are disconnected from the controller.
- Step 1: D00 (Load Working Time)
Press the PRG button, then the LCD displays D00. This setting is for load working time (Default is 24-hour). Press ENT until numbers flash, then use UP/DOWN to set the desired time. Long-press ENT to confirm. The output voltage is the same as the battery. This load output is only for small DC loads less than 5A. If no load is connected, leave it. - Step 2: D01 (Floating Charging Voltage)
Press the UP button, the LCD shows 13.8 (default value). Press ENT until numbers flash, then use UP/DOWN to set the desired voltage. Long-press ENT to confirm. - Step 3: D02 (Absorption Charging Voltage)
Continue to press the UP button, the LCD shows 14.5 (highest absorption charging voltage). Follow the same procedure as D01 to set and confirm the voltage. - Step 4: D03 (Battery Discharge Protection)
Continue to press the UP button, the LCD shows 10.0. This is the protection value for battery discharge. Follow the same procedure as D01 to set and confirm the voltage. This means the output power from OU+ and OU- will be cut off when a 12V battery drops below 10.0V. - Step 5: D04 (Battery Voltage Calibration)
Continue to press the UP button, the LCD shows C12.2. This setting is used to calibrate the battery voltage, ensuring the controller's detected battery voltage matches the actual battery voltage. - Step 6: D05 (Battery Type Setting)
Continue to press the UP button, the LCD shows the battery type setting program. The default option is USE. The available battery types are:Type Description SEL Sealed Lead-Acid Battery GEL Gel Sealed Lead-Acid Battery FLd Flooded Lead-Acid Battery L04 4-series Lithium Iron Phosphate Battery L08 8-series Lithium Iron Phosphate Battery L15 15-series Lithium Iron Phosphate Battery L16 16-series Lithium Iron Phosphate Battery USE User-defined Battery Type CAUTION: When selecting SEL, GEL, and FLd battery types, the controller automatically detects the system voltage.
- Step 7: D06 (User-defined System Voltage)
If you choose the USE option in the D05 battery type setting, you will need to manually configure the system voltage in the D06 setup program. The configuration range is 12V/24V/36V/48V.
CAUTION: This value is for one 12V battery. If multiple batteries are in series, the controller will automatically multiply the voltage proportionally, and the LCD will only display the voltage of one battery (e.g., for a 4x12V battery bank, setting 14.1V will result in a 4x14.1V charge voltage, but the LCD will still display 14.1V).
Press ESC to exit the setting menu.
Reminder: After setting all steps, please disconnect the battery. Reconnect the controller to verify successful settings. Once all settings are confirmed, connect the PV modules to the controller.
5. Troubleshooting & Protections
5.1. Troubleshooting Guide
| Code | Description | How to solve |
|---|---|---|
| 18 | Input PV voltage is low | Increase the PV voltage |
| 60 | Over-temperature protection | Fan will work and temperature reduction automatically |
| 63 | Battery voltage is high | Battery high voltage protection and wait for recovery |
| 65 | Battery voltage is low | Battery over-discharge and wait for recovery |
| 71 | Input PV voltage is high | Decrease the PV voltage |
| 73 | Over-charging current | Decrease the PV power |
5.2. Protections
- PV Over Current: The controller will limit charging power to the rated charge power. An over-sized PV array will not operate at maximum power point.
- PV Short Circuit: When a PV short circuit occurs, the controller will stop charging. Remove the short circuit to resume normal operation.
- PV Reverse Polarity: Full protection against PV reverse polarity. No damage to the controller. Correct the connection to start normal operation.
- Battery Over Voltage: If other energy sources charge the battery, and the battery voltage exceeds 15.5V (for 12V system), 31.0V (for 24V system), 46.5V (for 36V system), or 62.0V (for 48V system), the controller will stop charging to protect the battery from overcharging damage. (Note: 'Stop charging' means the charging current becomes very low).
- Battery Over Discharge: When battery voltage drops to the set low voltage disconnect point, the controller will stop discharging to protect the battery from over-discharging damage.
- Load Over Current Protection: If the load current exceeds 1.25 times the maximum load current rating, the controller will disconnect the load.
- Load Short Circuit Protection: Once a load short circuit happens, the Load Short circuit protection will activate automatically.
- Over Temperature Protection: The controller includes mechanisms to protect against overheating.
