SUMRY HGX Series

Contents

SUMRY HGX Series Hybrid Solar Inverter User Manual

Models: 3.0KW/4.0KW/4.5KW/6.5KW Inverter / Charger

1. Introduction

This manual describes the assembly, installation, operation, and troubleshooting of your SUMRY HGX Series Hybrid Solar Inverter. Please read this manual carefully before installation and operation, and keep it for future reference.

The SUMRY HGX Series Hybrid Solar Inverter is a multi-function inverter/charger, combining the functions of an inverter, MPPT solar charger, and battery charger to provide uninterruptible power support in a portable size. Its comprehensive large LCD display offers user-configurable and easy-to-access touch button operation for settings such as battery charging current, AC/solar charger priority, and acceptable input voltage based on different applications.

Key Features:

  • Off-grid solar inverter functionality.
  • No battery function available (for specific configurations).
  • Adjustable AC voltage (100VAC, 110VAC, 120VAC) in Under Battery Mode.
  • Utility power, battery, and PV power complement each other.
  • Pure sine wave solar inverter output.
  • Unique glass top cover design with 6.25-inch LCD display and touchable buttons.
  • Built-in 140A MPPT (Max PV 5600W) solar charger.
  • High PV input range from 55V-350Vdc.
  • Smart battery charger design for optimized battery performance.
  • Configurable AC/Battery input priority via LCD setting.
  • Auto restart while PV is recovering.
  • Overload, over-temperature, and output short circuit protection.
  • Cold restart function.
  • Built-in lithium battery automatic activation.
  • Communication with RS232/RS485.
  • WiFi monitoring function (optional).
  • Anti-dust kit for harsh environments (optional).
  • Restore default settings with one click.

Basic System Architecture:

The inverter/charger can power various home and office appliances, including motor-type appliances like tube lights, fans, refrigerators, and air conditioners. A typical system includes solar modules (optional), a generator or utility grid, battery packs, and home appliances.

Diagram showing the hybrid power system architecture with solar panels, generator/utility, inverter, battery, and home appliances.
Figure 1: Hybrid Power System Architecture
Diagram showing the 4KW Solar Inverter connections for solar power, generator/utility, battery, and home appliances.
Figure 2: 4KW Solar Inverter with 6.25-inch LCD Screen & Touch Buttons Display and Connection Overview

2. Safety Instructions

WARNING: This chapter contains important safety and operating instructions. Read and keep this manual for future reference.

  1. Before using the unit, read all instructions and cautionary markings on the unit, the batteries, and all appropriate sections of this manual.
  2. CAUTION: To reduce the risk of injury, charge only deep-cycle lead-acid type rechargeable batteries. Other types of batteries may burst, causing personal injury and damage.
  3. Do not disassemble the unit. Take it to a qualified service center when service or repair is required. Incorrect re-assembly may result in a risk of electric shock or fire.
  4. To reduce the risk of electric shock, disconnect all wirings before attempting any maintenance or cleaning. Turning off the unit will not reduce this risk.
  5. CAUTION: Only qualified personnel can install this device with a battery.
  6. NEVER charge a frozen battery.
  7. For optimum operation of this inverter/charger, please follow the required specifications to select appropriate cable size. It's very important to correctly operate this inverter/charger.
  8. Be very cautious when working with metal tools on or around batteries. A potential risk exists to drop a tool to spark or short circuit batteries or other electrical parts and could cause an explosion.
  9. Please strictly follow the installation procedure when you want to disconnect AC or DC terminals. Please refer to the INSTALLATION section of this manual for details.
  10. GROUNDING INSTRUCTIONS: This inverter/charger should be connected to a permanent grounded wiring system. Be sure to comply with local requirements and regulations to install this inverter.
  11. NEVER cause AC output and DC input short-circuited. Do NOT connect to the mains when DC input short circuits.
  12. Warning!! Only qualified service persons are able to service this device. If errors still persist after following the troubleshooting table, please send this inverter/charger back to the local dealer or service center for maintenance.

