1. Introduction
The TOMZN TOVPD1 series is a multi-functional protective device designed to safeguard electrical appliances and circuits from voltage and current anomalies. It offers comprehensive protection against over-voltage, under-voltage, and over-current conditions, featuring automatic recovery once normal parameters are restored. Certain models (TOVPD1-63VAE) also include a cumulative energy (kWh) display and a prepaid function.
Key Functions:
- Over-voltage protection
- Under-voltage protection
- Over-current protection
- Automatic recovery
- Real-time Voltage display (measurement)
- Real-time Current display (measurement)
- Voltage calibration
- Restore factory settings
- Fault inquiry
- Cumulative energy (kWh) display (TOVPD1-63VAE models)
- Prepaid function (TOVPD1-63VAE models)
2. Specifications
The device is designed for 35mm DIN rail installation and features a robust construction with a built-in magnetic latching relay for high current impact resistance.
General Parameters (TOVPD1-60-EC Series):
| Parameter | Value (230V Version) | Value (110V Version) |
|---|---|---|
| Model Number | TOVPD1-60-EC (Voltage/Current Type), TOVPD1-63VAE (Voltage/Current/kWh Type) | |
| Power Supply | 230VAC 50/60Hz | 110VAC 50/60Hz |
| Max. Loading Power | 1~40A / 1~63A Adjustable (default: 40A/63A) | 1~63A Adjustable (default: 63A) |
| Over-voltage Protection Range | 230V~300V~OFF (default: 270V) | 80V~300V~OFF (default: 145V) |
| Over-voltage Recovery Range | 225V~295V (default: 250V) | 75V~295V (default: 140V) |
| Over-voltage Action Time | 0.1s~30s (default: 0.5s) | |
| Over-voltage Recovery Delay Time | 1s~500s (default: 30s) | |
| Under-voltage Protection Range | 140V~210V~OFF (default: 170V) | 80V~300V~OFF (default: 90V) |
| Under-voltage Recovery Range | 145V~215V (default: 190V) | 85V~305V (default: 95V) |
| Under-voltage Action Time | 0.1s~30s (default: 0.5s) | |
| Under-voltage Recovery Delay Time | 1s~500s (default: 30s) | |
| Over-current Adjustment Range | 1-40A (default: 20A) / 1-63A (default: 40A) | 1-63A (default: 40A) |
| Over-current Action Range | 0.1~30 seconds (default: 0.5s) | |
| Over-current Recovery Delay Time | 1s~500s (default: 30s) | |
| Power-on Delay Time | 1s~500s (default: 10s) | |
| Power Consumption | <2W | |
| Electrical Machinery Life | 100,000 times | |
| Installation | 35mm DIN rail | |
| Certification | CE | |
Dimensions:
- Standard Type (Voltage/Current): 85mm (Height) x 35mm (Width) x 65mm (Depth)
- kWh Type (Voltage/Current/kWh): 85mm (Height) x 36mm (Width) x 45mm (Depth)
3. Installation and Setup
The device is designed for easy installation on a standard 35mm DIN rail. Ensure all power is disconnected before attempting installation.
Mounting:
Simply clip the device onto a 35mm DIN rail. The installation and disassembly process is straightforward.
Wiring Diagram:
Connect the power lines (L and N) to the 'IN' terminals and the load lines to the 'OUT' terminals. Ensure proper polarity. When inserting power lines, screw down to penetrate the insulating layer of the wires for a secure connection.
4. Operation
Display and Indicators:
The device features a dual digital display for real-time voltage and current. Models with kWh functionality will also show cumulative energy consumption. LED indicators provide quick status updates.
- V Display: Shows real-time voltage.
- A Display: Shows real-time current.
- kWh Display: Shows cumulative energy consumption (on TOVPD1-63VAE models).
- >V Indicator: Lights up for Over Voltage condition.
- <V Indicator: Lights up for Under Voltage condition.
- >A Indicator: Lights up for Over Current condition.
- POWER Indicator: Indicates the device is powered on.
Button Functions:
- Power Button (ON/OFF): Press to manually switch the protection function on or off.
- SET Button: Press and hold for more than 3 seconds to enter the setting state. Press again to confirm settings or exit.
- UP/DOWN Adjustment Keys: Used to change setting values when in setting mode.
Setting Parameters:
To adjust protection parameters, press and hold the SET button until the display enters setting mode. Use the UP/DOWN keys to navigate through parameters (A1 to A16) and adjust their values. Press SET again to confirm each parameter and move to the next, or to exit the setting mode.
Parameter List:
- A1: Power-on delay time (1-500s)
- A2: Over-voltage protection value (230-300V)
- A3: Over-voltage recovery value (225-295V)
- A4: Over-voltage recovery delay time (1-500s)
- A5: Over-voltage protection action time (0.1-30s)
- A6: Under-voltage protection value (140-210V)
- A7: Under-voltage recovery value (145-215V)
- A8: Under-voltage recovery delay time (1-500s)
- A9: Under-voltage protection action time (0.1-30s)
- A10: Over-current protection value (0.5-40A/63A)
- A11: Over-current recovery delay time (1-500s)
- A12: Over-current protection action time (0.1-30s)
- A13: Continuous over current faults times
- A14: Voltage calibration
- A15: Current calibration
- A16: Kilowatt-hour calibration
Screen Display Status Codes:
- Over Voltage Protection: Displays "HU V" with the actual voltage flashing.
- Under Voltage Protection: Displays "LU V" with the actual voltage flashing.
- Over Current Protection: Displays "HA A" with the actual current flashing. The protector will reset automatically at the recovery time.
- Kilowatt-hour (kWh) and kW Display: When normally powered on, kWh is displayed by default. Press the UP key to switch and display kW.
Restoring Factory Settings:
To restore the device to its factory default settings, press and hold the DOWN button for more than 12 seconds.
5. Maintenance
The TOMZN protective device is designed for durability and requires minimal maintenance. Keep the device clean and free from dust and moisture. Periodically check the wiring connections to ensure they are secure. Do not attempt to open or repair the device yourself; refer to qualified personnel for any issues beyond basic troubleshooting.
6. Troubleshooting
The device is equipped with a fault inquiry function to help diagnose issues.
Fault Inquiry:
To inquire about faults, press the UP button for more than 12 seconds.
Automatic Recovery:
In case of over-voltage, under-voltage, or over-current faults, the device will automatically disconnect the power supply. Once the voltage or current returns to normal parameters, the device will automatically restore the power supply after the set recovery delay time.
If the device does not recover automatically or displays persistent error codes, verify the input voltage and current are within the normal operating range. If issues persist, consult a qualified electrician.
7. User Tips
- Energy Monitoring: If you need to monitor your electricity consumption, ensure you select the "V A Kwh type" model (e.g., TOVPD1-63VAE) as it includes the cumulative energy (kWh) display.
- Calibration: If you suspect the voltage or current readings are inaccurate, use the voltage (A14) and current (A15) calibration functions in the setting menu to fine-tune the display.
- Power-on Delay: Utilize the adjustable power-on delay (A1) to protect sensitive equipment from immediate power surges after a power outage.
8. Warranty and Support
For warranty information, technical support, or service inquiries, please refer to the official TOMZN website or contact your authorized dealer. Keep your purchase receipt as proof of purchase.