1. Introduction
This manual describes the assembly, installation, operation, and troubleshooting of your SUMRY HGX Series Hybrid Solar Inverter. Please read this manual carefully before installation and operation, and keep it for future reference.
The SUMRY HGX Series Hybrid Solar Inverter is a multi-function inverter/charger, combining the functions of an inverter, MPPT solar charger, and battery charger to provide uninterruptible power support in a portable size. Its comprehensive large LCD display offers user-configurable and easy-to-access touch button operation for settings such as battery charging current, AC/solar charger priority, and acceptable input voltage based on different applications.
Key Features:
- Off-grid solar inverter functionality.
- No battery function available (for specific configurations).
- Adjustable AC voltage (100VAC, 110VAC, 120VAC) in Under Battery Mode.
- Utility power, battery, and PV power complement each other.
- Pure sine wave solar inverter output.
- Unique glass top cover design with 6.25-inch LCD display and touchable buttons.
- Built-in 140A MPPT (Max PV 5600W) solar charger.
- High PV input range from 55V-350Vdc.
- Smart battery charger design for optimized battery performance.
- Configurable AC/Battery input priority via LCD setting.
- Auto restart while PV is recovering.
- Overload, over-temperature, and output short circuit protection.
- Cold restart function.
- Built-in lithium battery automatic activation.
- Communication with RS232/RS485.
- WiFi monitoring function (optional).
- Anti-dust kit for harsh environments (optional).
- Restore default settings with one click.
Basic System Architecture:
The inverter/charger can power various home and office appliances, including motor-type appliances like tube lights, fans, refrigerators, and air conditioners. A typical system includes solar modules (optional), a generator or utility grid, battery packs, and home appliances.
2. Safety Instructions
WARNING: This chapter contains important safety and operating instructions. Read and keep this manual for future reference.
- Before using the unit, read all instructions and cautionary markings on the unit, the batteries, and all appropriate sections of this manual.
- CAUTION: To reduce the risk of injury, charge only deep-cycle lead-acid type rechargeable batteries. Other types of batteries may burst, causing personal injury and damage.
- Do not disassemble the unit. Take it to a qualified service center when service or repair is required. Incorrect re-assembly may result in a risk of electric shock or fire.
- To reduce the risk of electric shock, disconnect all wirings before attempting any maintenance or cleaning. Turning off the unit will not reduce this risk.
- CAUTION: Only qualified personnel can install this device with a battery.
- NEVER charge a frozen battery.
- For optimum operation of this inverter/charger, please follow the required specifications to select appropriate cable size. It's very important to correctly operate this inverter/charger.
- Be very cautious when working with metal tools on or around batteries. A potential risk exists to drop a tool to spark or short circuit batteries or other electrical parts and could cause an explosion.
- Please strictly follow the installation procedure when you want to disconnect AC or DC terminals. Please refer to the INSTALLATION section of this manual for details.
- GROUNDING INSTRUCTIONS: This inverter/charger should be connected to a permanent grounded wiring system. Be sure to comply with local requirements and regulations to install this inverter.
- NEVER cause AC output and DC input short-circuited. Do NOT connect to the mains when DC input short circuits.
- Warning!! Only qualified service persons are able to service this device. If errors still persist after following the troubleshooting table, please send this inverter/charger back to the local dealer or service center for maintenance.
3. Setup
3.1 Unpacking and Inspection
Before installation, please inspect the unit. Be sure that nothing inside the package is damaged. You should have received the following items:
- The inverter unit x 1
- User manual x 1
3.2 Preparation
Before connecting any wiring, remove the bottom cover by unscrewing the two screws as shown in the diagram below.
3.3 Mounting the Unit
Consider the following points when selecting an installation location:
- Do not mount the inverter on flammable construction materials.
- Mount on a solid surface.
- Install this inverter at eye level to allow the LCD display to be read easily.
- The ambient temperature should be between 0°C and 55°C for optimal operation.
- The recommended installation position is vertically on a wall.
- Ensure sufficient heat dissipation and space for wiring by maintaining clearances as shown in the diagram.
