Schneider Electric LC1D

Contents

Schneider Electric LC1D Series DC Contactor User Manual

Models: LC1D09, LC1D12, LC1D18, LC1D25, LC1D32, LC1D38

1. Product Information

1.1 General Description

This series of electrical products are primarily used in AC 50/60 Hz circuits, with a rated insulation voltage up to 690V. They are designed for remote switching, circuit control, motor starting, protection, and automatic control applications. These contactors are widely utilized in power distribution cabinets, automation equipment, machinery, machine tools, building electrical systems, and industrial control systems, offering stable performance and reliable operation.

1.2 Compliance Standards

  • GB 14048.1
  • GB 14048.4
  • IEC 60947-4-1
  • GB 21518
  • GB/T 14048 series
  • CE Certified

2. Specifications

Technical Parameters
ParameterValue
Rated Operational VoltageAC 24V ~ 415V
Rated Insulation Voltage690V
Rated Impulse Withstand Voltage6kV ~ 8kV
Degree of ProtectionIP20 or higher
Mechanical EnduranceUp to 8,000,000 operations
Electrical EnduranceUp to 1,200,000 operations
Mounting TypeDIN rail mounting / Screw fixing
Connection TypeScrew clamp terminals
Phase3
Number of Pole3
Electricity TypeDC
Current TypeDC
High-concerned chemicalAcetochlor (Warning: This product contains Acetochlor, a chemical known to the State of California to cause cancer. For more information go to www.P65Warnings.ca.gov)

2.1 Product Features

  • Imported Flame Retardant Shell: The shell is made of high flame retardant material, offering strong and wear-resistant properties, high temperature resistance, and corrosion resistance for enhanced safety.
  • High Purity Copper Coil: Features fine and numerous coil copper wire, capable of withstanding high voltage, ensuring high purity, high quality, and greatly increased service life.
  • Silver Alloy Contact: Designed to carry larger current, providing stronger electrical conductivity and sensitive contact.
  • High Quality Iron Core: Contains 32 pieces of high quality iron core, complying with national standards for smoother suction.

3. Setup and Installation

3.1 Installation Conditions

  • Ambient Temperature: -5°C to +40°C
  • Altitude: ≤ 2000m
  • Environment: Must be free from explosive hazards, corrosive gas, conductive dust, and be well-ventilated.
  • Stability: Installation shall be firm, stable, and free from vibration.

3.2 Terminal Identification

  • Main Circuit: L1, L2, L3 (line side); T1, T2, T3 (load side)
  • Control Coil: A1, A2
  • Auxiliary Contacts: NO (normally open), NC (normally closed)

3.3 Wiring Instructions

WARNING: All wiring work must be performed with ALL POWER DISCONNECTED.

Contactor wiring diagram
Contactor wiring diagram showing power supply, fuse/circuit breaker, start/stop buttons, contactor, and load connections.
Detailed view of contactor terminals
Detailed view of contactor terminals, showing control voltage input, NC/NO auxiliary contacts, main contacts input, and screw mounting hole.
  • Ensure the rated voltage of the product matches the actual control voltage of your system.
  • All wiring terminals must be securely fastened to prevent loose connections.
  • Wrong connections, short circuits, or loose connections are strictly prohibited and can lead to damage or hazards.
Product features diagram
Diagram highlighting main contact inlet/outlet holes, A1/A2 coils, and opening/closing auxiliary contact.
Product features diagram alternative view
Alternative view of product features diagram.

4. Operation

  • Operate the contactor within its rated voltage, current, and specified utilization category.
  • Long-term overload operation is strictly forbidden as it can lead to equipment failure or fire.
  • Always use the contactor with supporting protective devices such as circuit breakers and relays to ensure safe operation.
  • Monitor the contactor during operation; there should be no abnormal noise, odor, or excessive heating.

5. Maintenance

WARNING: Regular inspection and maintenance must be carried out under power-off conditions.

  • Perform regular inspections to check for any signs of wear or damage.
  • Replace damaged or worn parts in a timely manner with genuine replacement components.
  • Live maintenance, disassembly, or modification of the contactor is strictly prohibited.

6. Troubleshooting

  • No Operation: Check if the power supply is connected and matches the rated voltage. Verify all wiring connections are secure and correct.
  • Abnormal Noise, Odor, or Heating: Immediately stop operation if any of these symptoms occur. Disconnect power and inspect the unit for faults, loose connections, or signs of overload.
  • Equipment Failure: Ensure the contactor is not operating under long-term overload conditions. Check for proper functioning of supporting protective devices like circuit breakers and relays.
  • Interlocking Issues: If using multiple contactors with interlocking, ensure the interlocking mechanism is correctly installed and functioning as intended.

7. Safety Warnings

7.1 General Safety Requirements

  • This product shall be installed, operated, and maintained only by qualified electricians.
  • Always disconnect all power sources and verify voltage absence using appropriate testing equipment before performing any operation, installation, or maintenance.
  • Improper installation, wiring, or use may cause electric shock, fire, equipment damage, or personal injury.
  • Installation, commissioning, and maintenance must be performed by qualified electrical personnel.

7.2 Warning Statements

DANGER: High voltage may cause fatal electric shock. Disconnect, test, and ground before working!

WARNING: Live working may lead to electric shock, burns, or death!

WARNING: Overload operation may cause fire or equipment failure!

WARNING: Wrong wiring may cause short circuit, electric shock, or damage!

CAUTION: Stop operation immediately if abnormal noise, odor, or heating occurs!

7.3 Safety Symbols

  • ⚡ Warning: Risk of electric shock
  • 🔥 Warning: Risk of fire
  • ⛔ Do not work live
  • 🦺 Wear insulating protection
  • ⚡ Disconnect and test voltage before operation
  • ⛔ Do not disassemble or modify without approval

8. User Tips

  • Verify Coil Voltage: Before installation, always double-check the coil voltage of your specific contactor model (e.g., 24V DC, 110V DC, 220V DC) to ensure it matches your control circuit.
  • Interlocking Capability: These contactors can be interlocked with each other for specific control applications. Consult a qualified electrician for proper interlocking configurations.
  • CE Certification: The product is CE certified, indicating compliance with European safety, health, and environmental protection requirements.

9. Additional Resources & Support

For further detailed information, technical drawings, or specific application guidance, please refer to the official Schneider Electric documentation. A user manual in PDF format is available for download:

View User Manual (PDF)

For product support or warranty inquiries, please contact your seller or an authorized Schneider Electric service center.

Documents and downloads

Ask a question about this manual

Ask about setup, troubleshooting, compatibility, parts, safety, or missing instructions. Manuals+ will review the question and use this page’s manual context to help answer it.

After a successful submission, we securely hash the supplied account or form email before sending it to Microsoft Advertising for conversion attribution. Privacy details.