1. Introduction
Thank you for choosing the MASTECH MS5908A/MS5908C Circuit Breaker Analyzer. This device is designed for professional use to analyze circuit breakers, test RCDs (Residual Current Devices) and GFCIs (Ground Fault Circuit Interrupters), and measure voltage. This manual provides essential information for the safe operation, maintenance, and troubleshooting of your analyzer. Please read it thoroughly before use.
2. Safety Information
Always adhere to safety precautions when operating electrical testing equipment. Failure to do so may result in injury or damage to the device.
- Ensure the device is in good working condition before each use.
- Do not use the device if it appears damaged or if the insulation is compromised.
- Always follow local electrical safety codes and regulations.
- Do not attempt to measure voltages or currents exceeding the device's specified limits.
- Keep hands and fingers away from live circuits during testing.
- Replace batteries promptly when the low battery indicator appears to ensure accurate readings.
- The device is rated CAT III 300V. Observe this rating for all measurements.
3. Product Overview
The MASTECH MS5908A/MS5908C is a handheld circuit analyzer designed for comprehensive electrical system diagnostics. It features an LCD display for clear readings and intuitive controls.
3.1 Key Features
- Automatic Power Off: Conserves battery life.
- Data Hold: Freezes the current reading on the display.
- Low Battery Display: Indicates when batteries need replacement.
- RCD/GFCI Testing: Measures trip time and current.
- Voltage and Frequency Measurement.
- Impedance Measurement (Live, Neutral, Earth).
- Voltage Drop Measurement.
3.2 Package Contents
Upon unpacking, verify that all items are present:
- MASTECH MS5908A or MS5908C Circuit Breaker Analyzer
- Power Cord
- Carry Bag
- User's Manual (this document)
- Calibration Certificate (may be included)
- Quick Start Guide (may be included)
- 6x 1.5V AAA Batteries (not included with delivery)


3.3 Device Layout and Dimensions


4. Specifications
4.1 General Specifications (MS5908A & MS5908C)
- Power Supply: 6x 1.5V AAA Batteries (not included)
- Product Size: 194mm x 78mm x 37mm (7.64" x 3.07" x 1.46")
- Product Weight: 254g (0.56lb)
- Certificates: CE / ETL / RoHS
- Safety Rating: CAT III 300V
4.2 MASTECH MS5908A Technical Specifications
| Specification | Range | Resolution | Accuracy |
|---|---|---|---|
| Line Voltage | 85.0~135.0V | 0.1V | ±(1.0%+2) |
| Peak Line Voltage | 120.0~190.0V | 0.1V | ±(1.0%+2) |
| Voltage With Loading Equipments | 10.0~135.0V | 0.1V | ±(2.5%+2) |
| Line Frequency | 45.0~65.0Hz | 0.1Hz | ±(1.0%+2) |
| Impedance-live and Neutral & Earth | 0.00~3.00Ω | 0.01Ω | ±(2.5%+2) |
| >3.00Ω | 0.01Ω | No ensure | |
| Neutral-Ground Voltage | 0.0~10.0V | 0.1V | ±(2.5%+2) |
| RCD Trip Time | 1ms~6.5S | 1mS | ±(1.0%+2) |
| RCD Trip Current | 30mA~37mA | 0.1mA | ±(1.0%+2) |
| GFCI Trip Time | 1ms~6.5S | 1mS | ±(1.0%+2) |
| GFCI Trip Current | 6mA~9mA | 0.1mA | ±(1.0%+2) |
| Voltage Drop | 0.1~99.9% | 0.10% | ±(2.5%+2) |
| Voltage Drop Load Current | 12/15/20A | - | - |
4.3 MASTECH MS5908C Technical Specifications
| Specification | Range | Resolution | Accuracy |
|---|---|---|---|
| Line Voltage | 85.0~265.0V | 0.1V | ±(1.0%+2) |
| Peak Line Voltage | 120.0~375.0V | 0.1V | ±(1.0%+2) |
| Voltage With Loading Equipments | 10.0~265.0V | 0.1V | ±(2.5%+2) |
| Line Frequency | 45.0~65.0Hz | 0.1Hz | ±(1.0%+2) |
| Impedance-live and Neutral & Earth | 0.00~3.00Ω | 0.01Ω | ±(2.5%+2) |
| >3.00Ω | 0.01Ω | No ensure | |
| Neutral-Ground Voltage | 0.0~10.0V | 0.1V | ±(2.5%+2) |
| RCD Trip Time | 1ms~6.5S | 1mS | ±(1.0%+2) |
| RCD Trip Current | 30mA~37mA | 0.1mA | ±(1.0%+2) |
| GFCI Trip Time | 1ms~6.5S | 1mS | ±(1.0%+2) |
| GFCI Trip Current | 6mA~9mA | 0.1mA | ±(1.0%+2) |
| Voltage Drop | 0.1~99.9% | 0.10% | ±(2.5%+2) |
| Voltage Drop Load Current | 5/8/10A | - | - |
5. Setup and Battery Installation
The device requires 6x 1.5V AAA batteries for operation. Ensure batteries are installed correctly before use.
- Locate the battery compartment on the back of the device.
- Open the battery compartment cover.
- Insert 6 AAA batteries, observing the correct polarity (+/-) as indicated inside the compartment.
- Close the battery compartment cover securely.
- Press the power button (ON/OFF) to turn on the device.