CAUTION: Suitable for mounting on concrete or other non-combustible surfaces only.
Install the unit by screwing two screws into the wall.
3.4 Battery Connection
CAUTION: For safety and regulatory compliance, install a separate DC over-current protector or disconnect device between the battery and inverter. It is still recommended to have over-current protection installed even if a disconnect device is not required in some applications.
WARNING: All wiring must be performed by qualified personnel. Use appropriate cable for battery connection to reduce risk of injury. Use the proper recommended cable and terminal size.
Follow these steps for battery connection:
- Assemble battery ring terminals based on recommended battery cable and terminal size.
- Connect all battery packs as required.
- Insert the ring terminal of the battery cable flatly into the battery connector of the inverter and ensure the bolts are tightened with a torque of 2-3 Nm. Ensure correct polarity (+ to + and - to -) at both the battery and the inverter/charger, and that ring terminals are tightly screwed to the battery terminals.
NOTE: Only use sealed lead-acid, sealed GEL/AGM lead-acid, or lithium batteries.
WARNING: Shock Hazard! Installation must be performed with care due to high battery voltage in series.
CAUTION: Do not place anything between the flat part of the inverter terminal and the ring terminal, as overheating may occur. Do not apply anti-oxidant substance on the terminals before they are connected tightly. Before making the final DC connection or closing the DC breaker/disconnector, ensure positive (+) is connected to positive (+) and negative (-) to negative (-).
Recommended Battery Cable and Terminal Size:
| Model | Typical Amperage | Battery Capacity | Wire Size | Cable (mm²) | Torque Value (Nm) |
|---|---|---|---|---|---|
| 3.0KW 24V | 110A | 100AH / 200AH | 1*4AWG | 22 | 2~3 |
| 4.0KW 24V | 150A | 200AH | 1*2AWG | 35 | 2~3 |
3.5 AC Input/Output Connection
CAUTION: Before connecting to an AC input power source, install a separate AC breaker between the inverter and the AC input power source. This ensures the inverter can be securely disconnected during maintenance and fully protected from overcurrent. Recommended AC breaker specs: 32A for 3.0KW, 40A for 4.0KW.
CAUTION: There are two terminal blocks labeled "INPUT" and "OUTPUT". Do NOT mis-connect input and output connectors.
WARNING: All wiring must be performed by qualified personnel. Use appropriate cable for AC input connection to reduce risk of injury. Use the proper recommended cable size.
Follow these steps for AC input/output connection:
- Before making AC input/output connections, ensure the DC protector or disconnector is open.
- Remove 10mm of insulation from the six conductors. Shorten phase L and neutral conductor N by 3mm.
- Insert AC input wires according to the polarities indicated on the terminal block and tighten the terminal screws.
- Insert AC output wires according to the polarities indicated on the terminal block and tighten the terminal screws. Be sure to connect the PE protective conductor (Ground) first.
- Ensure all wires are securely connected.
CAUTION: Important! Be sure to connect AC wires with correct polarity. If L and N wires are connected reversely, it may cause utility short-circuited when these inverters are operated in parallel. Appliances like air conditioners require 2-3 minutes to restart. If a power shortage occurs and recovers quickly, it can damage connected appliances. Check the air conditioner manufacturer for time-delay function before installation. Otherwise, the inverter/charger may trigger overload fault to protect the appliance, but internal damage to the air conditioner may still occur.
Suggested Cable Requirement for AC Wires:
| Model | Gauge | Torque Value (Nm) |
|---|---|---|
| 3.0KW | 10 AWG | 1.2~1.6 |
| 4.0KW | 8 AWG | 1.4~1.6 |
3.6 PV Connection
CAUTION: Before connecting to PV modules, install a separate DC circuit breaker between the inverter and PV modules.
WARNING: All wiring must be performed by qualified personnel. Use appropriate cable for PV module connection to reduce risk of injury. Use the proper recommended cable size.
Follow these steps for PV module connection:
- Remove 10mm of insulation from positive and negative conductors.