3. Setup

3.1 Unpacking and Inspection

Before installation, please inspect the unit. Be sure that nothing inside the package is damaged. You should have received the following items:

  • The inverter unit x 1
  • User manual x 1
Video: Unboxing and initial setup demonstration of the SUMRY Hybrid Solar Inverter.

3.2 Preparation

Before connecting any wiring, remove the bottom cover by unscrewing the two screws as shown in the diagram below.

3.3 Mounting the Unit

Consider the following points when selecting an installation location:

  • Do not mount the inverter on flammable construction materials.
  • Mount on a solid surface.
  • Install this inverter at eye level to allow the LCD display to be read easily.
  • The ambient temperature should be between 0°C and 55°C for optimal operation.
  • The recommended installation position is vertically on a wall.
  • Ensure sufficient heat dissipation and space for wiring by maintaining clearances as shown in the diagram.

CAUTION: Suitable for mounting on concrete or other non-combustible surfaces only.

Diagram showing recommended mounting clearances for the inverter.
Figure 3: Recommended Mounting Clearances (20cm sides, 50cm top/bottom)

Install the unit by screwing two screws into the wall.

3.4 Battery Connection

CAUTION: For safety and regulatory compliance, install a separate DC over-current protector or disconnect device between the battery and inverter. It is still recommended to have over-current protection installed even if a disconnect device is not required in some applications.

WARNING: All wiring must be performed by qualified personnel. Use appropriate cable for battery connection to reduce risk of injury. Use the proper recommended cable and terminal size.

Follow these steps for battery connection:

  1. Assemble battery ring terminals based on recommended battery cable and terminal size.
  2. Connect all battery packs as required.
  3. Insert the ring terminal of the battery cable flatly into the battery connector of the inverter and ensure the bolts are tightened with a torque of 2-3 Nm. Ensure correct polarity (+ to + and - to -) at both the battery and the inverter/charger, and that ring terminals are tightly screwed to the battery terminals.

NOTE: Only use sealed lead-acid, sealed GEL/AGM lead-acid, or lithium batteries.

WARNING: Shock Hazard! Installation must be performed with care due to high battery voltage in series.

CAUTION: Do not place anything between the flat part of the inverter terminal and the ring terminal, as overheating may occur. Do not apply anti-oxidant substance on the terminals before they are connected tightly. Before making the final DC connection or closing the DC breaker/disconnector, ensure positive (+) is connected to positive (+) and negative (-) to negative (-).

Model Typical Amperage Battery Capacity Wire Size Cable (mm²) Torque Value (Nm)
3.0KW 24V 110A 100AH / 200AH 1*4AWG 22 2~3
4.0KW 24V 150A 200AH 1*2AWG 35 2~3
Wiring diagram showing connections for solar power, generator, utility, external battery packs, and home appliances with circuit breakers.
Figure 4: Installation Knowledge and Wiring Diagram with Circuit Breakers. Before installing and using the inverter, it is recommended to install 4 circuit breakers in the following positions: 1. Between the battery and the inverted battery. 2. Between the solar panel and the photovoltaic input of the inverter. 3. Between the grid power input and the inverter. 4. Between the inverter output and the load. The circuit breaker is to effectively prevent wrong connection or reverse connection of the middle input and inverter output; when there is a short circuit, short circuit load, or overload at the output, the circuit breaker can directly cut off the circuit to protect the Inverter.

3.5 AC Input/Output Connection

CAUTION: Before connecting to an AC input power source, install a separate AC breaker between the inverter and the AC input power source. This ensures the inverter can be securely disconnected during maintenance and fully protected from overcurrent. Recommended AC breaker specs: 32A for 3.0KW, 40A for 4.0KW.

CAUTION: There are two terminal blocks labeled "INPUT" and "OUTPUT". Do NOT mis-connect input and output connectors.

WARNING: All wiring must be performed by qualified personnel. Use appropriate cable for AC input connection to reduce risk of injury. Use the proper recommended cable size.

