Eastron SDM630Modbus V3

Contents

Eastron SDM630Modbus V3 Multi-function Power Analyser User Manual

Model: SDM630Modbus V3

1. Product Overview

The Eastron SDM630Modbus V3 is an advanced multi-function three-phase energy monitoring solution. It is designed for measuring and displaying various electrical parameters in 1-phase 2-wire, 3-phase 3-wire, and 3-phase 4-wire systems. This device is equipped with optional outputs such as pulses and RS485 RTU Modbus communication, making it suitable for integration into PV solar systems and other energy management applications.

It features configuration and display buttons for easy navigation through parameters and settings. The unit is housed for DIN rail mounting and offers IP51 protection. It supports direct connection up to 100A and allows for selectable measurement modes using free configuration software for kWh display, including Total kWh (Import + Export), Import kWh, and Net kWh (Export - Import).

Front view of the Eastron SDM630Modbus V3 Multi-function Power Analyser

Figure 1: Front view of the SDM630Modbus V3

2. Key Features

  • Max. 100A Direct Load
  • 4 Module (72mm wide) DIN rail mounting
  • Bi-directional Measurement
  • 2 Pulse outputs + RS485 Modbus communication
  • Multi-measurement capabilities: kWh, kvarh, W, Var, VA, PF, Hz, dmd, V, A, etc.
  • Compatible with 3P4W, 3P3W, and 1P2W systems
  • Operating Temperature: -25 to +55 degrees Celsius
  • Rated Voltage: 230V AC
  • Accuracy Class: Cl. 1
  • Measuring Energy Range: 0-999999.99 kWh
  • Display Type: LCD
  • Communication Protocol: Modbus RTU
  • Pulse Output 1: Configurable
  • Pulse Output 2: 400imp/kWh (Passive type)

3. Installation and Setup

3.1 Safety Precautions

  • Installation should only be performed by qualified personnel.
  • Ensure all power is disconnected before installation or maintenance.
  • Follow local electrical codes and regulations.
  • Do not operate the device if it appears damaged.

3.2 Mounting

The SDM630Modbus V3 is designed for DIN rail mounting. Securely attach the device to a standard 35mm DIN rail within an appropriate enclosure, ensuring adequate ventilation.

Side view of the energy meter showing DIN rail mounting clips

Figure 2: Side view illustrating DIN rail mounting

3.3 Wiring Diagram

The meter supports 1-phase 2-wire, 3-phase 3-wire, and 3-phase 4-wire connections. Refer to the diagram below for correct wiring. Ensure all connections are tight and secure.

Wiring diagram for 1P2W, 3P3W, and 3P4W configurations, and physical dimensions of the SDM630Modbus V3

Figure 3: Wiring Diagram and Dimensions. The diagram shows connections for 1-phase 2-wire, 3-phase 3-wire, and 3-phase 4-wire systems. For 3-phase 4-wire, L1, L2, L3, and N are connected to terminals 1, 4, 7, and 10 respectively, with corresponding load connections on terminals 3, 6, 9, and 12. RS485 A and B are connected to terminals 13 and 14. Pulse outputs are on terminals 15 and 16.

Wiring Notes:

  • Power Input: Connect the phase and neutral wires according to the diagram for your specific system (1P2W, 3P3W, or 3P4W). The meter supports direct connection up to 100A.
  • RS485 Communication: Connect the RS485 A and B lines to terminals 13 and 14 respectively for Modbus RTU communication.
  • Pulse Outputs: Pulse output 1 and 2 are available on terminals 15 and 16. These are passive outputs.

4. Operation

The SDM630Modbus V3 features an LCD display and several buttons for navigating and configuring the device.

4.1 Display and Buttons

The LCD displays various electrical parameters. The buttons (U/I, M, P, E) allow users to cycle through measurements, access menus, and confirm selections.

  • U/I Button: Typically used to cycle through voltage (U) and current (I) readings, or other instantaneous parameters.
  • M Button: Likely serves as a 'Mode' or 'Menu' button to access different measurement screens or configuration settings.
  • P Button: May be used for 'Parameter' selection or 'Pulse' related settings.
  • E Button: Generally functions as an 'Enter' or 'Exit' button to confirm selections or leave a menu.

For detailed navigation and configuration, refer to the official datasheet and configuration software manual available on the Eastron website.

