EARUELETRIC EAMT1-M1

Contents

EARUELETRIC Multifunction Time Delay Relay

Model: EAMT1-M1

1. Introduction

The EARUELETRIC EAMT1-M1 is a versatile multifunction time delay relay designed for a wide range of industrial and home automation applications. It supports a universal AC/DC voltage input from 12V to 240V and offers 10 distinct time delay functions, allowing for precise control over electrical circuits. This manual provides detailed instructions for the safe and effective installation, operation, and maintenance of your time delay relay.

EARUELETRIC Multifunction Time Relay EAMT1-M1

Figure 1: EARUELETRIC Multifunction Time Delay Relay

2. Specifications

Below are the key technical specifications for the EAMT1-M1/EAMT1-M2 series time delay relays:

FeatureSpecification
Model NumberEAMT1-M1 / EAMT1-M2
Voltage RangeAC/DC 12-240V (50-60Hz)
Rated Current16A
Rated Voltage250VAC
TheoryTime Relay
Time Ranges0.1 seconds - 10 days, ON, OFF
Time SettingPotentiometer
Mechanical Life1x107
Electrical Life (AC1)1x105
Reset TimeMax. 200ms
Pollution Degree2
Operating Temperature-20°C to +55°C (-4°F to 131°F)
OriginMainland China
CertificationCE
UseGeneral Purpose
Package Length19 cm
Package Width12 cm
Package Height3 cm
Package Weight0.104 kg
Product dimensions and specifications table for EAMT1-M1/M2

Figure 2: Product Dimensions and Specifications

3. Product Overview

The EAMT1-M1/M2 time delay relay features a compact design suitable for DIN rail mounting. It includes multiple control knobs for setting time ranges and functions, along with indicator lights for power and output status.

3.1. Components

Labeled components of the EARUELETRIC time delay relay

Figure 3: Labeled Components of the Relay

  • Trigger terminal: Input for external trigger signal.
  • Working power input terminal: A1(+) and A2(-) for power supply.
  • Supply indication (green): LED indicating power status.
  • Output indication (red): LED indicating relay output status.
  • Time gear selection: Knob 1 for selecting time range (seconds, minutes, hours, days).
  • Time percentage setting: Knob 2 for fine adjustment of delay time (10% - 100%).
  • 10 delay mode options: Knob 3 for selecting the operating function (A-J).
  • Product model: EAMT1-M1 (Multifunctional type).
  • Second group of conversion contacts: Terminals 25, 26, 28.
  • First set of conversion contacts: Terminals 15, 16, 18.

4. Installation and Setup

4.1. Mounting

The EAMT1-M1/M2 time delay relay is designed for DIN rail mounting. Ensure it is securely fastened to the DIN rail in a suitable enclosure, away from excessive heat, moisture, and vibration.

Two EARUELETRIC relays mounted on a DIN rail

Figure 4: DIN Rail Mounting Example

4.2. Wiring

Refer to the wiring diagram below for proper connection. Ensure all connections are tight and secure. The tightening torque for terminals is 0.4Nm.

Wiring diagram for EARUELETRIC time delay relay with lamp and trigger

Figure 5: Wiring Diagram

  • A1(+) and A2(-): Power input terminals (12-240V AC/DC).
  • S: Trigger terminal.
  • 15-18: Normally Open (NO) contacts.
  • 15-16: Normally Closed (NC) contacts.
  • 25-28: Second set of Normally Open (NO) contacts (for EAMT1-M2).
  • 25-26: Second set of Normally Closed (NC) contacts (for EAMT1-M2).

Example Wiring Explanation (for E mode with trigger):

  • 15-18 are normally open, 15-16 are normally closed.
  • If the working mode is set to E mode, the trigger terminal closes.
  • After the trigger terminal is closed, the relay operates, 15-18 is closed, 15-16 is disconnected.
  • After the trigger terminal is disconnected, it begins to delay.
  • After the delay time, the relay will reset, 15-18 will be disconnected and 15-16 will be closed.

4.3. Setting Delay Time and Function

The relay features three rotary knobs for configuration:

Knob 1 for time range and Knob 2 for time percentage setting

Figure 6: Time Setting Knobs

  • Knob 1 (Top): Time Gear Selection
    Sets the time range: 's' for second, 'm' for minute, 'h' for hour, 'd' for day. 'ON' for relay action (15-18/25-28 closed). 'OFF' for relay open (15-18/25-28 open).
  • Knob 2 (Middle): Time Percentage Setting
    Fine adjustment of delay time, 10% ~ 100% adjustable.
  • Knob 3 (Bottom): 10 Delay Mode Options
    Selects one of the 10 available functions (A-J).

Calculating Delay Time: Delay time = Knob 1 setting x Knob 2 percentage.

  • Example 1: To set for 5 seconds. Set Knob 1 to '10s', Knob 2 to '50%'. Delay time = 10s x 50% = 5s.
  • Example 2: To set for 8 minutes. Set Knob 1 to '10m', Knob 2 to '80%'. Delay time = 10m x 80% = 8m.

5. Operating Instructions

The EAMT1-M1/M2 offers 10 distinct operating modes, selected via Knob 3. Each mode defines how the relay responds to power input (U) and trigger signals (S).