Follow these steps for AC input/output connection:

  1. Before making AC input/output connections, ensure the DC protector or disconnector is open.
  2. Remove 10mm of insulation from the six conductors. Shorten phase L and neutral conductor N by 3mm.
  3. Insert AC input wires according to the polarities indicated on the terminal block and tighten the terminal screws.
  4. Insert AC output wires according to the polarities indicated on the terminal block and tighten the terminal screws. Be sure to connect the PE protective conductor (Ground) first.
  5. Ensure all wires are securely connected.

CAUTION: Important! Be sure to connect AC wires with correct polarity. If L and N wires are connected reversely, it may cause utility short-circuited when these inverters are operated in parallel. Appliances like air conditioners require 2-3 minutes to restart. If a power shortage occurs and recovers quickly, it can damage connected appliances. Check the air conditioner manufacturer for time-delay function before installation. Otherwise, the inverter/charger may trigger overload fault to protect the appliance, but internal damage to the air conditioner may still occur.

Suggested Cable Requirement for AC Wires:

Model Gauge Torque Value (Nm)
3.0KW 10 AWG 1.2~1.6
4.0KW 8 AWG 1.4~1.6

3.6 PV Connection

CAUTION: Before connecting to PV modules, install a separate DC circuit breaker between the inverter and PV modules.

WARNING: All wiring must be performed by qualified personnel. Use appropriate cable for PV module connection to reduce risk of injury. Use the proper recommended cable size.

Follow these steps for PV module connection:

  1. Remove 10mm of insulation from positive and negative conductors.
  2. Check correct polarity of connection cable from PV modules and PV input connectors. Connect positive (+) to positive (+) and negative (-) to negative (-).
  3. Ensure all wires are securely connected.

PV Module Selection:

When selecting PV modules, consider the following parameters:

  • Open circuit Voltage (Voc) of PV modules should not exceed the max. PV array open circuit voltage of the inverter.
  • Open circuit Voltage (Voc) of PV modules should be higher than the min. PV Array MPPT Voltage range.
INVERTER MODEL 3.0KW 4.0KW
Max. PV Array Open Circuit Voltage 350Vdc
PV Array MPPT Voltage Range 55Vdc~350Vdc
Model Wire Size Cable (mm²) Torque Value (max)
3.0KW/4.0KW 1 x 12AWG 4 1.2 Nm

3.7 Final Assembly

After connecting all wirings, replace the bottom cover by screwing the two screws back in.

4. Operating Instructions

4.1 Power ON/OFF

Once the unit is properly installed and the batteries are connected, simply press the On/Off switch (located on the bottom of the case) to turn on the unit.

4.2 Operation and Display Panel

The operation and display panel is located on the front of the inverter. It includes three indicators, four function keys, and an LCD display, providing operating status and input/output power information.

Front view of the inverter showing LCD display, status indicators, and function touch buttons.
Figure 5: Inverter Front Panel - LCD Display, Indicators, and Buttons

LED Indicators and Messages:

LED Indicator Color State Messages
AC/INV Green Solid On Output is powered by utility in Line mode.
Flashing Output is powered by battery or PV in battery mode.
CHG Green Solid On Battery is fully charged.
Flashing Battery is charging.
FAULT Red Solid On Fault occurs in the inverter.
Flashing Warning condition occurs in the inverter.

Function Keys:

Function Key Description
ESC To exit setting mode
UP To go to previous selection
DOWN To go to next selection
ENTER To confirm the selection in setting mode or enter setting mode

4.3 LCD Display Icons

The LCD displays various information including input source, configuration, fault information, output, and battery status. Refer to the manual for a detailed breakdown of each icon.

Load Information:

The right-side flashing bar and load icon indicate the load level by 0-24%, 25-50%, 50-75%, and 75-100%.

Mode Operation Information:

  • Indicates unit connects to the mains.
  • Indicates unit connects to the PV panel.
  • Indicates load is supplied by utility power (BYPASS).
  • Indicates the utility charger circuit is working.
  • Indicates the DC/AC inverter circuit is working.