4.2 Measurement Modes

The device can measure a wide range of parameters including:

  • Active Energy (kWh) - Total, Import, Export, Net
  • Reactive Energy (kvarh)
  • Active Power (W)
  • Reactive Power (Var)
  • Apparent Power (VA)
  • Power Factor (PF)
  • Frequency (Hz)
  • Voltage (V)
  • Current (A)
  • Demand (dmd)
  • And more.

Specific measurement modes and their display can be configured using the provided software.

5. Maintenance

The SDM630Modbus V3 is designed for reliable operation with minimal maintenance. However, periodic checks are recommended:

  • Cleaning: Keep the device clean and free from dust. Use a soft, dry cloth for cleaning. Do not use abrasive cleaners or solvents.
  • Connections: Periodically inspect all wiring connections to ensure they remain tight and secure. Loose connections can lead to inaccurate readings or device malfunction.
  • Environment: Ensure the operating environment remains within the specified temperature and humidity ranges to prevent damage.

6. Troubleshooting

If you encounter issues with your SDM630Modbus V3, consider the following troubleshooting steps:

  • No Display/Power:
    • Check the main power supply to the meter.
    • Verify all power connections are correctly wired and secure.
  • Inaccurate Readings:
    • Ensure the wiring configuration matches your electrical system (1P2W, 3P3W, 3P4W).
    • Check for loose or incorrect wiring connections.
    • Verify that the meter's settings (e.g., CT ratio if applicable, though this model is direct connect up to 100A) are correctly configured.
  • Communication Issues (RS485 Modbus):
    • Check RS485 A and B connections for correct polarity and secure fit.
    • Verify the Modbus address, baud rate, parity, and stop bits settings on both the meter and the master device.
    • Ensure the communication cable length does not exceed the maximum recommended distance (1000m).

If problems persist, consult the official datasheet or contact Eastron technical support.

7. Specifications

Detailed technical specifications for the SDM630Modbus V3 are provided below.

Table of Product Parameters including Electrical Characteristics, Input & Output, and Ethernet Communication

Figure 4: Detailed Product Parameters

ParameterValue
Brand NameEastron
Model NumberSDM630Modbus V3
Dimensions100*72*66mm
Operating Temperature-25 to +55 degree centigrade
Output Voltage230V
Accuracy ClassCl. 1
Measuring Energy Range0-999999.99kWh
PhaseThree Phase
Max Operating Current100A (Direct Load)
Rated Voltage230V
Power SupplyAC
Display TypeLCD
DIY SuppliesElectrical
Communication typeRS485
Communication protocolModbus RTU
Pulse output 1Configurable
Pulse output 2400imp/kWh
Pulse output typePassive

Electrical Characteristics (from image)

Type of MeasurementAccuracy
Power0.5% of range maximum
Active EnergyIEC 62053-21 Class 1.0
Reactive EnergyIEC62053-23 Class 2
Frequency0.2% of mid-frequency
Current0.5% of range maximum
Voltage0.5% of range maximum
Power Factor1% of unity (0.01)

Input & Output (from image)

ParameterValue
Rated Current (Ib/Iref)10A
Max Current (Imax.)100A
Min Current (Imin.)0.5A
Starting Current40mA
Rated Voltage (Un)230V L-N / 120V L-N
Operational Voltage80%~120% of Un
Output2 Pulse Outputs + RS485 Modbus

Ethernet Communication (from image)

ParameterValue
Bus typeRS485 (semi-duplex)
Communication Address1~247
Transmission Distance1000m Maximum
Transmission Speed2400bps~38400bps
ParityNone (default), Odd, Even
Stop Bits1

8. Warranty and Support

8.1 Warranty Information

The Eastron SDM630Modbus V3 comes with an 18-month warranty from the date of purchase.

8.2 Technical Support and Resources

  • Datasheet: A detailed datasheet for the SDM630Modbus V3 can be downloaded from the official Eastron website: www.eastrongroup.com.
  • Modbus Protocol Instruction / Register Map: For specific Modbus protocol instructions and register maps, please contact Eastron directly.
  • General Inquiries: For any further questions or support, please contact Eastron customer service.
FAQ section with questions about MID vs non-MID, datasheet, warranty, delivery time, and Modbus protocol

Figure 5: Frequently Asked Questions

9. User Tips

  • Inverter Compatibility: The SDM630Modbus V3 has been reported by users to be compatible with Deye Inverters. Always verify specific model compatibility with your inverter manufacturer or Eastron support if unsure.
  • Software Configuration: Utilize the free configuration software provided by Eastron to customize measurement modes and display settings for optimal performance in your specific application.