1. Introduction and Overview
The EARU T80 Intelligent Pressure Controller is a versatile device designed for precise liquid level measurement and control. It features a light column display for intuitive visualization of liquid levels and a digital display for exact values. With a 4-20mA input signal, it is compatible with a wide range of liquid level transmitters and offers relay on-off signal outputs for control applications.
This controller is engineered for broad media compatibility, capable of measuring levels in various liquids, from water and oil to viscous sewage. Its advanced temperature compensation ensures stable and accurate readings, even in challenging environments where foaming or material deposition might occur. The T80 is suitable for applications requiring liquid level monitoring and control up to 200 meters deep.
2. Safety Information
- Ensure all electrical connections are made by qualified personnel in accordance with local electrical codes.
- Verify the power supply voltage (AC85~260V) matches the device requirements before connecting.
- Disconnect power before performing any installation, wiring, or maintenance.
- Avoid exposing the device to extreme temperatures, humidity, or corrosive environments unless specifically rated for such conditions.
- Do not attempt to open or repair the device yourself. Refer to authorized service personnel.
3. Product Features
- Wide Media Compatibility: Measures water, oil, sewage, and viscous liquids.
- Temperature Compensation: Unaffected by foaming or deposition of measured medium.
- Deep Measurement Capability: Supports measurements up to 200 meters deep.
- High Precision Sensor: Utilizes a diffusion silicon sensor for accurate and stable measurements (0.5 Class precision).
- Robust Probe Design: Transmitter probe features a full stainless steel sealing structure, silicone oil filling, and complete isolation of the sensor chip from the media.
- User-Friendly Display: Equipped with a light column display for visual level indication and a digital PV display for precise readings.
- Flexible Control Outputs: Provides four relay on-off signal outputs for alarm and control functions.
- Compact and Durable: Strong, compact structure for easy installation and long-term use.
- Versatile Applications: Ideal for water plants, sewage treatment, urban water supply, high-rise pools, wells, mines, industrial water, water tanks, oil pools, hydrological geology, reservoirs, rivers, and seas.
4. Specifications
| Parameter | Value |
|---|---|
| Model Number | T80 |
| Brand Name | EARU |
| Power Supply | AC85~260V |
| Input Signal | 4~20mA |
| Output Signal | Relay on-off Signal (or Other Customization) |
| Precision | 0.5 Class |
| Measuring Range | -999~9999 |
| Power Consumption | ≤3W |
| Load Power | ≤200W (Resistive Load) |
| Measuring Medium | Liquid |
| Weight | Approx. 521g / 18.4oz |
| Dimensions (L x W x H) | 160mm x 80.9mm x 94.8mm |
| Certification | CE |
| Battery Included | No |
Physical Dimensions

Image: Front and side views of the T80 controller with key dimensions (160mm length, 80.9mm width, 94.8mm height) and a table of product parameters.
5. Components and Front Panel Overview
Front Panel Layout

Image: Detailed view of the T80 controller's front panel, highlighting the light column display, digital PV display, and control buttons.
- Measuring Light Column Display: Visual representation of the measured value, often indicating percentage or relative level.
- Measuring Value Display (PV): Digital display showing the precise measured value.
- Alarm Indicators:
- AHH: Upper Limit Alarm (High High)
- AH: Upper Limit Alarm (High)
- AL: Lower Limit Alarm (Low)
- ALL: Lower Limit Alarm (Low Low)
- SET Button: Used to confirm settings and enter/exit programming modes.
- Up Arrow Key: Increases numerical values during setting.
- Down Arrow Key: Reduces numerical values during setting.
- Right Arrow (Shift) Key: Moves the cursor or shifts digits during setting.
6. Setup and Installation
Proper installation and wiring are crucial for the correct operation of the T80 controller. Refer to the following diagrams and instructions carefully.
6.1 General Terminal Connections

Image: Terminal block of the T80 controller, showing connections for power, sensor input, and relay outputs.
- Power Supply (AC 220V): Connect the Live (L) wire to terminal 23 and the Neutral (N) wire to terminal 24.
- Sensor Input (4-20mA): Connect the positive wire of your 4-20mA liquid level transmitter to terminal 13 (+24V) and the negative wire to terminal 7 (0-20mA-).
- Relay Outputs: The controller provides four relay outputs for alarm switches (AHH, AH, AL, ALL). These can be used to control external devices such as pumps, valves, or alarms. Refer to specific application diagrams for detailed connections.
6.2 Application-Specific Wiring Diagrams
6.2.1 220V Water Pump Control (Drainage)

Image: Diagram illustrating how to wire the T80 controller to a 220V water pump via an alternating current contactor for drainage, where the pump starts when the level is high and stops when it's low.
This diagram shows a typical setup for drainage. The liquid level transmitter sends data to the T80 controller. The controller's relay output (e.g., a lower limit alarm switch) activates an Alternating Current Contactor, which in turn controls the 220V water pump. The pump will operate to drain liquid when the level reaches a set high point and stop when it reaches a set low point.
6.2.2 Liquid Level Display with Alarms

Image: Wiring diagram for connecting high and low level alarms to the T80 controller, along with the liquid level sensor and power supply.
Connect external high and low alarms to the corresponding Upper Limit Alarm and Lower Limit Alarm switches on the T80 controller. Ensure the 220V incoming line (Zero Line and Firewire) is connected to a power switch for safety and control.
6.2.3 Valve Control for Water Make-Up