6. Operating Instructions
This section details the basic operation of the MASTECH MS5908A/MS5908C Circuit Breaker Analyzer.
6.1 Power On/Off
- Press the ON/OFF button to turn the device on.
- The device will automatically power off after a period of inactivity to save battery.
- To manually turn off, press and hold the ON/OFF button.
6.2 Function Selection
Use the FUNC button to cycle through different measurement modes (e.g., Voltage, Frequency, Impedance, RCD/GFCI Test).
6.3 Data Hold
Press the HOLD button to freeze the current reading on the display. Press it again to release the hold function.
6.4 Backlight
Press the backlight button (light bulb icon) to illuminate the display for use in low-light conditions.
6.5 Performing a Test
- Plug the analyzer into the electrical outlet you wish to test.
- Select the desired measurement function using the FUNC button.
- For RCD/GFCI tests, ensure the correct current setting is selected (if applicable) using the arrow buttons.
- Press the TEST button to initiate the measurement or trip test.
- Observe the readings on the LCD display.
- For RCD/GFCI tests, the device will indicate if the RCD/GFCI trips within the specified time and current.
Important: Always ensure the circuit is safe to test before initiating any measurements, especially RCD/GFCI trip tests which will temporarily cut power to the circuit.
7. Maintenance
Proper maintenance ensures the longevity and accuracy of your MASTECH Circuit Breaker Analyzer.
- Cleaning: Wipe the device with a soft, damp cloth. Do not use abrasive cleaners or solvents.
- Battery Replacement: When the low battery indicator appears, replace all 6 AAA batteries promptly. Remove batteries if the device will not be used for an extended period.
- Storage: Store the device in its carry bag in a cool, dry place, away from direct sunlight and extreme temperatures.
- Calibration: Regular calibration by qualified personnel is recommended to maintain measurement accuracy. Refer to the calibration certificate for recommended intervals.
8. Troubleshooting
This section addresses common issues you might encounter with your device.
| Problem | Possible Cause | Solution |
|---|---|---|
| Device does not power on. | Dead or incorrectly installed batteries. | Check battery polarity and replace with fresh AAA batteries. |
| Inaccurate readings. | Low battery, device needs calibration, or incorrect function selected. | Replace batteries, ensure correct function is selected. Consider professional calibration if issue persists. |
| RCD/GFCI test fails to trip. | Faulty RCD/GFCI, incorrect test procedure, or device malfunction. | Ensure the RCD/GFCI is functional. Re-read operating instructions. If other tests work, the RCD/GFCI might be faulty. If no tests work, the analyzer might be faulty. |
| Display is dim or flickering. | Low battery. | Replace batteries. |
9. User Tips
- Always double-check your connections before initiating any test to prevent false readings or damage.
- For consistent results, perform tests multiple times and compare readings.
- Keep the display clean for optimal visibility.
10. Warranty and Support
For warranty information and technical support, please refer to the documentation provided with your purchase or contact the manufacturer directly. Keep your purchase receipt as proof of purchase for warranty claims.