Mute Operation:

  • Indicates unit alarm is disabled.

4.4 LCD Settings

To enter setting mode, press and hold the ENTER button for 3 seconds. Use the UP or DOWN buttons to select programs, and ENTER to confirm or ESC to exit. Key settings include:

  • Program 00: Exit setting mode.
  • Program 01: Output source priority: Configures load power source priority (Solar first, SBU mode, or Utility first).
  • Program 02: Maximum charging current: Configures total charging current for solar and utility chargers.
  • Program 03: AC input voltage range: Selects acceptable AC input voltage range (Appliances or UPS).
  • Program 04: Power saving mode enable/disable: Enables or disables power saving mode.
  • Program 05: Battery type: Selects battery type (AGM, Flooded, Lithium battery, User-Defined, or Lithium battery with communication).
  • Program 06: Auto restart when overload occurs: Enables or disables auto restart after overload.
  • Program 07: Auto restart when over temperature occurs: Enables or disables auto restart after over temperature.
  • Program 08: Output voltage: Sets output voltage (100V, 110V, 120V).
  • Program 09: Output frequency: Sets output frequency (50Hz, 60Hz).
  • Program 11: Maximum utility charging current: Sets the maximum charging current from utility.
  • Program 12: Setting voltage point back to utility source when selecting "SBU priority": Configures the voltage point for switching to utility in SBU mode.
  • Program 13: Setting voltage point back to battery mode when selecting "SBU priority": Configures the voltage point for switching to battery in SBU mode.
  • Program 16: Charger source priority: Configures charger source priority (Solar first, Solar and Utility, or Only Solar).
  • Program 18: Alarm control: Enables or disables alarms.
  • Program 19: Auto return to default display screen: Configures whether the display returns to default after inactivity.
  • Program 20: Backlight control: Turns backlight on or off.
  • Program 22: Beeps while primary source is interrupted: Enables or disables beeping on primary source interruption.
  • Program 25: Record Fault code: Enables or disables fault code recording.
  • Program 26: Bulk charging voltage (C.V voltage): Sets the bulk charging voltage.
  • Program 27: Floating charging voltage: Sets the floating charging voltage.
  • Program 29: Low DC cut-off voltage: Sets the low DC cut-off voltage.
  • Program 30: Restore default settings: Restores all settings to default.
  • Program 33: Battery equalization: Enables or disables battery equalization.
  • Program 34: Battery equalization voltage: Sets the battery equalization voltage.
  • Program 35: Battery equalized time: Sets the duration for battery equalization.
  • Program 36: Battery equalized timeout: Sets the timeout for battery equalization.
  • Program 37: Equalization interval: Sets the interval between battery equalization cycles.
  • Program 39: Equalization activated immediately: Activates battery equalization immediately.

4.5 Lithium Battery Connection and Settings

If the inverter is matched with lithium batteries, only those with a compatible BMS communication protocol are allowed. You must set the battery type to "Lib-485" in Program 5.

Connecting RJ45 to BMS Communication Port: Ensure the BMS port of the lithium battery corresponds to the pin of the inverter's BMS communication port. The inverter BMS interface pin definition is provided in the manual.

Note: When the battery type is set to "Lib-485", the charge current cannot be modified by the user. If communication fails, the inverter will cut off output. If the communication protocol does not match, you can select "LIB" mode.

4.6 Operating Mode Description

The inverter operates in various modes, including Standby, Power Saving, and Line Mode, with different charging and power supply behaviors depending on the selected priority and available power sources.

Battery Equalization Description:

Battery equalization reverses negative chemical effects like stratification and removes sulfate crystals, improving battery capacity and lifespan. It can be applied by setting an equalization interval (Program 37) or activating immediately (Program 39), provided the function is enabled in Program 33.

5. Maintenance

To ensure the longevity and safe operation of your inverter, regular maintenance is recommended. Always disconnect all wirings before attempting any maintenance or cleaning to prevent electric shock. The unit should be cleaned periodically to prevent dust buildup, especially around cooling vents, which can affect performance and lead to overheating.

