1. Introduction and Overview
The TONGOU TOQCB2L-80 is a smart RCBO (Residual Current Breaker with Overcurrent protection) designed for modern electrical systems. It integrates WiFi connectivity, allowing for remote control, real-time metering, and smart automation through the Tuya Smart Life application. This device offers comprehensive protection against various electrical faults, enhancing safety and convenience in your home or business.

This smart circuit breaker is designed to prevent hidden dangers from short circuits, over power, over voltage, under voltage, high temperature, and electric shock, making your electrical environment safer and smarter.
2. Safety Information
- Professional Installation Recommended: Installation should be performed by a qualified electrician to ensure safety and compliance with local electrical codes.
- Correct Wiring: Power must enter from the top of the device and must be a Live line + Neutral Line (L+N) connection. Live line + Live line (L+L) configurations cannot be used.
- Power-Off State: After the power is disconnected and reconnected, this product will be in the off state for safety reasons.
- Voltage Compatibility: The TOQCB2L is an RCBO and is not suitable for 110V applications. The over-undervoltage protection function is not available for 110V systems. The rated operating voltage range is 145V-295V.
- Safety Lock: When the safety lock is pulled up, the device enters a maintenance state. In this state, both remote and manual switches are locked to prevent accidental operation and the risk of electric shock during maintenance.


3. Product Features
- Comprehensive Protection: Includes Over-Voltage, Under-Voltage, Over-Current, Terminal Temperature, High Power, Short-Circuit, and Leakage Protection.
- Smart Connectivity: Built-in TUYA chip ensures stable WiFi signal transmission and reception, avoiding congestion interference.
- Remote Control: Control the circuit breaker remotely via the mobile app.
- Voice Control: Compatible with Amazon Alexa and Google Assistant for convenient voice commands.
- Real-time Monitoring: Monitor power, voltage, current, temperature, and other grid parameters in real-time.
- Electricity Metering: Records electricity consumption by day, month, and year.
- Cloud Timing: Precise time control equipment for scheduling operations.
- Automatic Reclosing: Automatically recloses when the circuit voltage returns to normal after a voltage-related trip.
- Operation Log: Keeps a record of all operations and events.
- Visible Window: Multi-functional window panel for clear, at-a-glance monitoring and to prevent misoperation.
- Positioning Clip: Designed for easy disassembly and simple installation.
- Certifications: Professional CE-EMC and CE-LVD tests ensure safe and reliable communication.


4. Specifications
| Parameter | Value |
|---|---|
| Brand Name | TONGOU |
| Model Number | TOQCB2L-80 |
| Type | Earth Leakage Circuit Breaker (RCBO) |
| Is Smart Device | Yes |
| Origin | Mainland China |
| Certification | CE |
| Warranty | One year |
| Protocol | WIFI (Default) |
| Number of Poles | 2P, 3P, 4P |
| Rated Operating Voltage Range | 145V-295V (50/60Hz) |
| Maximum Frame Current | 63A |
| Service Temperature | -25°C ~ +100°C |
| Short Circuit Breaking Capacity | Icn=Ics=10KA |
| Mechanical Life | > 10000 times |
| Electrical Life | > 6000 times |
| Trip Type | Type C |
| Electricity Metering Accuracy | 1.0 class |
| Control Type | Manual, Remote Control, Automatic |
| Customization Options | Lora, SigMesh, RS 485, ZigBee, RJ45 |
| Package Dimensions (L x W x H) | 13 cm x 5 cm x 5 cm |
| Package Weight | 0.4 kg |

5. Installation and Setup
5.1 Wiring Instructions
Ensure all power is disconnected before attempting any wiring. Follow the wiring diagrams carefully for your specific pole configuration (2P, 3P, or 4P).

- 2P Wiring: Connect the Live wire to the 'L' pole and the Neutral wire to the 'N' pole from the upper input terminals. Ensure correct polarity.
- 3P Wiring: Connect Phase A, Phase B, and Phase C to the respective 'L' poles and the Neutral wire to the 'N' pole from the upper input terminals.
- 4P Wiring: Connect Phase A, Phase B, and Phase C to the respective 'L' poles and the Neutral wire to the 'N' pole from the upper input terminals.



5.2 Network Pairing
To enable smart features, the device needs to be paired with the Tuya Smart Life app.
- Connect Wiring: Ensure the Live wire is connected to the L pole and the Neutral wire to the N pole from the upper input terminals of the smart circuit breaker. Verify the wiring is correct and you have a strong Wi-Fi signal in the installation area.
- Activate Pairing Mode: Turn on Bluetooth and Wi-Fi on your mobile phone. Open the Tuya Smart Life app. Long press the 'CFQ/QUERY' button on the circuit breaker for about 5-10 seconds. The LED indicator will flash blue light slowly, indicating it's in pairing mode.
- Discover Device: In the app, wait for the device to be discovered automatically, or click the '+' icon in the upper right corner, then choose 'Add Device' to search for devices. Once found, click 'Add'.
- Connect to Network: Enter your Wi-Fi network password and click 'Next step'. Wait for the device to connect to the network.
- Connection Confirmation: Once the device is successfully connected to the network, the LED indicator will change from a red slow flashing light to a red steady light.