- Check correct polarity of connection cable from PV modules and PV input connectors. Connect positive (+) to positive (+) and negative (-) to negative (-).
- Ensure all wires are securely connected.
PV Module Selection:
When selecting PV modules, consider the following parameters:
- Open circuit Voltage (Voc) of PV modules should not exceed the max. PV array open circuit voltage of the inverter.
- Open circuit Voltage (Voc) of PV modules should be higher than the min. PV Array MPPT Voltage range.
| INVERTER MODEL | 3.0KW | 4.0KW |
|---|---|---|
| Max. PV Array Open Circuit Voltage | 350Vdc | |
| PV Array MPPT Voltage Range | 55Vdc~350Vdc | |
Recommended PV Cable Size:
| Model | Wire Size | Cable (mm²) | Torque Value (max) |
|---|---|---|---|
| 3.0KW/4.0KW | 1 x 12AWG | 4 | 1.2 Nm |
3.7 Final Assembly
After connecting all wirings, replace the bottom cover by screwing the two screws back in.
4. Operating Instructions
4.1 Power ON/OFF
Once the unit is properly installed and the batteries are connected, simply press the On/Off switch (located on the bottom of the case) to turn on the unit.
4.2 Operation and Display Panel
The operation and display panel is located on the front of the inverter. It includes three indicators, four function keys, and an LCD display, providing operating status and input/output power information.
LED Indicators and Messages:
| LED Indicator | Color | State | Messages |
|---|---|---|---|
| AC/INV | Green | Solid On | Output is powered by utility in Line mode. |
| Flashing | Output is powered by battery or PV in battery mode. | ||
| CHG | Green | Solid On | Battery is fully charged. |
| Flashing | Battery is charging. | ||
| FAULT | Red | Solid On | Fault occurs in the inverter. |
| Flashing | Warning condition occurs in the inverter. |
Function Keys:
| Function Key | Description |
|---|---|
| ESC | To exit setting mode |
| UP | To go to previous selection |
| DOWN | To go to next selection |
| ENTER | To confirm the selection in setting mode or enter setting mode |
4.3 LCD Display Icons
The LCD displays various information including input source, configuration, fault information, output, and battery status. Refer to the manual for a detailed breakdown of each icon.
Load Information:
The right-side flashing bar and load icon indicate the load level by 0-24%, 25-50%, 50-75%, and 75-100%.
Mode Operation Information:
- Indicates unit connects to the mains.
- Indicates unit connects to the PV panel.
- Indicates load is supplied by utility power (BYPASS).
- Indicates the utility charger circuit is working.
- Indicates the DC/AC inverter circuit is working.
Mute Operation:
- Indicates unit alarm is disabled.
4.4 LCD Settings
To enter setting mode, press and hold the ENTER button for 3 seconds. Use the UP or DOWN buttons to select programs, and ENTER to confirm or ESC to exit. Key settings include:
- Program 00: Exit setting mode.
- Program 01: Output source priority: Configures load power source priority (Solar first, SBU mode, or Utility first).
- Program 02: Maximum charging current: Configures total charging current for solar and utility chargers.
- Program 03: AC input voltage range: Selects acceptable AC input voltage range (Appliances or UPS).
- Program 04: Power saving mode enable/disable: Enables or disables power saving mode.
- Program 05: Battery type: Selects battery type (AGM, Flooded, Lithium battery, User-Defined, or Lithium battery with communication).
- Program 06: Auto restart when overload occurs: Enables or disables auto restart after overload.
- Program 07: Auto restart when over temperature occurs: Enables or disables auto restart after over temperature.
- Program 08: Output voltage: Sets output voltage (100V, 110V, 120V).
- Program 09: Output frequency: Sets output frequency (50Hz, 60Hz).
- Program 11: Maximum utility charging current: Sets the maximum charging current from utility.
- Program 12: Setting voltage point back to utility source when selecting "SBU priority": Configures the voltage point for switching to utility in SBU mode.
- Program 13: Setting voltage point back to battery mode when selecting "SBU priority": Configures the voltage point for switching to battery in SBU mode.