Image: Schematic showing the T80 controller managing a water make-up system, where a pump and solenoid valve are activated at low water levels and deactivated at high levels.
In a water make-up system, the T80 controller receives water level information. Its outputs control an AC Contactor, which then manages both a water pump and a water inlet solenoid valve. The pump and valve will turn on when the water level drops below a set lower limit and turn off when it reaches the upper limit.
6.2.4 Three-Phase Water Pump Control

Image: Wiring diagram for controlling a three-phase water pump using the T80 controller and a 380V alternating current contactor.
For three-phase water pump control, the principle is similar to the 220V pump. The T80 controller's power supply remains 220V. The relay output controls a 380V Alternating Current Contactor, which then manages the three-phase water pump. If there is no neutral line available on site for the 220V power supply, a small 380V to 220V transformer may be required to power the T80 controller.
6.2.5 Liquid Level Transmitter Connection to Display

Image: Diagram showing the direct connection of a liquid level transmitter to the T80 controller's input terminals.
This diagram illustrates the basic connection of a liquid level transmitter to the T80 controller. The P20V power supply for the transmitter is connected to terminals 13 and 7. The transmitter's positive output connects to terminal 13, and its negative output connects to terminal 7.
6.2.6 Detailed Drainage Wiring Diagram

Image: A more detailed wiring diagram for drainage control, showing sensor connections and outputs for solenoid valves and pumps.
Connect the sensor's red wire to terminal A (positive, typically +24V) and the black wire to terminal B (negative, typically 0-20mA-). Terminals C and D can be connected to a solenoid valve or a small pump motor. For loads exceeding 3A, an AC solver (contactor) should be added to control larger pumps. Terminals C and D can also be used as upper limit alarm switch signals. Terminals E and F connect to the AC 220V power supply; the zero and fire wires are indistinguishable for this connection.
6.2.7 Two Sensors Driven by One Light Column Meter

Image: Diagram showing how two T80 controllers can be connected to a single 4-20mA two-wire system transmitter, allowing multiple displays for one sensor.
This configuration allows a single 4-20mA two-wire system transmitter to drive two T80 light column meters, providing redundant or remote display capabilities for the same liquid level measurement.
7. Operating Instructions
7.1 Basic Operation
Once the T80 controller is correctly wired and powered on, it will display the current liquid level on both the light column and the digital PV display. The light column provides a quick visual reference, while the digital display offers precise numerical data.
7.2 Setting Alarm Limits and Parameters
To set alarm limits (AHH, AH, AL, ALL) or other operational parameters, use the front panel buttons:
- Press the SET button to enter the parameter setting mode.
- Use the Up Arrow and Down Arrow keys to adjust numerical values.
- Use the Right Arrow (Shift) key to move between digits or parameters.
- Press SET again to confirm changes and exit the setting mode.
Consult the full programming manual (if available) for detailed parameter codes and their functions, including input signal type setting, output mode setting, and zero/range adjustment.
7.3 Operational Demonstration
Watch this video demonstration to see the T80 controller in action, controlling water levels between set limits.
Video: Demonstration of the T80 controller managing water levels. The video shows the controller activating a pump when the water level drops below 20cm and deactivating it when the level reaches 30cm, maintaining the water level within the desired range. The light column and digital display dynamically reflect the changes.
8. Maintenance
- Regular Cleaning: Keep the front panel and display clean using a soft, dry cloth. Avoid abrasive cleaners or solvents.
- Connection Checks: Periodically inspect all wiring connections for tightness and signs of corrosion or damage.
- Sensor Inspection: If using a liquid level transmitter, regularly check the probe for buildup, fouling, or damage, especially in harsh environments. Clean the sensor according to its manufacturer's instructions.
- Calibration: If accuracy issues arise, recalibrate the sensor and controller according to the detailed instructions in the full product manual.
9. Troubleshooting
- No Power/Display Off:
- Check the AC85~260V power supply connection to terminals 23 and 24.
- Ensure the power source is active.
- Incorrect Readings/No Signal:
- Verify the 4-20mA sensor wiring to terminals 13 and 7.
- Check the sensor itself for proper operation and cleanliness.
- Ensure the input signal type is correctly configured in the controller's settings.
- Alarms Not Triggering/Outputs Not Working:
- Confirm alarm limits are set correctly in the controller.
- Check the wiring of external devices (pumps, valves, alarms) to the relay output terminals.
- Verify the output mode setting in the controller.
- Display Flashing/Error Codes:
- Refer to the detailed programming manual for specific error code interpretations.
- Try power cycling the device.
10. User Tips
- Parameterization for Specific Heights: The T80 controller is highly configurable. When setting up, ensure you accurately parameterize the device for your specific tank height or desired measurement range (e.g., for a 5-meter height, adjust the range settings accordingly). This ensures precise control and accurate readings for your application.
- Environmental Considerations: While the device has wide temperature compensation, consider the operating environment for the sensor probe. Regular cleaning of the probe can prevent inaccuracies due to buildup.
11. Warranty and Support
For warranty information, technical support, or service inquiries, please contact your point of purchase or the manufacturer directly. Ensure you have your product model (T80) and any relevant purchase details available when seeking support.