List of 10 adjustable delay functions (A-J)

Figure 7: 10 Adjustable Delay Functions

Functions diagram showing timing charts for modes A through J

Figure 8: Functions Diagram (Timing Charts)

5.1. Function Descriptions

  • A: On Delay (Power On)
    When input voltage U is applied, timing delay 't' begins. The relay contacts R change state after the delay is complete. Contacts R return to their shelf state when input voltage U is removed. The trigger switch is not used in this function.
  • B: Interval (Power On)
    When input voltage U is applied, relay contacts R change state immediately and the timing cycle begins. When the time delay is complete, contacts return to their shelf state. When input voltage U is removed, contacts will also return to their shelf state. The trigger switch is not used in this function.
  • C: Repeat Cycle (Starting Off)
    When input voltage U is applied, time delay 't' begins. When the time delay is complete, relay contacts R change state for time delay 't'. This cycle will repeat until input voltage U is removed. The trigger switch is not used in this function.
  • D: Repeat Cycle (Starting On)
    When input voltage U is applied, relay contacts R change state immediately and time delay 't' begins. When the time delay is complete, contacts return to their shelf state for time delay 't'. This cycle will repeat until input voltage U is removed. The trigger switch is not used in this function.
  • E: Off Delay (S Break)
    Input voltage U must be applied continuously. When trigger switch S is closed, relay contacts R change state. When trigger switch S is opened, delay 't' begins. When delay 't' is complete, contacts R return to their shelf state. If trigger switch S is closed before delay 't' is complete, then time is reset. When trigger switch S is opened, the delay begins again, and relay contacts R remain in their energized state. If input voltage U is removed, relay contacts R return to their shelf state.
  • F: Single Shot
    Upon application of input voltage U, the relay is ready to accept trigger signal S. Upon application of the trigger signal S, the relay contacts R transfer and the preset time 't' begins. During time-out, the trigger signal S is ignored. The relay resets by applying the trigger switch S when the relay is not energized.
  • G: Single Shot Trailing Edge (Non-Retriggerable)
    Upon application of input voltage U, the relay is ready to accept trigger signal S. Upon application of the trigger signal S, the relay contacts R transfer and the preset time 't' begins. At the end of the preset time 't', the relay contacts R return to their normal condition unless the trigger switch S is opened and closed prior to time out 't' (before preset time elapses). Continuous cycling of the trigger switch S at a rate faster than the preset time will cause the relay contacts R to remain closed. If input voltage U is removed, relay contacts R return to their shelf state.
  • H: On/Off Delay
    Input voltage U must be applied continuously. When trigger switch S is closed, time delay 't' begins. When the time delay 't' is complete, relay contacts R change state and remain transferred until trigger switch S is opened. If input voltage U is removed, relay contacts R return to their shelf state.
  • I: Latching Relay
    Input voltage U must be applied continuously. Output changes state with every trigger switch S closure. If input voltage U is removed, relay contacts R return to their shelf state.
  • J: Pulse Generator
    Upon application of input voltage U, a single output pulse of 0.5 seconds is delivered to the relay after time delay 't'. Power must be removed and re-applied to repeat the pulse. The trigger switch is not used in this function.

5.2. Function Demonstration Video

Watch this video for a practical demonstration of the various time delay functions and their wiring configurations.

Video 1: Demonstration of Time Delay Relay Functions (A-J). The video shows device link 15-18 as Normally Open (NO), set time 10S, 50%. Button link is Normally Closed (NC) Latching.

6. Maintenance

The EARUELETRIC time delay relay is designed for long-term, reliable operation with minimal maintenance. However, regular checks can help ensure optimal performance:

  • Cleaning: Keep the device clean and free from dust and debris. Use a dry, soft cloth for cleaning. Do not use liquid cleaners.
  • Connection Checks: Periodically inspect all wiring connections to ensure they remain tight and free from corrosion. Loose connections can lead to intermittent operation or damage.
  • Environmental Conditions: Ensure the operating environment remains within the specified temperature and humidity ranges to prevent premature failure.

7. Troubleshooting

If you encounter issues with your time delay relay, consider the following common troubleshooting steps:

ProblemPossible CauseSolution
Relay not powering on (Green LED off)No power supply or incorrect voltage.Check power connections to A1(+) and A2(-). Verify input voltage is within 12-240V AC/DC.
Relay not switching (Red LED off/incorrect)Incorrect function setting, incorrect time setting, or faulty trigger signal.Verify Knob 3 function setting. Check Knob 1 and Knob 2 time settings. Ensure trigger signal (S) is correctly applied for modes requiring it. Check load connections.
Intermittent operationLoose wiring connections or unstable power supply.Tighten all terminal connections. Ensure power supply is stable.
Relay contacts not returning to shelf stateInput voltage U not removed (for some modes) or trigger signal not reset.Review the specific function diagram (Figure 8) for the selected mode to understand the expected behavior. Ensure input voltage or trigger signal is managed as required.

8. User Tips

  • Model Number: For support or specific inquiries, remember to reference the model number, EAMT1-M1.
  • Understanding Functions: The relay has 10 functions (A-J). Carefully study the 'Functions Diagram' (Figure 8) and the 'Function Demonstration Video' (Video 1) to fully understand how each mode operates and how to apply it to your specific needs.
  • Contact Configuration: The relay typically has one set of changeover contacts (15-16-18). The EAMT1-M2 variant has two sets (15-16-18 and 25-26-28). Ensure your wiring matches the contact configuration of your specific model.

9. Warranty and Support

For warranty information, technical support, or service inquiries, please contact your retailer or the manufacturer directly. Keep your purchase receipt as proof of purchase.