- Program 16: Charger source priority: Configures charger source priority (Solar first, Solar and Utility, or Only Solar).
- Program 18: Alarm control: Enables or disables alarms.
- Program 19: Auto return to default display screen: Configures whether the display returns to default after inactivity.
- Program 20: Backlight control: Turns backlight on or off.
- Program 22: Beeps while primary source is interrupted: Enables or disables beeping on primary source interruption.
- Program 25: Record Fault code: Enables or disables fault code recording.
- Program 26: Bulk charging voltage (C.V voltage): Sets the bulk charging voltage.
- Program 27: Floating charging voltage: Sets the floating charging voltage.
- Program 29: Low DC cut-off voltage: Sets the low DC cut-off voltage.
- Program 30: Restore default settings: Restores all settings to default.
- Program 33: Battery equalization: Enables or disables battery equalization.
- Program 34: Battery equalization voltage: Sets the battery equalization voltage.
- Program 35: Battery equalized time: Sets the duration for battery equalization.
- Program 36: Battery equalized timeout: Sets the timeout for battery equalization.
- Program 37: Equalization interval: Sets the interval between battery equalization cycles.
- Program 39: Equalization activated immediately: Activates battery equalization immediately.
4.5 Lithium Battery Connection and Settings
If the inverter is matched with lithium batteries, only those with a compatible BMS communication protocol are allowed. You must set the battery type to "Lib-485" in Program 5.
Connecting RJ45 to BMS Communication Port: Ensure the BMS port of the lithium battery corresponds to the pin of the inverter's BMS communication port. The inverter BMS interface pin definition is provided in the manual.
Note: When the battery type is set to "Lib-485", the charge current cannot be modified by the user. If communication fails, the inverter will cut off output. If the communication protocol does not match, you can select "LIB" mode.
4.6 Operating Mode Description
The inverter operates in various modes, including Standby, Power Saving, and Line Mode, with different charging and power supply behaviors depending on the selected priority and available power sources.
Battery Equalization Description:
Battery equalization reverses negative chemical effects like stratification and removes sulfate crystals, improving battery capacity and lifespan. It can be applied by setting an equalization interval (Program 37) or activating immediately (Program 39), provided the function is enabled in Program 33.
5. Maintenance
To ensure the longevity and safe operation of your inverter, regular maintenance is recommended. Always disconnect all wirings before attempting any maintenance or cleaning to prevent electric shock. The unit should be cleaned periodically to prevent dust buildup, especially around cooling vents, which can affect performance and lead to overheating.
Periodically check all cable connections for tightness and signs of wear or corrosion. Ensure that the ambient temperature around the inverter remains within the specified operating range (0°C to 55°C) to prevent overheating.
6. Troubleshooting
This section provides solutions for common issues. If an error persists after following these steps, contact a qualified service center.
Fault Reference Code:
| Fault Code | Fault Event |
|---|---|
| 01 | Fan is locked when inverter is off. |
| 02 | Over temperature |
| 03 | Battery voltage is too high |
| 04 | Battery voltage is too low |
| 05 | Output short circuited or over temperature is detected by internal converter components. |
| 06 | Output voltage is too high. |
| 07 | Overload time out |
| 08 | Bus voltage is too high |
| 09 | Bus soft start failed |
| 11 | Main relay failed |
| 51 | Over current or surge |
| 52 | Bus voltage is too low |
| 53 | Inverter soft start failed |
