1. Introduction
The Smartgen HGM1790N is a single unit automation and monitoring control module designed for generator sets. It offers automatic start/stop, data measurement, alarm protection, and remote control functions. This manual provides essential information for the safe and efficient operation of your HGM1790N controller.

2. Setup and Installation
2.1 Mounting
The HGM1790N controller is designed for panel mounting. Ensure adequate space for wiring and ventilation. Refer to the dimensions diagram for precise panel cutout requirements.

2.2 Wiring Connections
All wiring should be performed by qualified personnel, adhering to local electrical codes and safety standards. Ensure the generator set is completely shut down and isolated from power before making any connections.

The following table details the terminal connections:
| Terminal No. | Description |
|---|---|
| 1 | B- (Battery Negative) |
| 2 | B+ (Battery Positive) |
| 3 | Em. Stop Input (Emergency Stop Input) |
| 4 | Fuel Output |
| 5 | Crank Output |
| 6 | Remote Start Input |
| 7 | Aux. Input (Auxiliary Input) |
| 8 | Oil Pressure Input |
| 9 | Engine Temp Input (Engine Temperature Input) |
| 10 | Magnetic Pickup |
| 11 | Gens(L) (Generator Line) |
| 12 | Gens(N) (Generator Neutral) |
| 13 | Load(L*) (Load Line) |
| 14 | Aux. Output 1 (Auxiliary Output 1) |
| 15 | Aux. Output 2 (Auxiliary Output 2) |
| 16 | Aux. Output 3 (Auxiliary Output 3) |
| 17 | Aux. Output 4 (Auxiliary Output 4) |
2.3 USB Connection
The controller features a USB port for connection to a computer, allowing for configuration and monitoring via dedicated software (not included).
3. Operation
3.1 Control Panel Overview
The front panel of the HGM1790N controller provides essential controls and a digital display for monitoring generator parameters.
- Display: Shows voltage, frequency, and other operational data.
- Stop Button (Red 'O'): Manually stops the generator.
- Auto Button (White 'Auto' with swirl icon): Activates automatic operation mode. The generator will start/stop based on configured conditions (e.g., remote start signal).
- Start Button (Green 'I'): Manually starts the generator.
- Alarm Indicator (L1): Illuminates to indicate an active alarm condition.
3.2 Starting the Generator
- Manual Start: Press the green 'Start' button. The controller will initiate the starting sequence.
- Automatic Start: Press the white 'Auto' button. The controller will wait for a remote start signal or other configured conditions to automatically start the generator.
3.3 Stopping the Generator
- Manual Stop: Press the red 'Stop' button. The controller will initiate the stopping sequence.
- Automatic Stop: In 'Auto' mode, the generator will stop automatically when the configured conditions for stopping are met (e.g., remote start signal removed).
3.4 Monitoring
The digital display continuously shows key operational parameters such as voltage (V) and frequency (Hz). Use the navigation buttons (up/down arrows) to cycle through additional monitored values if available.
4. Maintenance
The HGM1790N controller is designed for minimal maintenance. However, regular checks can ensure its longevity and reliable operation.
- Cleaning: Keep the controller's front panel clean and free of dust. Use a soft, dry cloth. Do not use abrasive cleaners or solvents.
- Connections: Periodically check all wiring connections for tightness and signs of corrosion. Ensure all terminals are securely fastened.
- Environment: Ensure the operating environment is within the specified temperature and humidity ranges to prevent damage to the electronic components.
- Software Updates: If available, periodically check the manufacturer's website for firmware updates that may improve performance or add features.
5. Troubleshooting
This section provides guidance for common issues. For complex problems, contact qualified service personnel.
- Controller Not Powering On:
- Check battery connections (B+ and B-).
- Verify battery voltage is within the controller's operating range.
- Inspect fuses in the power supply circuit.
- Generator Fails to Start:
- Ensure the 'Stop' button is not active.
- Check for active alarm conditions indicated by the 'Alarm L1' light. Address any alarms.
- Verify fuel supply and engine crank system.
- In 'Auto' mode, confirm the remote start signal is present.
- Generator Stops Unexpectedly:
- Check for any active alarm conditions (e.g., low oil pressure, high engine temperature, overspeed).
- Ensure the emergency stop input is not triggered.
- Incorrect Readings on Display:
- Verify sensor connections (Oil Pressure, Engine Temp, Magnetic Pickup).
- Ensure generator voltage and frequency inputs (Gens L, Gens N) are correctly wired.
6. Specifications
| Feature | Detail |
|---|---|
| Model Number | HGM1790N |
| Brand Name | Smartgen (YING LI TE) |
| Origin | Mainland China |
| Electrified | Yes |
| High-concerned chemical | None |
| Product Depth | 47 mm (excluding bezel) |
| Bezel Thickness | 7 mm |
| Package Length | 20 cm |
| Package Width | 15 cm |
| Package Height | 7 cm |
| Package Weight | 0.45 kg |
7. User Tips
- Computer Connection: The HGM1790N controller can be connected to a computer via its USB port for advanced configuration and monitoring. Ensure you have the correct software and drivers installed for seamless communication.
- Regular Testing: Periodically test the automatic start/stop functions of your generator set to ensure the controller is operating correctly and all safety features are active.
8. Warranty and Support
For warranty information, technical support, or service inquiries, please refer to the documentation provided with your purchase or contact the manufacturer directly. Keep your purchase receipt as proof of purchase.