Periodically check all cable connections for tightness and signs of wear or corrosion. Ensure that the ambient temperature around the inverter remains within the specified operating range (0°C to 55°C) to prevent overheating.

6. Troubleshooting

This section provides solutions for common issues. If an error persists after following these steps, contact a qualified service center.

Fault Reference Code:

Fault Code Fault Event
01Fan is locked when inverter is off.
02Over temperature
03Battery voltage is too high
04Battery voltage is too low
05Output short circuited or over temperature is detected by internal converter components.
06Output voltage is too high.
07Overload time out
08Bus voltage is too high
09Bus soft start failed
11Main relay failed
51Over current or surge
52Bus voltage is too low
53Inverter soft start failed
55Over DC voltage in AC output
56Battery connection is open
57Current sensor failed
58Output voltage is too low

Warning Indicator:

Warning Code Warning Event Audible Alarm
01Fan is locked when inverter is on.Beep twice every second
03Battery is over-chargedBeep twice every second
04Low batteryBeep twice every second
07OverloadBeep twice every second
10Output power deratingBeep twice every second
12Solar charger stops due to low battery.
13Solar charger stops due to high PV voltage.
14Solar charger stops due to overload.
15PV is weak
61When the battery communication is abnormal, stop charging and discharging.

Troubleshooting Table:

Problem Explanation / Possible Cause What to do
Unit shuts down automatically during startup process. The battery voltage is too low (<1.91V/Cell) 1. Re-charge battery.
2. Replace battery.
No response after power on. 1. The battery voltage is far too low. (<1.4V/Cell)
2. Battery polarity is connected reversed.
1. Check if batteries and the wiring are connected well.
2. Re-charge battery.
3. Replace battery.
Input protector is tripped Check if AC breaker is tripped and AC wiring is connected well.
Mains exist but the unit works in battery mode. Insufficient quality of AC power. (Shore or Generator) 1. Check if AC wires are too thin and/or too long.
2. Check if generator (if applied) is working well or if input voltage range setting is correct. (UPS Appliance)
Set "Solar First" as the priority of output source. Change output source priority to Utility first.
When the unit is turned on, internal relay is switched on and off repeatedly. Battery is disconnected. Check if battery wires are connected well.
Overload error. The inverter is overloaded 110% and time is up. Reduce the connected load by switching off some equipment.
Output short circuited. Check if wiring is connected well and remove abnormal load.
Temperature of internal converter component is over 120°C. Check whether the air flow of the unit is blocked or whether the ambient temperature is too high.
Internal temperature of inverter component is over 100°C. Return to repair center.
Battery is over-charged. Check if spec and quantity of batteries are meet requirements.
Buzzer beeps continuously and red LED is on. Fan fault Replace the fan.
Output abnormal (Inverter voltage below than 190Vac or is higher than 260Vac) 1. Reduce the connected load.
2. Return to repair center
Internal components failed. Return to repair center.
Over current or surge. Restart the unit, if the error happens again, please return to repair center.
Bus voltage is too low.
Output voltage is unbalanced.
Battery is not connected well or fuse is burnt. If the battery is connected well, please return to repair center.

7. Specifications

7.1 Table 1 Line Mode Specifications

INVERTER MODEL 3.0KW/24V 4.0KW/24V
Input Voltage WaveformSinusoidal (utility or generator)
Nominal Input Voltage120Vac
Low Loss Voltage95Vac±5V(UPS); 65Vac±7V(Appliances)
Low Loss Return Voltage100Vac±5V(UPS); 70Vac±5V(Appliances)
High Loss Voltage140Vac±5V
High Loss Return Voltage135Vac±5V
Max AC Input Voltage150Vac
Nominal Input Frequency50Hz/60Hz (It can be set in program 09)
Low Loss Frequency45±1Hz/55±1Hz
Low Loss Return Frequency47±1Hz/57±1Hz
High Loss Frequency55±1Hz/65±1Hz
High Loss Return Frequency53±1Hz/63±1Hz
Output Short Circuit ProtectionLine mode: Circuit Breaker
Battery mode: Electronic Circuits
Efficiency (Line Mode)>95% (Rated R load, battery full charged)
Transfer Time10ms typical (UPS); 20ms typical (Appliances)