| 55 | Over DC voltage in AC output |
| 56 | Battery connection is open |
| 57 | Current sensor failed |
| 58 | Output voltage is too low |
Warning Indicator:
| Warning Code | Warning Event | Audible Alarm |
|---|---|---|
| 01 | Fan is locked when inverter is on. | Beep twice every second |
| 03 | Battery is over-charged | Beep twice every second |
| 04 | Low battery | Beep twice every second |
| 07 | Overload | Beep twice every second |
| 10 | Output power derating | Beep twice every second |
| 12 | Solar charger stops due to low battery. | |
| 13 | Solar charger stops due to high PV voltage. | |
| 14 | Solar charger stops due to overload. | |
| 15 | PV is weak | |
| 61 | When the battery communication is abnormal, stop charging and discharging. |
Troubleshooting Table:
| Problem | Explanation / Possible Cause | What to do |
|---|---|---|
| Unit shuts down automatically during startup process. | The battery voltage is too low (<1.91V/Cell) | 1. Re-charge battery. 2. Replace battery. |
| No response after power on. | 1. The battery voltage is far too low. (<1.4V/Cell) 2. Battery polarity is connected reversed. |
1. Check if batteries and the wiring are connected well. 2. Re-charge battery. 3. Replace battery. |
| Input protector is tripped | Check if AC breaker is tripped and AC wiring is connected well. | |
| Mains exist but the unit works in battery mode. | Insufficient quality of AC power. (Shore or Generator) | 1. Check if AC wires are too thin and/or too long. 2. Check if generator (if applied) is working well or if input voltage range setting is correct. (UPS Appliance) |
| Set "Solar First" as the priority of output source. | Change output source priority to Utility first. | |
| When the unit is turned on, internal relay is switched on and off repeatedly. | Battery is disconnected. | Check if battery wires are connected well. |
| Overload error. The inverter is overloaded 110% and time is up. | Reduce the connected load by switching off some equipment. | |
| Output short circuited. | Check if wiring is connected well and remove abnormal load. | |
| Temperature of internal converter component is over 120°C. | Check whether the air flow of the unit is blocked or whether the ambient temperature is too high. | |
| Internal temperature of inverter component is over 100°C. | Return to repair center. | |
| Battery is over-charged. | Check if spec and quantity of batteries are meet requirements. | |
| Buzzer beeps continuously and red LED is on. | Fan fault | Replace the fan. |
| Output abnormal (Inverter voltage below than 190Vac or is higher than 260Vac) | 1. Reduce the connected load. 2. Return to repair center |
|
| Internal components failed. | Return to repair center. | |
| Over current or surge. | Restart the unit, if the error happens again, please return to repair center. | |
| Bus voltage is too low. | ||
| Output voltage is unbalanced. | ||
| Battery is not connected well or fuse is burnt. | If the battery is connected well, please return to repair center. |
7. Specifications
7.1 Table 1 Line Mode Specifications
| INVERTER MODEL | 3.0KW/24V | 4.0KW/24V |
|---|---|---|
| Input Voltage Waveform | Sinusoidal (utility or generator) | |
| Nominal Input Voltage | 120Vac | |
| Low Loss Voltage | 95Vac±5V(UPS); 65Vac±7V(Appliances) | |
| Low Loss Return Voltage | 100Vac±5V(UPS); 70Vac±5V(Appliances) | |
| High Loss Voltage | 140Vac±5V | |
| High Loss Return Voltage | 135Vac±5V | |
| Max AC Input Voltage | 150Vac | |
| Nominal Input Frequency | 50Hz/60Hz (It can be set in program 09) | |
| Low Loss Frequency | 45±1Hz/55±1Hz | |
| Low Loss Return Frequency | 47±1Hz/57±1Hz | |
| High Loss Frequency | 55±1Hz/65±1Hz | |
| High Loss Return Frequency | 53±1Hz/63±1Hz | |
| Output Short Circuit Protection | Line mode: Circuit Breaker Battery mode: Electronic Circuits | |
| Efficiency (Line Mode) | >95% (Rated R load, battery full charged) | |