6. Operation
6.1 Manual Operation
The circuit breaker can be manually switched ON/OFF using the operating handle on the front panel.
6.2 Remote Control via Mobile App
After successful network pairing, you can control and monitor the device using the Tuya Smart Life app (or compatible apps like Smart Life, @Smart).

6.3 Real-time Electricity Statistics
The app provides real-time data on your electricity usage.
- View current, voltage, power, and temperature.
- Record electricity consumption by year, month, day, and hour.
- Access operation logs for historical data.

6.4 APP Function Panel (Threshold Setting)
You can customize protection thresholds via the app:
| Protection Type | Adjustable Range | Function Status |
|---|---|---|
| Over-Voltage Value | 245V - 295V | Closed / Alarm / Open |
| Under-Voltage Value | 145V - 220V | Closed / Alarm / Open |
| Rated Current Value | 1A - 63A | Closed / Alarm / Open |
| Terminal Temp Value | -25°C - 100°C | Closed / Alarm / Open |
| Over-Power | 5W - 25005W | Closed / Alarm / Open |
| Electrical Leakage | 30mA - 500mA | Closed / Alarm / Open |


6.5 Voice Control
Integrate your RCBO with smart home assistants for hands-free control.
- Compatible with Amazon Alexa.
- Compatible with Google Assistant.

6.6 Cloud Timing and Smart Scenarios
Utilize the app for advanced automation.
- Cloud Timing: Set precise schedules for the circuit breaker to turn on or off.
- Smart Scenarios: Create custom automation rules based on various conditions, integrating with other smart devices. Examples include:
- Outdoor advertising control
- Intelligent breeding farm management
- Garden smart irrigation systems
- New energy smart power consumption optimization


7. Automatic Reclosing Function
The automatic reclosing feature is designed to restore power automatically under specific conditions:
- When the circuit breaker trips due to voltage protection (over-voltage or under-voltage), it will automatically reclose once the circuit voltage returns to its normal operating range.
- Important Note: For safety reasons, this function only applies to trips caused by voltage fluctuations. For other types of trips (e.g., overcurrent, short circuit, leakage), manual intervention is required to ensure the underlying issue is resolved before re-energizing the circuit.
8. Maintenance
- Regular Inspection: Periodically check the circuit breaker for any visible damage, loose connections, or signs of overheating.
- Cleaning: Keep the device clean and free from dust and debris. Use a dry, soft cloth for cleaning. Do not use liquids or abrasive cleaners.
- Firmware Updates: Ensure the device firmware is up-to-date through the Tuya Smart Life app for optimal performance and security.
- Safety Lock Usage: Always use the safety lock feature when performing any maintenance or inspection on the electrical circuit to prevent accidental re-energization.
9. Troubleshooting
Common Issues and Solutions:
- Q: Does it function as a differential (RCD) or a switch (MCB)?
A: The TONGOU TOQCB2L-80 is an RCBO (Residual Current Breaker with Overcurrent protection), meaning it combines the functions of both a Residual Current Device (RCD/differential) for earth leakage protection and a Miniature Circuit Breaker (MCB/switch) for overcurrent and short-circuit protection. - Q: How do I set it to automatic restart after it has tripped?
A: The automatic reclosing function is specifically designed for trips caused by voltage protection (over-voltage or under-voltage). It will automatically reclose when the voltage returns to normal. For other trip types (e.g., overcurrent, leakage), manual reset is required after addressing the underlying issue. - Q: Can I use this with a 110V + 110V electrical service (two phases of 110V)?
A: No, the TOQCB2L is not suitable for 110V applications. Its rated operating voltage range is 145V-295V. The over-undervoltage protection function will not be available or function correctly on a 110V system. - Q: Is this device only compatible with 50Hz electrical systems?
A: No, the device supports both 50Hz and 60Hz electrical systems, as indicated by the '50/60Hz' marking on the product. - Q: The app shows an 'Abnormal operation' reminder. What does this mean?
A: The 'Abnormal operation' reminder indicates a circuit failure or an unexpected event detected by the device. Check the operation log in the app for details and inspect your electrical system for any faults.

10. User Tips
- Verify Voltage: Always confirm your electrical system's voltage is within the 145V-295V range for optimal performance and protection features. This device is not recommended for 110V circuits.
- Correct Wiring is Crucial: Double-check that power input is L+N (Live + Neutral) and not L+L (Live + Live) to ensure proper functioning and safety.
- Utilize the App: Take full advantage of the Tuya Smart Life app for remote control, real-time monitoring of electricity usage, and setting custom protection thresholds.
- Understand Auto-Reclosing: Remember that automatic reclosing only occurs for voltage-related trips. For other faults, manually inspect and reset the breaker after resolving the issue.
- Explore Smart Scenarios: Use the app's automation features to create smart routines for your devices, enhancing convenience and energy efficiency.
11. Warranty and Support
This TONGOU TOQCB2L-80 Circuit Breaker comes with a one-year warranty from the date of purchase, covering manufacturing defects. For technical support, troubleshooting assistance, or warranty claims, please contact your retailer or the manufacturer's customer service.
The product complies with CE certification standards, ensuring it meets European safety, health, and environmental protection requirements.