7.2 Table 2 Inverter Mode Specifications

INVERTER MODEL 3.0KW/24V 4.0KW/24V
Rated Output Power3.0KW4.0KW
Output Voltage WaveformPure Sine Wave
Output Voltage Regulation120Vac±5%
Output Frequency60Hz or 50Hz
Peak Efficiency94%
Overload Protection5s@≥150% load; 10s@110%~150% load
Surge Capacity2* rated power for 5 seconds
Nominal DC Input Voltage24Vdc
Cold Start Voltage23.0Vdc
Low DC Warning Voltage22.0Vdc
Low DC Warning Return Voltage23.0Vdc
Low DC Cut-off Voltage21.0Vdc
High DC Recovery Voltage29Vdc
High DC Cut-off Voltage31Vdc
No Load Power Consumption<35W

7.3 Table 3 Charge Mode Specifications

Utility Charging Mode:

INVERTER MODEL 3.0KW/24V 4.0KW/24V
Charging Current (UPS) @ Nominal Input Voltage80A110A
Bulk Charging Voltage (Flooded)29.2Vdc
Bulk Charging Voltage (AGM / Gel Battery)28.2Vdc
Floating Charging Voltage27Vdc
Charging Algorithm3-Step

Solar Charging Mode:

INVERTER MODEL 3.0KW/24V 4.0KW/24V
Rated Power5600W
PV Charge Current100A140A
Efficiency98.0% max.
Max. PV Array Open Circuit Voltage350Vdc
PV Array MPPT Voltage Range55-350Vdc
Standby Power Consumption2W
Battery Voltage Accuracy+/-0.3%
PV Voltage Accuracy+/-2V
Charging Algorithm3-Step

7.4 Table 4 General Specifications

INVERTER MODEL 3.0KW/24V 4.0KW/24V
Safety CertificationCE
Operating Temperature Range0°C to 55°C
Storage temperature-15°C~60°C
Dimension (D*W*H), mm400*250*89mm
Net Weight, kg7.5kg8.5kg

7.5 Appendix: Approximate Back-up Time Table

Model Load (W) Backup Time @ 24Vdc 100Ah (min) Backup Time @ 24Vdc 200Ah (min)
4.0KW3004491100
600222525
900124303
120095227
150068164
180056126
210048108
24003594
27003174
32002867

Note: Backup time depends on the quality of the battery, age of battery, and type of battery. Specifications of batteries may vary depending on different manufacturers.

* Product technical specifications are subject to change without notice.

8. User Tips

  • WiFi Monitoring: If your inverter includes the optional WiFi monitoring function, ensure proper setup and stable connection to avoid constant offline issues. Check compatibility with your specific application and network settings.
  • Appliance Compatibility: The inverter is designed to power various home appliances. When connecting high-power devices like air conditioners (e.g., a 12000 BTU dual inverter AC), verify that the inverter's output capacity (e.g., 4KW, 4.5KW, 6.5KW) is sufficient for the appliance's starting and running wattage. Consult the appliance's specifications and the inverter's overload protection limits.
  • Battery Selection: Always use compatible battery types (sealed lead-acid, GEL/AGM, or specific lithium batteries with BMS communication). Incorrect battery types or configurations can lead to malfunction or damage.
  • Wiring Integrity: Double-check all wiring connections (battery, AC input/output, PV) for correct polarity, secure fastening, and appropriate cable gauges to prevent faults and ensure efficient operation.

9. Warranty and Support

For any issues not resolved by the troubleshooting guide, or for service and repair, please contact your local dealer or an authorized service center. Only qualified service personnel should attempt repairs to avoid electric shock or further damage to the unit.

The product is certified with CE, ensuring compliance with European safety standards.