| Transfer Time | 10ms typical (UPS); 20ms typical (Appliances) | |
7.2 Table 2 Inverter Mode Specifications
| INVERTER MODEL | 3.0KW/24V | 4.0KW/24V |
|---|---|---|
| Rated Output Power | 3.0KW | 4.0KW |
| Output Voltage Waveform | Pure Sine Wave | |
| Output Voltage Regulation | 120Vac±5% | |
| Output Frequency | 60Hz or 50Hz | |
| Peak Efficiency | 94% | |
| Overload Protection | 5s@≥150% load; 10s@110%~150% load | |
| Surge Capacity | 2* rated power for 5 seconds | |
| Nominal DC Input Voltage | 24Vdc | |
| Cold Start Voltage | 23.0Vdc | |
| Low DC Warning Voltage | 22.0Vdc | |
| Low DC Warning Return Voltage | 23.0Vdc | |
| Low DC Cut-off Voltage | 21.0Vdc | |
| High DC Recovery Voltage | 29Vdc | |
| High DC Cut-off Voltage | 31Vdc | |
| No Load Power Consumption | <35W | |
7.3 Table 3 Charge Mode Specifications
Utility Charging Mode:
| INVERTER MODEL | 3.0KW/24V | 4.0KW/24V |
|---|---|---|
| Charging Current (UPS) @ Nominal Input Voltage | 80A | 110A |
| Bulk Charging Voltage (Flooded) | 29.2Vdc | |
| Bulk Charging Voltage (AGM / Gel Battery) | 28.2Vdc | |
| Floating Charging Voltage | 27Vdc | |
| Charging Algorithm | 3-Step | |
Solar Charging Mode:
| INVERTER MODEL | 3.0KW/24V | 4.0KW/24V |
|---|---|---|
| Rated Power | 5600W | |
| PV Charge Current | 100A | 140A |
| Efficiency | 98.0% max. | |
| Max. PV Array Open Circuit Voltage | 350Vdc | |
| PV Array MPPT Voltage Range | 55-350Vdc | |
| Standby Power Consumption | 2W | |
| Battery Voltage Accuracy | +/-0.3% | |
| PV Voltage Accuracy | +/-2V | |
| Charging Algorithm | 3-Step | |
7.4 Table 4 General Specifications
| INVERTER MODEL | 3.0KW/24V | 4.0KW/24V |
|---|---|---|
| Safety Certification | CE | |
| Operating Temperature Range | 0°C to 55°C | |
| Storage temperature | -15°C~60°C | |
| Dimension (D*W*H), mm | 400*250*89mm | |
| Net Weight, kg | 7.5kg | 8.5kg |
7.5 Appendix: Approximate Back-up Time Table
| Model | Load (W) | Backup Time @ 24Vdc 100Ah (min) | Backup Time @ 24Vdc 200Ah (min) |
|---|---|---|---|
| 4.0KW | 300 | 449 | 1100 |
| 600 | 222 | 525 | |
| 900 | 124 | 303 | |
| 1200 | 95 | 227 | |
| 1500 | 68 | 164 | |
| 1800 | 56 | 126 | |
| 2100 | 48 | 108 | |
| 2400 | 35 | 94 | |
| 2700 | 31 | 74 | |
| 3200 | 28 | 67 |
Note: Backup time depends on the quality of the battery, age of battery, and type of battery. Specifications of batteries may vary depending on different manufacturers.
* Product technical specifications are subject to change without notice.
8. User Tips
- WiFi Monitoring: If your inverter includes the optional WiFi monitoring function, ensure proper setup and stable connection to avoid constant offline issues. Check compatibility with your specific application and network settings.
- Appliance Compatibility: The inverter is designed to power various home appliances. When connecting high-power devices like air conditioners (e.g., a 12000 BTU dual inverter AC), verify that the inverter's output capacity (e.g., 4KW, 4.5KW, 6.5KW) is sufficient for the appliance's starting and running wattage. Consult the appliance's specifications and the inverter's overload protection limits.
- Battery Selection: Always use compatible battery types (sealed lead-acid, GEL/AGM, or specific lithium batteries with BMS communication). Incorrect battery types or configurations can lead to malfunction or damage.
- Wiring Integrity: Double-check all wiring connections (battery, AC input/output, PV) for correct polarity, secure fastening, and appropriate cable gauges to prevent faults and ensure efficient operation.
9. Warranty and Support
For any issues not resolved by the troubleshooting guide, or for service and repair, please contact your local dealer or an authorized service center. Only qualified service personnel should attempt repairs to avoid electric shock or further damage to the unit.
The product is certified with CE, ensuring compliance with European safety standards.