6. Specifications
| Parameter | Value (HHJ-60A) | |||
|---|---|---|---|---|
| Model Name | MPPT-60A | |||
| Charging mode | MPPT Maximum power point tracking automatically | |||
| Charging | 3-stage: constant current (MPPT), constant voltage (Absorption Voltage), floating charge | |||
| System type | DC12V/24V/36V/48V Recognition automatically | |||
| System voltage automatic recognition | 12V system (DC9V-DC15V) 24V system (DC18V-DC29V) 36V system (DC30V-DC39V) 48V system (DC40V-DC60V) | |||
| Soft start time | ≤1S | |||
| Dynamic response and recovery time | ≥98.1% (Voc is 1.5 or 2 times than battery, then it’s best efficiency) | |||
| PV utilization | ≥99% | |||
| Input specification | ||||
| Voc from PV (Make sure Voc of PV meets requirement. Voc is 1.5 or 2 times than battery for best efficiency.) | 12V system (DC20V~DC80V) 24V system (DC37V~DC105V) 36V system (DC50V~DC160V) 48V system (DC72V~DC160V) | |||
| The maximum PV input voltage (Voc) | DC190V (Controller can’t work at this voltage for long duration, will break controller. Refer to Input voltage from PV.) | |||
| The maximum PV input power (Total power rated of PV can’t be over this watt that will break the controller.) | 12V (360W) 24V (720W) 36V (1080W) 48V (1440W) | 12V (480W) 24V (960W) 36V (1400W) 48V (1700W) | 12V (600W) 24V (1200W) 36V (1800W) 48V (2200W) | 12V (720W) 24V (1440W) 36V (2100W) 48V (2800W) |
| Output specification | ||||
| Selectable battery type (default is Sealed) | Vented/Sealed/Gel/NiCd/Lithium battery (defined voltage for other battery by user) | |||
| Absorption Charging Voltage | Refer to Batteries charging reference | |||
| Floating Charging Voltage | Refer to Batteries charging reference | |||
| Overcharging protection voltage | 12V system (15V) 24V system (30V) 36V system (45V) 48V system (60V) | |||
| Rated output current | 30A | 40A | 50A | 60A |
| Temperature Coefficient | ±0.02%/centi-degree | |||
| Automatic temperature compensation | 14.2V-(Max temperature-25 centi-degree)*0.3 | |||
| Output voltage ripple-peak | 100mV | |||
| Output voltage accuracy | ≤±1% | |||
| Input Anti-intrusion protection | Yes | |||
| Temperature Protection | 75°C | |||
| Temperature increased protection | Output power will reduce when it’s more than 70°C Output power will be normal when it’s less than 55°C | |||
| Fan-on temperature | >40°C | |||
| Fan-off temperature | <35°C | |||
| Acoustic noise | ≤40dB | |||
| Cooling way | Forced air cooling | |||
| Components | Imported materials, Accord to EU standards, Industrial grade range. | |||
| Environmental requirements | Meet 2002/95/EC; No cadmium, hydrides and fluorides | |||
| Security Level | Accord to CE, PSE, FCC, EMC, EN60950 | |||
| Electromagnetic compatibility | Accord to EN61000, EN55022, EN55024 | |||
| Enclosure | IP21 | |||
| Environmental temperature | -20°C ~ +55°C | |||
| Storage temperature | -40°C ~ +75°C | |||
| Size (mm)/(in) | 214x115x50mm / 8.43x4.53x1.97in | |||
| Net weight (Kg)/(lb) | 1.1 / 2.43 | |||
| Gross weight (Kg)/(lb) | 1.2 / 2.65 | |||

7. Content Included
The product package typically includes:
- 1x MPPT Solar Charge Controller (HHJ-60A)
- 4x Corner connections
- 4x Screws for controller casing
- 1x User Manual (English)

8. User Tips
No specific user tips were found in the provided reviews or Q&A content.
9. Warranty & Support
9.1. Warranty Regulations
Any damaged unit caused by the user's failure to install, disassemble, or incorrect use of this product may void the warranty.
- Within 30 days from the date of purchase, a faulty controller will be replaced free of charge under normal use (with authorization from technical personnel).
- Within 2 years from the date of purchase, a faulty controller will be repaired free of charge.
Note: Disassembling the product privately voids the warranty.
9.2. Liability Disclaimer
The manufacturer shall not be liable for damages, especially to the battery, caused by use other than as intended or as mentioned in this manual, or if the recommendations of the battery manufacturer are neglected. The manufacturer is not liable if service or repair has been carried out by any unauthorized person, or due to unusual use, wrong installation, or bad system design.
9.3. Contact Information
For support or inquiries, please use the following contact details:
- Tel/Fax: +86 755-28219903
- Email: support@powmr.com
- Web: www.powmr.com
- Address: Henggang Street, Longgang District, Shenzhen, Guangdong, China